Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2018-04-01 → 2018-06-30 |
| MCL | Health-based | Resolved | 2018-04-01 → 2018-06-30 |
| MCL | Health-based | Resolved | 2018-04-01 → 2018-06-30 |
| MCL | Health-based | Resolved | 2018-04-01 → 2018-06-30 |
| RPT | Monitoring | Resolved | 2023-12-11 |
| RPT | Monitoring | Resolved | 2023-12-11 |
| MR | Monitoring | Resolved | 2023-04-19 |
| MR | Monitoring | Resolved | 2023-04-19 |
| MR | Monitoring | Resolved | 2023-04-19 |
| MR | Monitoring | Resolved | 2023-04-01 → 2023-06-30 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Chloroform | 11.58 µg/L No EPA limit set
worst single sample: 19 µg/L | 125/133 | SYR4 | 2012–2019 |
| TTHM | 16.91 µg/L 21% of the EPA limit 80 µg/L
worst single sample: 26 µg/L | 119/120 | SYR4 | 2012–2019 |
| Bromodichloromethane | 4.225 µg/L No EPA limit set
worst single sample: 5.2 µg/L | 112/133 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 6.6915 µg/L 11% of the EPA limit 60 µg/L
worst single sample: 7.8 µg/L | 90/120 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 4.704 µg/L No EPA limit set
worst single sample: 6.95 µg/L | 85/120 | SYR4 | 2012–2019 |
| Copper | 178.8 µg/L 14% of the EPA limit 1300 µg/L
worst single sample: 300 µg/L | 74/97 | SYR4 | 2012–2018 |
| Dibromochloromethane | 1.97 µg/L No EPA limit set
worst single sample: 2.7 µg/L | 74/133 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 1.7965 µg/L No EPA limit set
worst single sample: 2.1 µg/L | 30/120 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 5.6045 µg/L No EPA limit set
worst single sample: 7.33 µg/L | 18/120 | SYR4 | 2012–2019 |
| Lead | 0.00040 mg/L 2.7% of the EPA limit 0.0150 mg/L | 15/15 | LCR | 2024 |
| Nitrate-Nitrite | 2776 µg/L 28% of the EPA limit 10000 µg/L
worst single sample: 3070 µg/L | 15/21 | SYR4 | 2013–2019 |
| Combined Radium (-226 And -228) | 7.81 pCi/L 156% of the EPA limit, at the 95th percentile of samples — 5 pCi/L
worst single sample: 9.5 pCi/L | 14/16 | SYR4 | 2014–2019 |
| Gross Alpha, Excl. Radon And U | 14.56 pCi/L 97% of the EPA limit 15 pCi/L
worst single sample: 17.5 pCi/L | 13/14 | SYR4 | 2014–2018 |
| Lead | 4.8 µg/L 32% of the EPA limit 15 µg/L
worst single sample: 6 µg/L | 9/90 | SYR4 | 2012–2018 |
| Barium | 90 µg/L 4.5% of the EPA limit 2000 µg/L | 6/6 | SYR4 | 2014–2017 |
| Bromoform | 0.7250 µg/L No EPA limit set
worst single sample: 0.8000 µg/L | 6/133 | SYR4 | 2012–2019 |
| Fluoride | 70 µg/L 1.8% of the EPA limit 4000 µg/L | 6/13 | SYR4 | 2013–2017 |
| Chromium | 1 µg/L 1% of the EPA limit 100 µg/L | 4/6 | SYR4 | 2014–2017 |
| Monobromoacetic Acid | 2.07 µg/L No EPA limit set
worst single sample: 2.15 µg/L | 3/120 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 2.919 µg/L No EPA limit set
worst single sample: 2.99 µg/L | 2/120 | SYR4 | 2012–2019 |
| Nitrate | 1400 µg/L 14% of the EPA limit 10000 µg/L | 2/6 | SYR4 | 2012 |
| Cyanide | 4 µg/L 2% of the EPA limit 200 µg/L | 1/6 | SYR4 | 2014–2017 |
| Di(2-ethylhexyl) Adipate | 0.0740 µg/L 0% of the EPA limit 400 µg/L | 1/1 | SYR4 | 2013 |
| Di(2-ethylhexyl) Phthalate | 0.1690 µg/L 2.8% of the EPA limit 6 µg/L | 1/1 | SYR4 | 2013 |
77 contaminants tested, none detected
Utility contact
Frequently asked questions about Manchester Twp Water Utility - Eastern
Is Manchester Twp Water Utility - Eastern tap water safe to drink?
EPA monitoring detected 27 contaminants in Manchester Twp Water Utility - Eastern's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Manchester Twp Water Utility - Eastern's water?
EPA monitoring detected Chloroform, TTHM, Bromodichloromethane, Total Haloacetic Acids (HAA5), Dichloroacetic Acid, and others. The full list with the level and data source for each is above.
How many people does Manchester Twp Water Utility - Eastern serve?
Manchester Twp Water Utility - Eastern reports serving 23,980 people in New Jersey, per its EPA record.
Has Manchester Twp Water Utility - Eastern had any water quality violations?
The EPA has 72 violations on file for Manchester Twp Water Utility - Eastern, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?