← New Jersey

Tap water quality report

Lakewood Twp Mua

EPA monitoring tested this supplier for 99 contaminants and detected 33. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

99
contaminants tested
33
detected
27,614
people served
7
health-based violations
Water source
SWP
Ownership
Local government
Counties served
Ocean

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

7
health-based violations
81
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2002-03-01 → 2002-03-31
MCL Health-based Resolved 2002-03-01 → 2002-03-31
MCL Health-based Resolved 2002-03-01 → 2002-03-31
MCL Health-based Resolved 2002-03-01 → 2002-03-31
MCL Health-based Resolved 2000-06-01 → 2000-06-30
MCL Health-based Resolved 2000-06-01 → 2000-06-30
MCL Health-based Resolved 2000-06-01 → 2000-06-30
Other Monitoring Resolved 2024-07-01
Other Monitoring Resolved 2024-07-01
MR Monitoring Resolved 2021-12-01 → 2021-12-31

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
PFOA 0.0115 µg/L 12/18 2024
Pfhxa 0.0262 µg/L 10/18 2024
Pfpea 0.0338 µg/L 9/18 2024
PFBS 0.0106 µg/L 6/18 2024
6:2 Fts 0.0210 µg/L 1/18 2024
Pfba 0.0115 µg/L 1/18 2024
Pfhpa 0.0118 µg/L 1/18 2024

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Bromodichloromethane
10.6675 µg/L
No EPA limit set
worst single sample: 13.5 µg/L
126/126 SYR4 2012–2019
Chloroform
27.275 µg/L
No EPA limit set
worst single sample: 39.4 µg/L
126/126 SYR4 2012–2019
TTHM
41.225 µg/L 52%
of the EPA limit 80 µg/L
worst single sample: 47.9 µg/L
126/126 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
31.195 µg/L 52%
of the EPA limit 60 µg/L
worst single sample: 42.8 µg/L
126/126 SYR4 2012–2019
Dibromochloromethane
6.488 µg/L
No EPA limit set
worst single sample: 8.12 µg/L
124/126 SYR4 2012–2019
Dichloroacetic Acid
11.355 µg/L
No EPA limit set
worst single sample: 18.48 µg/L
124/126 SYR4 2012–2019
Monochloroacetic Acid
11.4 µg/L
No EPA limit set
worst single sample: 16.8 µg/L
109/126 SYR4 2012–2019
Trichloroacetic Acid
10.812 µg/L
No EPA limit set
worst single sample: 18.5 µg/L
109/126 SYR4 2012–2019
Dibromoacetic Acid
2.6805 µg/L
No EPA limit set
worst single sample: 8.67 µg/L
92/126 SYR4 2012–2019
Bromoform
2.279 µg/L
No EPA limit set
worst single sample: 3.94 µg/L
74/126 SYR4 2012–2019
Copper
126.45 µg/L 9.7%
of the EPA limit 1300 µg/L
worst single sample: 144 µg/L
60/97 SYR4 2012–2019
Monobromoacetic Acid
6.0885 µg/L
No EPA limit set
worst single sample: 16.1 µg/L
34/126 SYR4 2012–2019
Nitrate
1496.5 µg/L 15%
of the EPA limit 10000 µg/L
worst single sample: 1500 µg/L
22/82 SYR4 2012–2019
Lead
0.0021 mg/L 14%
of the EPA limit 0.0150 mg/L
21/21 LCR 2025
Dichloromethane
0.3810 µg/L 7.6%
of the EPA limit 5 µg/L
worst single sample: 0.4800 µg/L
12/59 SYR4 2012–2019
Lead
123.8 µg/L 825%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 137 µg/L
12/91 SYR4 2013–2019
Combined Radium (-226 And -228)
3.85 pCi/L 77%
of the EPA limit 5 pCi/L
11/21 SYR4 2014–2019
Barium
373.28 µg/L 19%
of the EPA limit 2000 µg/L
worst single sample: 626 µg/L
10/10 SYR4 2014–2017
Gross Alpha, Excl. Radon And U
7.6108 pCi/L 51%
of the EPA limit 15 pCi/L
worst single sample: 8.51 pCi/L
5/15 SYR4 2014–2018
Mercury
0.2205 µg/L 11%
of the EPA limit 2 µg/L
worst single sample: 0.2400 µg/L
4/41 SYR4 2012–2019
Ethylbenzene
0.2900 µg/L 0%
of the EPA limit 700 µg/L
worst single sample: 0.3000 µg/L
3/59 SYR4 2012–2019
Arsenic
1.6 µg/L 16%
of the EPA limit 10 µg/L
1/10 SYR4 2014–2017
Combined Uranium
1.5645 µg/L 5.2%
of the EPA limit 30 µg/L
1/21 SYR4 2014–2019
Fluoride
100 µg/L 2.5%
of the EPA limit 4000 µg/L
1/16 SYR4 2012–2017
Toluene
0.1100 µg/L 0%
of the EPA limit 1000 µg/L
1/59 SYR4 2012–2019
Xylenes, Total
1.32 µg/L 0%
of the EPA limit 10000 µg/L
1/59 SYR4 2012–2019
66 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbon TetrachlorideChromiumDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMethoxychlorNetfosaaNfdhaNmefosaaPfdaPfdoaPfeesaPfhpsPFHXSPfmbaPfmpaPFNAPFOSPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
FLANEBAUM, JUSTIN
Phone
732-363-4422

Frequently asked questions about Lakewood Twp Mua

Is Lakewood Twp Mua tap water safe to drink?

EPA monitoring detected 33 contaminants in Lakewood Twp Mua's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Lakewood Twp Mua's water?

EPA monitoring detected Bromodichloromethane, Chloroform, TTHM, Total Haloacetic Acids (HAA5), Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does Lakewood Twp Mua serve?

Lakewood Twp Mua reports serving 27,614 people in New Jersey, per its EPA record.

Has Lakewood Twp Mua had any water quality violations?

The EPA has 81 violations on file for Lakewood Twp Mua, of which 7 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.