← New Jersey

Tap water quality report

Mount Olive Twp W D Main

EPA monitoring tested this supplier for 84 contaminants and detected 24. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

84
contaminants tested
24
detected
7,887
people served
15
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Morris

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

15
health-based violations
635
violations on file
9
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2024-08-30
TT Health-based Resolved 2024-08-30
TT Health-based Resolved 2024-08-30
MCL Health-based Resolved 2024-08-01 → 2024-08-31
MCL Health-based Resolved 2024-08-01 → 2024-08-31
MCL Health-based Resolved 2024-08-01 → 2024-08-31
MCL Health-based Resolved 2024-08-01 → 2024-08-31
MCL Health-based Resolved 2024-08-01 → 2024-08-31
MCL Health-based Resolved 2006-04-01 → 2006-06-30
MCL Health-based Resolved 1997-09-01 → 1997-09-30

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfhxa 0.0038 µg/L 6/6 2023
PFOA 0.0064 µg/L 6/6 2023
PFOS 0.0050 µg/L 6/6 2023
Pfpea 0.0052 µg/L 6/6 2023

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
387.65 µg/L 30%
of the EPA limit 1300 µg/L
worst single sample: 715 µg/L
60/68 SYR4 2012–2018
Nitrate-Nitrite
3322.5 µg/L 33%
of the EPA limit 10000 µg/L
worst single sample: 3550 µg/L
24/24 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
20/20 LCR 2025
Lead
4.3 µg/L 29%
of the EPA limit 15 µg/L
worst single sample: 5 µg/L
15/60 SYR4 2012–2018
Bromoform
1.14 µg/L
No EPA limit set
worst single sample: 1.2 µg/L
13/74 SYR4 2012–2019
Dibromochloromethane
2.05 µg/L
No EPA limit set
worst single sample: 3 µg/L
11/74 SYR4 2012–2019
TTHM
6.85 µg/L 8.6%
of the EPA limit 80 µg/L
worst single sample: 11 µg/L
11/19 SYR4 2012–2019
Barium
57 µg/L 2.9%
of the EPA limit 2000 µg/L
8/8 SYR4 2012–2018
Tetrachloroethylene
1.025 µg/L 21%
of the EPA limit 5 µg/L
worst single sample: 1.2 µg/L
8/55 SYR4 2012–2019
Nitrate
3160 µg/L 32%
of the EPA limit 10000 µg/L
6/6 SYR4 2013–2014
Chromium
1 µg/L 1%
of the EPA limit 100 µg/L
5/8 SYR4 2012–2018
Combined Radium (-226 And -228)
3.106 pCi/L 62%
of the EPA limit 5 pCi/L
worst single sample: 3.3 pCi/L
5/7 SYR4 2012–2018
Bromodichloromethane
3.6 µg/L
No EPA limit set
worst single sample: 3.9 µg/L
3/74 SYR4 2012–2019
Chloroform
3.22 µg/L
No EPA limit set
worst single sample: 3.5 µg/L
3/74 SYR4 2012–2019
Cyanide
3 µg/L 1.5%
of the EPA limit 200 µg/L
2/9 SYR4 2012–2018
Fluoride
50 µg/L 1.3%
of the EPA limit 4000 µg/L
2/14 SYR4 2012–2018
Dibromoacetic Acid
1.5 µg/L
No EPA limit set
1/19 SYR4 2012–2019
Dichloroacetic Acid
4.4 µg/L
No EPA limit set
1/19 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
5.9 µg/L 9.8%
of the EPA limit 60 µg/L
1/19 SYR4 2012–2019
Xylenes, Total
0.5000 µg/L 0%
of the EPA limit 10000 µg/L
1/55 SYR4 2012–2019
60 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicBenzeneBeryllium, TotalChlorobenzeneCadmiumCarbon TetrachlorideCombined UraniumDichloromethaneEthylene DibromideEthylbenzeneGross Alpha, Excl. Radon And UHfpo-DaMercuryMonobromoacetic AcidMonochloroacetic AcidNetfosaaNfdhaNmefosaaNitritePfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPFHXSPfmbaPfmpaPFNAPfpesPftaPftrdaPfunaSeleniumStyreneThallium, TotalTolueneTrichloroacetic AcidTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
LATA, MICHAEL J
Phone
973-584-7086

Frequently asked questions about Mount Olive Twp W D Main

Is Mount Olive Twp W D Main tap water safe to drink?

EPA monitoring detected 24 contaminants in Mount Olive Twp W D Main's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Mount Olive Twp W D Main's water?

EPA monitoring detected Copper, Nitrate-Nitrite, Lead, Lead, Bromoform, and others. The full list with the level and data source for each is above.

How many people does Mount Olive Twp W D Main serve?

Mount Olive Twp W D Main reports serving 7,887 people in New Jersey, per its EPA record.

Has Mount Olive Twp W D Main had any water quality violations?

The EPA has 635 violations on file for Mount Olive Twp W D Main, of which 15 are health-based (a contaminant limit or required treatment was breached) and 9 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.