← New Jersey

Tap water quality report

Southeast Morris County Mua

EPA monitoring tested this supplier for 102 contaminants and detected 39. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

102
contaminants tested
39
detected
62,349
people served
8
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Morris

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

8
health-based violations
529
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2018-10-01 → 2018-12-31
MCL Health-based Resolved 2018-10-01 → 2018-12-31
MCL Health-based Resolved 2018-10-01 → 2018-12-31
MCL Health-based Resolved 2018-10-01 → 2018-12-31
MCL Health-based Resolved 2018-07-01 → 2018-09-30
MCL Health-based Resolved 2018-07-01 → 2018-09-30
MCL Health-based Resolved 2018-07-01 → 2018-09-30
MCL Health-based Resolved 2018-07-01 → 2018-09-30
MR Monitoring Archived 2025-12-01 → 2025-12-31
MR Monitoring Archived 2025-12-01 → 2025-12-31

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
PFOA 0.0121 µg/L 12/22 2023
Pfhxa 0.0092 µg/L 9/22 2023
Pfpea 0.0104 µg/L 9/22 2023
Pfba 0.0157 µg/L 5/22 2023
PFOS 0.0068 µg/L 5/22 2023
PFBS 0.0044 µg/L 4/22 2023
PFHXS 0.0071 µg/L 3/22 2023
Pfhpa 0.0031 µg/L 1/22 2023

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
1074 µg/L 83%
of the EPA limit 1300 µg/L
worst single sample: 2180 µg/L
334/341 SYR4 2012–2019
Dibromochloromethane
13.8 µg/L
No EPA limit set
worst single sample: 19.8 µg/L
321/405 SYR4 2012–2019
Chloroform
62.125 µg/L
No EPA limit set
worst single sample: 77.4 µg/L
306/405 SYR4 2012–2019
Bromodichloromethane
23.55 µg/L
No EPA limit set
worst single sample: 35.7 µg/L
296/405 SYR4 2012–2019
Nitrate
3500 µg/L 35%
of the EPA limit 10000 µg/L
worst single sample: 5500 µg/L
256/282 SYR4 2012–2019
TTHM
84.265 µg/L 105%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 110.1 µg/L
250/250 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
52 µg/L 87%
of the EPA limit 60 µg/L
worst single sample: 70 µg/L
247/250 SYR4 2012–2019
Trichloroacetic Acid
34.88 µg/L
No EPA limit set
worst single sample: 42 µg/L
245/250 SYR4 2012–2019
Dichloroacetic Acid
18.85 µg/L
No EPA limit set
worst single sample: 33 µg/L
244/250 SYR4 2012–2019
Bromoform
2.6 µg/L
No EPA limit set
worst single sample: 3.8 µg/L
155/405 SYR4 2012–2019
Lead
10.55 µg/L 70%
of the EPA limit 15 µg/L
worst single sample: 283 µg/L
131/263 SYR4 2014–2019
Nitrate-Nitrite
3460 µg/L 35%
of the EPA limit 10000 µg/L
worst single sample: 5500 µg/L
129/141 SYR4 2012–2019
Dibromoacetic Acid
3.51 µg/L
No EPA limit set
worst single sample: 4.8 µg/L
90/250 SYR4 2012–2019
Barium
113.8 µg/L 5.7%
of the EPA limit 2000 µg/L
worst single sample: 530 µg/L
82/82 SYR4 2012–2019
Lead
0.0015 mg/L 10%
of the EPA limit 0.0150 mg/L
30/30 LCR 2025
Arsenic
1.36 µg/L 14%
of the EPA limit 10 µg/L
worst single sample: 1.4 µg/L
9/82 SYR4 2012–2019
Tetrachloroethylene
0.6580 µg/L 13%
of the EPA limit 5 µg/L
worst single sample: 0.6900 µg/L
9/157 SYR4 2012–2019
Chromium
8.325 µg/L 8.3%
of the EPA limit 100 µg/L
worst single sample: 12 µg/L
8/82 SYR4 2012–2019
Monochloroacetic Acid
4.22 µg/L
No EPA limit set
worst single sample: 4.5 µg/L
8/250 SYR4 2012–2019
Fluoride
212.5 µg/L 5.3%
of the EPA limit 4000 µg/L
worst single sample: 230 µg/L
6/82 SYR4 2012–2019
Combined Uranium
3.804 µg/L 13%
of the EPA limit 30 µg/L
worst single sample: 3.98 µg/L
5/10 SYR4 2014–2017
Nitrite
30 µg/L 3%
of the EPA limit 1000 µg/L
4/141 SYR4 2012–2019
Di(2-ethylhexyl) Phthalate
0.1260 µg/L 2.1%
of the EPA limit 6 µg/L
worst single sample: 0.1300 µg/L
3/6 SYR4 2012–2018
1,2-Dichloroethane
0.5950 µg/L 12%
of the EPA limit 5 µg/L
worst single sample: 0.6000 µg/L
2/157 SYR4 2012–2019
Mercury
0.1950 µg/L 9.8%
of the EPA limit 2 µg/L
worst single sample: 0.2000 µg/L
2/82 SYR4 2012–2019
Selenium
2.095 µg/L 4.2%
of the EPA limit 50 µg/L
worst single sample: 2.1 µg/L
2/82 SYR4 2012–2019
cis-1,2-Dichloroethylene
0.9950 µg/L 1.4%
of the EPA limit 70 µg/L
worst single sample: 1 µg/L
2/157 SYR4 2012–2019
Chlorobenzene
0.6000 µg/L 0.6%
of the EPA limit 100 µg/L
1/157 SYR4 2012–2019
Combined Radium (-226 And -228)
1.1 pCi/L 22%
of the EPA limit 5 pCi/L
1/10 SYR4 2014–2017
Gross Alpha, Excl. Radon And U
1.88 pCi/L 13%
of the EPA limit 15 pCi/L
1/6 SYR4 2014–2017
Trichloroethylene
0.5600 µg/L 11%
of the EPA limit 5 µg/L
1/157 SYR4 2012–2019
63 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalCyanideCadmiumCarbon TetrachlorideDichloromethaneDi(2-ethylhexyl) AdipateDinosebEthylene DibromideEndrinEthylbenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMethoxychlorMonobromoacetic AcidNetfosaaNfdhaNmefosaaPfdaPfdoaPfeesaPfhpsPfmbaPfmpaPFNAPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneThallium, TotalTolueneVinyl ChlorideXylenes, TotalLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
SASKOWITZ, DREW
Phone
973-476-4341

Frequently asked questions about Southeast Morris County Mua

Is Southeast Morris County Mua tap water safe to drink?

EPA monitoring detected 39 contaminants in Southeast Morris County Mua's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Southeast Morris County Mua's water?

EPA monitoring detected Copper, Dibromochloromethane, Chloroform, Bromodichloromethane, Nitrate, and others. The full list with the level and data source for each is above.

How many people does Southeast Morris County Mua serve?

Southeast Morris County Mua reports serving 62,349 people in New Jersey, per its EPA record.

Has Southeast Morris County Mua had any water quality violations?

The EPA has 529 violations on file for Southeast Morris County Mua, of which 8 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.