← New Jersey

Tap water quality report

Veolia Water New Jersey Matchaponix

EPA monitoring tested this supplier for 67 contaminants and detected 20. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

67
contaminants tested
20
detected
0
people served
1
health-based violations
Water source
Surface water
Ownership
Private
Counties served
Monmouth

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

1
health-based violations
15
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 1996-01-01 → 1996-12-31
MR Monitoring Archived 2025-08-01 → 2025-08-31
MR Monitoring Archived 2025-08-01 → 2025-08-31
MR Monitoring Resolved 2024-09-01 → 2024-09-30
MR Monitoring Resolved 2024-09-01 → 2024-09-30
MR Monitoring Resolved 2024-09-01 → 2024-09-30
MR Monitoring Resolved 2018-06-01 → 2018-06-30
MR Monitoring Resolved 2018-06-01 → 2018-06-30
MR Monitoring Resolved 2005-05-01 → 2005-05-31
MR Monitoring Resolved 2005-05-01 → 2005-05-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Bromodichloromethane
21.665 µg/L
No EPA limit set
worst single sample: 31.5 µg/L
96/96 SYR4 2012–2017
Chloroform
41.1 µg/L
No EPA limit set
worst single sample: 70.8 µg/L
96/96 SYR4 2012–2017
Dibromochloromethane
12.415 µg/L
No EPA limit set
worst single sample: 18.26 µg/L
96/96 SYR4 2012–2017
TTHM
76.2 µg/L 95%
of the EPA limit 80 µg/L
worst single sample: 110.3 µg/L
96/96 SYR4 2012–2017
Total Haloacetic Acids (HAA5)
46.75 µg/L 78%
of the EPA limit 60 µg/L
worst single sample: 57 µg/L
96/96 SYR4 2012–2017
Dichloroacetic Acid
18.22 µg/L
No EPA limit set
worst single sample: 30 µg/L
93/96 SYR4 2012–2017
Dibromoacetic Acid
6.465 µg/L
No EPA limit set
worst single sample: 7.85 µg/L
91/96 SYR4 2012–2017
Trichloroacetic Acid
15.36 µg/L
No EPA limit set
worst single sample: 20.2 µg/L
89/96 SYR4 2012–2017
Monochloroacetic Acid
17.175 µg/L
No EPA limit set
worst single sample: 21.8 µg/L
76/96 SYR4 2012–2017
Bromoform
1.974 µg/L
No EPA limit set
worst single sample: 2.42 µg/L
68/96 SYR4 2012–2017
Monobromoacetic Acid
12.08 µg/L
No EPA limit set
worst single sample: 21.8 µg/L
49/96 SYR4 2012–2017
Nitrate
800 µg/L 8%
of the EPA limit 10000 µg/L
18/18 SYR4 2012–2019
Nitrate-Nitrite
800 µg/L 8%
of the EPA limit 10000 µg/L
9/9 SYR4 2012–2019
Di(2-ethylhexyl) Phthalate
0.2930 µg/L 4.9%
of the EPA limit 6 µg/L
worst single sample: 0.3100 µg/L
3/5 SYR4 2012–2018
Barium
286.5 µg/L 14%
of the EPA limit 2000 µg/L
worst single sample: 300 µg/L
2/8 SYR4 2012–2019
2,4-D
0.6890 µg/L 1%
of the EPA limit 70 µg/L
1/4 SYR4 2012–2018
Beryllium, Total
0.1000 µg/L 2.5%
of the EPA limit 4 µg/L
1/8 SYR4 2012–2019
Copper
30 µg/L 2.3%
of the EPA limit 1300 µg/L
1/8 SYR4 2012–2019
Combined Radium (-226 And -228)
1.5 pCi/L 30%
of the EPA limit 5 pCi/L
1/1 SYR4 2017
Pentachlorophenol
0.0211 µg/L 2.1%
of the EPA limit 1 µg/L
1/4 SYR4 2012–2018
47 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane2,4,5-TPAntimony, TotalArsenicAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneChlorobenzeneCyanideCadmiumCarbon TetrachlorideChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDinosebEndrinEthylbenzeneFluorideHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNitritePicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
DE SHAW, JOHN
Phone
732-446-5102

Frequently asked questions about Veolia Water New Jersey Matchaponix

Is Veolia Water New Jersey Matchaponix tap water safe to drink?

EPA monitoring detected 20 contaminants in Veolia Water New Jersey Matchaponix's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Veolia Water New Jersey Matchaponix's water?

EPA monitoring detected Bromodichloromethane, Chloroform, Dibromochloromethane, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.

How many people does Veolia Water New Jersey Matchaponix serve?

Veolia Water New Jersey Matchaponix reports serving 0 people in New Jersey, per its EPA record.

Has Veolia Water New Jersey Matchaponix had any water quality violations?

The EPA has 15 violations on file for Veolia Water New Jersey Matchaponix, of which 1 is health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.