Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Unaddressed | 2025-12-30 |
| MR | Monitoring | Archived | 2020-01-01 → 2025-12-31 |
| MR | Monitoring | Archived | 2020-01-01 → 2025-12-31 |
| MR | Monitoring | Archived | 2020-01-01 → 2025-12-31 |
| MR | Monitoring | Archived | 2020-01-01 → 2025-12-31 |
| MR | Monitoring | Archived | 2020-01-01 → 2025-12-31 |
| MR | Monitoring | Archived | 2020-01-01 → 2025-12-31 |
| MR | Monitoring | Archived | 2020-01-01 → 2025-12-31 |
| MR | Monitoring | Archived | 2020-01-01 → 2025-12-31 |
| MR | Monitoring | Archived | 2020-01-01 → 2025-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 14/14 | LCR | 2025 |
| Total Haloacetic Acids (HAA5) | 7.619 µg/L 13% of the EPA limit 60 µg/L
worst single sample: 7.78 µg/L | 8/8 | SYR4 | 2012–2019 |
| Copper | 87.5 µg/L 6.7% of the EPA limit 1300 µg/L
worst single sample: 100 µg/L | 6/18 | SYR4 | 2012–2019 |
| Chloroform | 0.9425 µg/L No EPA limit set
worst single sample: 1 µg/L | 6/8 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 3.5525 µg/L No EPA limit set
worst single sample: 4.02 µg/L | 6/8 | SYR4 | 2012–2019 |
| TTHM | 1.075 µg/L 1.3% of the EPA limit 80 µg/L
worst single sample: 1.1 µg/L | 6/8 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 5.554 µg/L No EPA limit set
worst single sample: 6.17 µg/L | 5/8 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 0.8120 µg/L No EPA limit set
worst single sample: 0.8200 µg/L | 5/8 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 1.475 µg/L No EPA limit set
worst single sample: 1.52 µg/L | 3/8 | SYR4 | 2012–2019 |
| Nitrate | 300 µg/L 3% of the EPA limit 10000 µg/L | 2/18 | SYR4 | 2012–2019 |
| Barium | 200 µg/L 10% of the EPA limit 2000 µg/L | 1/3 | SYR4 | 2012–2018 |
| Bromodichloromethane | 0.3000 µg/L No EPA limit set | 1/8 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 1.5 pCi/L 30% of the EPA limit 5 pCi/L | 1/2 | SYR4 | 2012–2018 |
| Dibromoacetic Acid | 2.03 µg/L No EPA limit set | 1/8 | SYR4 | 2012–2019 |
| Fluoride | 200 µg/L 5% of the EPA limit 4000 µg/L | 1/4 | SYR4 | 2012–2018 |
35 contaminants tested, none detected
Utility contact
Frequently asked questions about Winding Brook Mhp System 2
Is Winding Brook Mhp System 2 tap water safe to drink?
EPA monitoring detected 15 contaminants in Winding Brook Mhp System 2's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Winding Brook Mhp System 2's water?
EPA monitoring detected Lead, Total Haloacetic Acids (HAA5), Copper, Chloroform, Dichloroacetic Acid, and others. The full list with the level and data source for each is above.
How many people does Winding Brook Mhp System 2 serve?
Winding Brook Mhp System 2 reports serving 184 people in New Jersey, per its EPA record.
Has Winding Brook Mhp System 2 had any water quality violations?
The EPA has 28 violations on file for Winding Brook Mhp System 2, of which 0 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.