Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2012-01-01 → 2012-03-31 |
| MCL | Health-based | Resolved | 2012-01-01 → 2012-03-31 |
| MCL | Health-based | Resolved | 2012-01-01 → 2012-03-31 |
| MCL | Health-based | Resolved | 2012-01-01 → 2012-03-31 |
| MCL | Health-based | Resolved | 2012-01-01 → 2012-03-31 |
| MCL | Health-based | Resolved | 2006-10-01 → 2006-12-31 |
| MCL | Health-based | Resolved | 2006-10-01 → 2006-12-31 |
| MCL | Health-based | Resolved | 2006-10-01 → 2006-12-31 |
| MCL | Health-based | Resolved | 2001-10-01 → 2001-10-31 |
| MCL | Health-based | Resolved | 1995-04-01 → 1995-04-30 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 234.3 µg/L 18% of the EPA limit 1300 µg/L
worst single sample: 2540 µg/L | 438/445 | SYR4 | 2013–2019 |
| Bromodichloromethane | 10.66 µg/L No EPA limit set
worst single sample: 12.6 µg/L | 143/165 | SYR4 | 2012–2019 |
| Dibromochloromethane | 4.234 µg/L No EPA limit set
worst single sample: 7 µg/L | 143/166 | SYR4 | 2012–2019 |
| TTHM | 45.83 µg/L 57% of the EPA limit 80 µg/L
worst single sample: 69.5 µg/L | 139/140 | SYR4 | 2012–2019 |
| Chloroform | 34.44 µg/L No EPA limit set
worst single sample: 56.6 µg/L | 129/168 | SYR4 | 2012–2019 |
| Bromoform | 4.4 µg/L No EPA limit set
worst single sample: 11.8 µg/L | 81/165 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 31.27 µg/L 52% of the EPA limit 60 µg/L
worst single sample: 43.7 µg/L | 72/140 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 22.045 µg/L No EPA limit set
worst single sample: 29.5 µg/L | 62/140 | SYR4 | 2012–2019 |
| Lead | 40.7 µg/L 271% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 385 µg/L | 59/432 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 14.065 µg/L No EPA limit set
worst single sample: 21.6 µg/L | 58/140 | SYR4 | 2012–2019 |
| Nitrate | 4000 µg/L 40% of the EPA limit 10000 µg/L | 54/72 | SYR4 | 2012–2018 |
| Combined Radium (-226 And -228) | 5.42 pCi/L 108% of the EPA limit, at the 95th percentile of samples — 5 pCi/L
worst single sample: 7 pCi/L | 33/135 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 4000 µg/L 40% of the EPA limit 10000 µg/L
worst single sample: 4100 µg/L | 30/39 | SYR4 | 2012–2019 |
| Lead | 0.0017 mg/L 11% of the EPA limit 0.0150 mg/L | 24/24 | LCR | 2025 |
| Barium | 52.64 µg/L 2.6% of the EPA limit 2000 µg/L
worst single sample: 77.4 µg/L | 9/13 | SYR4 | 2013–2017 |
| Chromium | 8.85 µg/L 8.9% of the EPA limit 100 µg/L
worst single sample: 9.35 µg/L | 9/13 | SYR4 | 2013–2017 |
| Dibromoacetic Acid | 4.3575 µg/L No EPA limit set
worst single sample: 4.76 µg/L | 8/140 | SYR4 | 2012–2019 |
| Arsenic | 2.298 µg/L 23% of the EPA limit 10 µg/L
worst single sample: 2.46 µg/L | 4/14 | SYR4 | 2013–2017 |
| Beryllium, Total | 0.7330 µg/L 18% of the EPA limit 4 µg/L
worst single sample: 0.7400 µg/L | 2/13 | SYR4 | 2013–2017 |
| Selenium | 9.488 µg/L 19% of the EPA limit 50 µg/L
worst single sample: 9.79 µg/L | 2/13 | SYR4 | 2013–2017 |
| Lithium | 20.7 µg/L No EPA limit set | 2/10 | UCMR-5 | 2024 |
| 1,1,1-Trichloroethane | 2.06 µg/L 1% of the EPA limit 200 µg/L | 1/42 | SYR4 | 2012–2019 |
| 1,1-Dichloroethylene | 1.05 µg/L 15% of the EPA limit 7 µg/L | 1/42 | SYR4 | 2012–2019 |
| Cyanide | 24 µg/L 12% of the EPA limit 200 µg/L | 1/13 | SYR4 | 2013–2017 |
| Nitrite | 900 µg/L 90% of the EPA limit 1000 µg/L | 1/34 | SYR4 | 2012–2018 |
70 contaminants tested, none detected
Utility contact
Frequently asked questions about Monroe Twp Utility Department
Is Monroe Twp Utility Department tap water safe to drink?
EPA monitoring detected 32 contaminants in Monroe Twp Utility Department's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Monroe Twp Utility Department's water?
EPA monitoring detected Copper, Bromodichloromethane, Dibromochloromethane, TTHM, Chloroform, and others. The full list with the level and data source for each is above.
How many people does Monroe Twp Utility Department serve?
Monroe Twp Utility Department reports serving 36,000 people in New Jersey, per its EPA record.
Has Monroe Twp Utility Department had any water quality violations?
The EPA has 524 violations on file for Monroe Twp Utility Department, of which 15 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.