← New Jersey

Tap water quality report

Trenton Water Works

EPA monitoring tested this supplier for 100 contaminants and detected 25. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

100
contaminants tested
25
detected
217,000
people served
107
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Mercer

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

107
health-based violations
499
violations on file
7
still open
ViolationTypeStatusPeriod
MCL Health-based Archived 2024-10-01 → 2024-12-31
MCL Health-based Archived 2024-10-01 → 2024-12-31
MCL Health-based Archived 2024-10-01 → 2024-12-31
TT Health-based Resolved 2021-07-01 → 2021-07-31
TT Health-based Resolved 2021-07-01 → 2021-07-31
MCL Health-based Archived 2021-07-01 → 2021-09-30
MCL Health-based Archived 2021-07-01 → 2021-09-30
MCL Health-based Archived 2021-07-01 → 2021-09-30
TT Health-based Resolved 2021-01-01 → 2021-06-30
TT Health-based Resolved 2021-01-01 → 2021-06-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Lead
31.4 µg/L 209%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 1430 µg/L
461/708 SYR4 2012–2019
Copper
145 µg/L 11%
of the EPA limit 1300 µg/L
worst single sample: 640 µg/L
341/715 SYR4 2012–2019
Bromodichloromethane
14.285 µg/L
No EPA limit set
worst single sample: 19.9 µg/L
264/264 SYR4 2012–2019
Chloroform
76.76 µg/L
No EPA limit set
worst single sample: 127 µg/L
264/264 SYR4 2012–2019
Dibromochloromethane
4.683 µg/L
No EPA limit set
worst single sample: 5.95 µg/L
260/264 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
70.04 µg/L 117%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 88.5 µg/L
257/257 SYR4 2012–2019
Dichloroacetic Acid
34.25 µg/L
No EPA limit set
worst single sample: 51.2 µg/L
256/257 SYR4 2012–2019
TTHM
90.95 µg/L 114%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 142 µg/L
256/256 SYR4 2012–2019
Trichloroacetic Acid
41 µg/L
No EPA limit set
worst single sample: 64.2 µg/L
253/257 SYR4 2012–2019
Monochloroacetic Acid
11.09 µg/L
No EPA limit set
worst single sample: 15.2 µg/L
95/257 SYR4 2012–2019
Monobromoacetic Acid
2.63 µg/L
No EPA limit set
worst single sample: 3.44 µg/L
53/257 SYR4 2012–2019
Dibromoacetic Acid
1.168 µg/L
No EPA limit set
worst single sample: 1.21 µg/L
45/257 SYR4 2012–2019
Lead
0.0060 mg/L 40%
of the EPA limit 0.0150 mg/L
34/34 LCR 2026
Nitrate
1300 µg/L 13%
of the EPA limit 10000 µg/L
16/16 SYR4 2012–2019
Fluoride
1284 µg/L 32%
of the EPA limit 4000 µg/L
worst single sample: 1340 µg/L
8/8 SYR4 2012–2019
Barium
327.5 µg/L 16%
of the EPA limit 2000 µg/L
worst single sample: 339 µg/L
6/8 SYR4 2012–2019
Chromium
2.614 µg/L 2.6%
of the EPA limit 100 µg/L
worst single sample: 2.94 µg/L
5/8 SYR4 2012–2019
Di(2-ethylhexyl) Phthalate
0.2910 µg/L 4.9%
of the EPA limit 6 µg/L
worst single sample: 0.3100 µg/L
3/5 SYR4 2012–2018
Arsenic
1.00065 µg/L 10%
of the EPA limit 10 µg/L
worst single sample: 1.04 µg/L
2/8 SYR4 2012–2019
Mercury
0.0959 µg/L 4.8%
of the EPA limit 2 µg/L
worst single sample: 0.0990 µg/L
2/7 SYR4 2013–2019
2,4-D
0.1480 µg/L 0.2%
of the EPA limit 70 µg/L
1/4 SYR4 2012–2018
Atrazine
0.2300 µg/L 7.7%
of the EPA limit 3 µg/L
1/7 SYR4 2012–2018
Benzo(A)Pyrene
0.0200 µg/L 10%
of the EPA limit 0.2000 µg/L
1/6 SYR4 2012–2018
Bromoform
0.8900 µg/L
No EPA limit set
1/264 SYR4 2012–2019
Selenium
2.12 µg/L 4.2%
of the EPA limit 50 µg/L
1/8 SYR4 2012–2019
75 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAsbestosBhc-GammaBenzeneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbon TetrachlorideCombined Radium (-226 And -228)Combined UraniumDichloromethaneDi(2-ethylhexyl) AdipateDinosebEthylene DibromideEndrinEthylbenzeneGross Alpha, Excl. Radon And UHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMethoxychlorNetfosaaNfdhaNmefosaaPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
SEMPLE, SEAN
Phone
609-433-4749
Email
[email protected]

Frequently asked questions about Trenton Water Works

Is Trenton Water Works tap water safe to drink?

EPA monitoring detected 25 contaminants in Trenton Water Works's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Trenton Water Works's water?

EPA monitoring detected Lead, Copper, Bromodichloromethane, Chloroform, Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does Trenton Water Works serve?

Trenton Water Works reports serving 217,000 people in New Jersey, per its EPA record.

Has Trenton Water Works had any water quality violations?

The EPA has 499 violations on file for Trenton Water Works, of which 107 are health-based (a contaminant limit or required treatment was breached) and 7 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.