← New Jersey

Tap water quality report

Aqua Nj - Bunnvale

EPA monitoring tested this supplier for 54 contaminants and detected 27. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

54
contaminants tested
27
detected
252
people served
1
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Hunterdon

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

1
health-based violations
589
violations on file
1
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2002-08-01 → 2002-08-31
MR Monitoring Unaddressed 2023-12-30
MR Monitoring Archived 2023-10-01 → 2024-09-30
MR Monitoring Archived 2023-10-01 → 2024-09-30
MR Monitoring Resolved 2022-07-01 → 2022-09-30
MR Monitoring Resolved 2022-07-01 → 2022-09-30
MR Monitoring Resolved 2022-07-01 → 2022-09-30
MR Monitoring Resolved 2022-07-01 → 2022-09-30
MR Monitoring Resolved 2022-07-01 → 2022-09-30
MR Monitoring Resolved 2022-07-01 → 2022-09-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
4600 µg/L 46%
of the EPA limit 10000 µg/L
48/62 SYR4 2012–2019
Chloroform
11.765 µg/L
No EPA limit set
worst single sample: 12.4 µg/L
28/36 SYR4 2012–2019
Barium
36.8 µg/L 1.8%
of the EPA limit 2000 µg/L
worst single sample: 44 µg/L
23/28 SYR4 2012–2018
Chromium
6.095 µg/L 6.1%
of the EPA limit 100 µg/L
worst single sample: 7 µg/L
22/28 SYR4 2012–2018
Dibromochloromethane
4.295 µg/L
No EPA limit set
worst single sample: 4.9 µg/L
22/36 SYR4 2012–2019
Lead
0.0025 mg/L 17%
of the EPA limit 0.0150 mg/L
22/22 LCR 2023
Bromodichloromethane
6.2 µg/L
No EPA limit set
worst single sample: 6.3 µg/L
21/36 SYR4 2012–2019
Nitrate-Nitrite
4600 µg/L 46%
of the EPA limit 10000 µg/L
21/28 SYR4 2012–2019
TTHM
23.825 µg/L 30%
of the EPA limit 80 µg/L
worst single sample: 23.9 µg/L
16/19 SYR4 2012–2019
Fluoride
1835 µg/L 46%
of the EPA limit 4000 µg/L
worst single sample: 1900 µg/L
14/28 SYR4 2012–2018
Bromoform
1.845 µg/L
No EPA limit set
worst single sample: 1.9 µg/L
12/36 SYR4 2012–2019
Dichloroacetic Acid
3.95 µg/L
No EPA limit set
worst single sample: 5.2 µg/L
11/19 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
6.55 µg/L 11%
of the EPA limit 60 µg/L
worst single sample: 7.8 µg/L
11/19 SYR4 2012–2019
Copper
905 µg/L 70%
of the EPA limit 1300 µg/L
worst single sample: 1400 µg/L
10/40 SYR4 2012–2018
Trichloroacetic Acid
2.15 µg/L
No EPA limit set
worst single sample: 2.3 µg/L
6/19 SYR4 2012–2019
Dibromoacetic Acid
1.2 µg/L
No EPA limit set
5/19 SYR4 2012–2019
Trichloroethylene
0.5640 µg/L 11%
of the EPA limit 5 µg/L
worst single sample: 0.5800 µg/L
5/46 SYR4 2012–2019
Xylenes, Total
2.16 µg/L 0%
of the EPA limit 10000 µg/L
worst single sample: 2.4 µg/L
5/46 SYR4 2012–2019
Gross Alpha, Excl. Radon And U
5.197 pCi/L 35%
of the EPA limit 15 pCi/L
worst single sample: 5.58 pCi/L
3/5 SYR4 2012–2018
Lead
2.59 µg/L 17%
of the EPA limit 15 µg/L
worst single sample: 2.6 µg/L
3/12 SYR4 2014–2017
Combined Uranium
4.854 µg/L 16%
of the EPA limit 30 µg/L
worst single sample: 5.03 µg/L
2/5 SYR4 2012–2018
Nitrite
138.5 µg/L 14%
of the EPA limit 1000 µg/L
worst single sample: 140 µg/L
2/29 SYR4 2012–2019
Toluene
11.75 µg/L 1.2%
of the EPA limit 1000 µg/L
worst single sample: 12.3 µg/L
2/46 SYR4 2012–2019
Arsenic
1.3 µg/L 13%
of the EPA limit 10 µg/L
1/28 SYR4 2012–2018
Combined Radium (-226 And -228)
0.1100 pCi/L 2.2%
of the EPA limit 5 pCi/L
1/5 SYR4 2012–2018
Ethylbenzene
0.5000 µg/L 0.1%
of the EPA limit 700 µg/L
1/46 SYR4 2012–2019
Selenium
1 µg/L 2%
of the EPA limit 50 µg/L
1/28 SYR4 2012–2018
27 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-DichloropropaneAntimony, TotalBenzeneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbon TetrachlorideDichloromethaneEthylene DibromideMercuryMonobromoacetic AcidMonochloroacetic AcidStyreneTetrachloroethyleneThallium, TotalVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
VANIM, ALYSSA
Phone
609-618-3850
Email
[email protected]

Frequently asked questions about Aqua Nj - Bunnvale

Is Aqua Nj - Bunnvale tap water safe to drink?

EPA monitoring detected 27 contaminants in Aqua Nj - Bunnvale's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Aqua Nj - Bunnvale's water?

EPA monitoring detected Nitrate, Chloroform, Barium, Chromium, Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does Aqua Nj - Bunnvale serve?

Aqua Nj - Bunnvale reports serving 252 people in New Jersey, per its EPA record.

Has Aqua Nj - Bunnvale had any water quality violations?

The EPA has 589 violations on file for Aqua Nj - Bunnvale, of which 1 is health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.