Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2005-11-01 → 2005-11-30 |
| MCL | Health-based | Resolved | 2005-11-01 → 2005-11-30 |
| MCL | Health-based | Archived | 2001-08-01 → 2001-08-31 |
| MCL | Health-based | Archived | 2001-08-01 → 2001-08-31 |
| MCL | Health-based | Archived | 2000-05-01 → 2000-05-31 |
| MCL | Health-based | Archived | 2000-01-01 → 2000-01-31 |
| MCL | Health-based | Resolved | 2000-01-01 → 2000-12-31 |
| MCL | Health-based | Resolved | 1994-05-01 → 1994-05-31 |
| MCL | Health-based | Resolved | 1994-05-01 → 1994-05-31 |
| MCL | Health-based | Resolved | 1994-05-01 → 1994-05-31 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Chloroform | 18.427 µg/L No EPA limit set
worst single sample: 25 µg/L | 74/77 | SYR4 | 2012–2019 |
| TTHM | 34.555 µg/L 43% of the EPA limit 80 µg/L
worst single sample: 45 µg/L | 70/71 | SYR4 | 2012–2019 |
| Bromodichloromethane | 9.2575 µg/L No EPA limit set
worst single sample: 12 µg/L | 66/77 | SYR4 | 2012–2019 |
| Copper | 447.2 µg/L 34% of the EPA limit 1300 µg/L
worst single sample: 614 µg/L | 65/65 | SYR4 | 2012–2018 |
| Dibromochloromethane | 7.947 µg/L No EPA limit set
worst single sample: 9.5 µg/L | 63/77 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 12.15 µg/L 20% of the EPA limit 60 µg/L
worst single sample: 23.7 µg/L | 51/71 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 5.6365 µg/L No EPA limit set
worst single sample: 10.6 µg/L | 48/71 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 6.64 µg/L No EPA limit set
worst single sample: 10.7 µg/L | 45/71 | SYR4 | 2012–2019 |
| Lead | 5.038 µg/L 34% of the EPA limit 15 µg/L
worst single sample: 42.1 µg/L | 43/61 | SYR4 | 2012–2018 |
| Bromoform | 2.75 µg/L No EPA limit set
worst single sample: 7.55 µg/L | 36/77 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 2.346 µg/L No EPA limit set
worst single sample: 2.5 µg/L | 30/71 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 27/27 | LCR | 2024 |
| Fluoride | 2340 µg/L 59% of the EPA limit 4000 µg/L | 10/10 | SYR4 | 2012–2018 |
| Barium | 37.375 µg/L 1.9% of the EPA limit 2000 µg/L
worst single sample: 37.5 µg/L | 6/6 | SYR4 | 2012–2018 |
| Nitrate | 780 µg/L 7.8% of the EPA limit 10000 µg/L | 6/32 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 2.204 µg/L No EPA limit set
worst single sample: 2.4 µg/L | 5/71 | SYR4 | 2012–2019 |
| Chromium | 2.81 µg/L 2.8% of the EPA limit 100 µg/L
worst single sample: 2.9 µg/L | 4/6 | SYR4 | 2012–2018 |
| Combined Radium (-226 And -228) | 1.5 pCi/L 30% of the EPA limit 5 pCi/L | 4/4 | SYR4 | 2012–2018 |
| Monobromoacetic Acid | 0.4360 µg/L No EPA limit set
worst single sample: 0.4600 µg/L | 4/71 | SYR4 | 2012–2019 |
| Arsenic | 1.7425 µg/L 17% of the EPA limit 10 µg/L
worst single sample: 1.8 µg/L | 2/6 | SYR4 | 2012–2018 |
| Selenium | 6.28 µg/L 13% of the EPA limit 50 µg/L
worst single sample: 6.5 µg/L | 2/6 | SYR4 | 2012–2018 |
57 contaminants tested, none detected
Utility contact
Frequently asked questions about Pitman Water Department
Is Pitman Water Department tap water safe to drink?
EPA monitoring detected 24 contaminants in Pitman Water Department's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Pitman Water Department's water?
EPA monitoring detected Chloroform, TTHM, Bromodichloromethane, Copper, Dibromochloromethane, and others. The full list with the level and data source for each is above.
How many people does Pitman Water Department serve?
Pitman Water Department reports serving 7,896 people in New Jersey, per its EPA record.
Has Pitman Water Department had any water quality violations?
The EPA has 135 violations on file for Pitman Water Department, of which 17 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.