Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2021-07-01 → 2021-12-31 |
| TT | Health-based | Resolved | 2021-07-01 → 2021-12-31 |
| TT | Health-based | Resolved | 2021-07-01 → 2021-12-31 |
| TT | Health-based | Resolved | 2021-07-01 → 2021-12-31 |
| TT | Health-based | Resolved | 2021-01-01 → 2021-06-30 |
| TT | Health-based | Resolved | 2021-01-01 → 2021-06-30 |
| TT | Health-based | Resolved | 2021-01-01 → 2021-06-30 |
| TT | Health-based | Resolved | 2021-01-01 → 2021-06-30 |
| TT | Health-based | Resolved | 2021-01-01 → 2021-06-30 |
| MCL | Health-based | Resolved | 2014-01-01 → 2014-03-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 7400 µg/L 74% of the EPA limit 10000 µg/L
worst single sample: 10700 µg/L | 56/56 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 4.9775 pCi/L 100% of the EPA limit 5 pCi/L
worst single sample: 8 pCi/L | 36/37 | SYR4 | 2012–2019 |
| Copper | 868.7 µg/L 67% of the EPA limit 1300 µg/L
worst single sample: 1288 µg/L | 30/33 | SYR4 | 2012–2018 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 21/21 | LCR | 2026 |
| Lead | 1.9 µg/L 13% of the EPA limit 15 µg/L
worst single sample: 2.32 µg/L | 21/30 | SYR4 | 2012–2018 |
| Dibromochloromethane | 2.964 µg/L No EPA limit set
worst single sample: 3.66 µg/L | 13/21 | SYR4 | 2012–2019 |
| TTHM | 7.955 µg/L 9.9% of the EPA limit 80 µg/L
worst single sample: 9 µg/L | 12/16 | SYR4 | 2012–2019 |
| Bromoform | 1.665 µg/L No EPA limit set
worst single sample: 1.7 µg/L | 11/21 | SYR4 | 2012–2019 |
| Chloroform | 1.185 µg/L No EPA limit set
worst single sample: 1.19 µg/L | 11/21 | SYR4 | 2012–2019 |
| Bromodichloromethane | 2.212 µg/L No EPA limit set
worst single sample: 2.52 µg/L | 9/21 | SYR4 | 2012–2019 |
| Barium | 153.2 µg/L 7.7% of the EPA limit 2000 µg/L
worst single sample: 154 µg/L | 5/5 | SYR4 | 2012–2018 |
| Arsenic | 0.6510 µg/L 6.5% of the EPA limit 10 µg/L
worst single sample: 0.7000 µg/L | 3/5 | SYR4 | 2012–2018 |
| Beryllium, Total | 0.1280 µg/L 3.2% of the EPA limit 4 µg/L
worst single sample: 0.1300 µg/L | 3/5 | SYR4 | 2012–2018 |
| Cadmium | 0.0590 µg/L 1.2% of the EPA limit 5 µg/L
worst single sample: 0.0600 µg/L | 3/5 | SYR4 | 2012–2018 |
| Chromium | 1.19 µg/L 1.2% of the EPA limit 100 µg/L
worst single sample: 1.2 µg/L | 3/5 | SYR4 | 2012–2018 |
| Selenium | 2.57 µg/L 5.1% of the EPA limit 50 µg/L
worst single sample: 2.7 µg/L | 3/5 | SYR4 | 2012–2018 |
| Combined Uranium | 1.40433 µg/L 4.7% of the EPA limit 30 µg/L
worst single sample: 1.4453 µg/L | 2/2 | SYR4 | 2012–2013 |
| Gross Alpha, Excl. Radon And U | 16.349 pCi/L 109% of the EPA limit, at the 95th percentile of samples — 15 pCi/L
worst single sample: 16.47 pCi/L | 2/2 | SYR4 | 2012–2013 |
| Mercury | 0.0626 µg/L 3.1% of the EPA limit 2 µg/L
worst single sample: 0.0630 µg/L | 2/5 | SYR4 | 2012–2018 |
| Antimony, Total | 0.0500 µg/L 0.8% of the EPA limit 6 µg/L | 1/5 | SYR4 | 2012–2018 |
| Dibromoacetic Acid | 1.98 µg/L No EPA limit set | 1/16 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 0.9400 µg/L No EPA limit set | 1/16 | SYR4 | 2012–2019 |
| Fluoride | 35.5 µg/L 0.9% of the EPA limit 4000 µg/L | 1/8 | SYR4 | 2012–2018 |
| Thallium, Total | 0.0400 µg/L 2% of the EPA limit 2 µg/L | 1/5 | SYR4 | 2012–2018 |
| Total Haloacetic Acids (HAA5) | 2.92 µg/L 4.9% of the EPA limit 60 µg/L | 1/16 | SYR4 | 2012–2019 |
45 contaminants tested, none detected
Utility contact
Frequently asked questions about Newfield Water Department
Is Newfield Water Department tap water safe to drink?
EPA monitoring detected 25 contaminants in Newfield Water Department's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Newfield Water Department's water?
EPA monitoring detected Nitrate, Combined Radium (-226 And -228), Copper, Lead, Lead, and others. The full list with the level and data source for each is above.
How many people does Newfield Water Department serve?
Newfield Water Department reports serving 1,616 people in New Jersey, per its EPA record.
Has Newfield Water Department had any water quality violations?
The EPA has 109 violations on file for Newfield Water Department, of which 20 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.