Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2013-03-01 → 2013-03-31 |
| MCL | Health-based | Resolved | 2013-03-01 → 2013-03-31 |
| MCL | Health-based | Resolved | 2013-03-01 → 2013-03-31 |
| MCL | Health-based | Resolved | 2013-03-01 → 2013-03-31 |
| Other | Monitoring | Resolved | 2013-07-01 |
| Other | Monitoring | Resolved | 2013-07-01 |
| MR | Monitoring | Resolved | 2006-04-01 → 2006-06-30 |
| MR | Monitoring | Resolved | 2006-04-01 → 2006-06-30 |
| MR | Monitoring | Resolved | 2006-04-01 → 2006-06-30 |
| MR | Monitoring | Resolved | 2006-04-01 → 2006-06-30 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Chloroform | 28 µg/L No EPA limit set
worst single sample: 42 µg/L | 98/107 | SYR4 | 2012–2019 |
| Bromodichloromethane | 16.025 µg/L No EPA limit set
worst single sample: 18.3 µg/L | 96/107 | SYR4 | 2012–2019 |
| Dibromochloromethane | 14.32 µg/L No EPA limit set
worst single sample: 21 µg/L | 87/107 | SYR4 | 2012–2019 |
| Copper | 294 µg/L 23% of the EPA limit 1300 µg/L
worst single sample: 381 µg/L | 84/85 | SYR4 | 2012–2018 |
| TTHM | 62 µg/L 78% of the EPA limit 80 µg/L
worst single sample: 68 µg/L | 70/72 | SYR4 | 2012–2019 |
| Bromoform | 14.97 µg/L No EPA limit set
worst single sample: 29.1 µg/L | 59/107 | SYR4 | 2012–2019 |
| Lead | 62.02 µg/L 413% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 102 µg/L | 53/74 | SYR4 | 2012–2018 |
| Total Haloacetic Acids (HAA5) | 13.48 µg/L 22% of the EPA limit 60 µg/L
worst single sample: 23 µg/L | 42/72 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 7.535 µg/L No EPA limit set
worst single sample: 15 µg/L | 40/72 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 6.53 µg/L No EPA limit set
worst single sample: 7.08 µg/L | 38/72 | SYR4 | 2012–2019 |
| Lead | 0.0040 mg/L 27% of the EPA limit 0.0150 mg/L | 19/19 | LCR | 2026 |
| Fluoride | 685.6 µg/L 17% of the EPA limit 4000 µg/L
worst single sample: 700 µg/L | 17/20 | SYR4 | 2012–2018 |
| Nitrate | 6800 µg/L 68% of the EPA limit 10000 µg/L | 14/54 | SYR4 | 2012–2019 |
| Barium | 95.695 µg/L 4.8% of the EPA limit 2000 µg/L
worst single sample: 96.1 µg/L | 10/10 | SYR4 | 2012–2018 |
| Dibromoacetic Acid | 1.8945 µg/L No EPA limit set
worst single sample: 2.07 µg/L | 10/72 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 4.67 pCi/L 93% of the EPA limit 5 pCi/L
worst single sample: 5.51 pCi/L | 9/11 | SYR4 | 2012–2018 |
| Arsenic | 3.73 µg/L 37% of the EPA limit 10 µg/L
worst single sample: 4 µg/L | 7/10 | SYR4 | 2012–2018 |
| Selenium | 19.72 µg/L 39% of the EPA limit 50 µg/L
worst single sample: 22.7 µg/L | 5/10 | SYR4 | 2012–2018 |
| Chromium | 3.4595 µg/L 3.5% of the EPA limit 100 µg/L
worst single sample: 3.6 µg/L | 2/10 | SYR4 | 2012–2018 |
| Monochloroacetic Acid | 1.0995 µg/L No EPA limit set
worst single sample: 1.11 µg/L | 2/72 | SYR4 | 2012–2019 |
| Lithium | 12 µg/L No EPA limit set | 2/10 | UCMR-5 | 2025 |
| Combined Uranium | 0.2235 µg/L 0.7% of the EPA limit 30 µg/L | 1/1 | SYR4 | 2012 |
| Gross Alpha, Excl. Radon And U | 3.87 pCi/L 26% of the EPA limit 15 pCi/L | 1/1 | SYR4 | 2012 |
| Monobromoacetic Acid | 0.5000 µg/L No EPA limit set | 1/72 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 679 µg/L 6.8% of the EPA limit 10000 µg/L | 1/1 | SYR4 | 2012 |
75 contaminants tested, none detected
Utility contact
Frequently asked questions about East Greenwich Twp Water Dept
Is East Greenwich Twp Water Dept tap water safe to drink?
EPA monitoring detected 30 contaminants in East Greenwich Twp Water Dept's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in East Greenwich Twp Water Dept's water?
EPA monitoring detected Chloroform, Bromodichloromethane, Dibromochloromethane, Copper, TTHM, and others. The full list with the level and data source for each is above.
How many people does East Greenwich Twp Water Dept serve?
East Greenwich Twp Water Dept reports serving 9,900 people in New Jersey, per its EPA record.
Has East Greenwich Twp Water Dept had any water quality violations?
The EPA has 41 violations on file for East Greenwich Twp Water Dept, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.