← New Jersey

Tap water quality report

Vineland Water & Sewer Utility

EPA monitoring tested this supplier for 82 contaminants and detected 35. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

82
contaminants tested
35
detected
36,250
people served
130
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Cumberland

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

130
health-based violations
725
violations on file
8
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2023-07-01 → 2023-12-31
TT Health-based Resolved 2023-07-01 → 2023-12-31
TT Health-based Resolved 2023-07-01 → 2023-12-31
TT Health-based Resolved 2023-07-01 → 2023-12-31
MCL Health-based Resolved 2014-07-01 → 2014-09-30
MCL Health-based Resolved 2014-07-01 → 2014-09-30
MCL Health-based Resolved 2014-07-01 → 2014-09-30
MCL Health-based Resolved 2014-07-01 → 2014-09-30
MCL Health-based Resolved 2014-07-01 → 2014-09-30
MCL Health-based Resolved 2014-04-01 → 2014-06-30

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
PFOA 0.0094 µg/L 12/19 2025
Pfhxa 0.0048 µg/L 7/19 2025
Pfpea 0.0044 µg/L 7/19 2025
PFOS 0.0108 µg/L 4/19 2025
PFHXS 0.0030 µg/L 1/19 2025

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
8355 µg/L 84%
of the EPA limit 10000 µg/L
worst single sample: 9360 µg/L
236/240 SYR4 2012–2019
Dibromochloromethane
3.67 µg/L
No EPA limit set
worst single sample: 9.09 µg/L
204/300 SYR4 2012–2019
Bromoform
5.4555 µg/L
No EPA limit set
worst single sample: 8.82 µg/L
178/301 SYR4 2012–2019
Copper
211.8 µg/L 16%
of the EPA limit 1300 µg/L
worst single sample: 389 µg/L
160/203 SYR4 2012–2019
Bromodichloromethane
1.944 µg/L
No EPA limit set
worst single sample: 4.27 µg/L
155/300 SYR4 2012–2019
TTHM
10.7785 µg/L 13%
of the EPA limit 80 µg/L
worst single sample: 21.37 µg/L
150/184 SYR4 2012–2019
Chloroform
0.8700 µg/L
No EPA limit set
worst single sample: 1.76 µg/L
127/299 SYR4 2012–2019
Combined Radium (-226 And -228)
4.3 pCi/L 86%
of the EPA limit 5 pCi/L
worst single sample: 5.13 pCi/L
86/171 SYR4 2012–2019
Lead
5.335 µg/L 36%
of the EPA limit 15 µg/L
worst single sample: 92.4 µg/L
78/173 SYR4 2014–2019
Dibromoacetic Acid
1.8855 µg/L
No EPA limit set
worst single sample: 2.89 µg/L
62/184 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
2.339 µg/L 3.9%
of the EPA limit 60 µg/L
worst single sample: 2.89 µg/L
62/184 SYR4 2012–2019
Trichloroethylene
0.9000 µg/L 18%
of the EPA limit 5 µg/L
44/211 SYR4 2012–2019
Barium
159.15 µg/L 8%
of the EPA limit 2000 µg/L
worst single sample: 163 µg/L
22/23 SYR4 2012–2017
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
22/22 LCR 2025
Mercury
2.19 µg/L 110%
of the EPA limit, at the 95th percentile of samples — 2 µg/L
worst single sample: 2.4 µg/L
22/29 SYR4 2012–2019
Ethylene Dibromide
0.1270 µg/L 254%
of the EPA limit, at the 95th percentile of samples — 0.0500 µg/L
worst single sample: 0.1400 µg/L
21/170 SYR4 2012–2019
Selenium
2.665 µg/L 5.3%
of the EPA limit 50 µg/L
worst single sample: 3.9 µg/L
20/23 SYR4 2012–2017
Tetrachloroethylene
0.5250 µg/L 11%
of the EPA limit 5 µg/L
worst single sample: 0.6600 µg/L
19/211 SYR4 2012–2019
Arsenic
2.79 µg/L 28%
of the EPA limit 10 µg/L
worst single sample: 3 µg/L
15/33 SYR4 2012–2019
Cadmium
0.4480 µg/L 9%
of the EPA limit 5 µg/L
worst single sample: 0.8000 µg/L
12/23 SYR4 2012–2017
1,2-Dichloroethane
0.8050 µg/L 16%
of the EPA limit 5 µg/L
worst single sample: 0.8700 µg/L
11/211 SYR4 2012–2019
Thallium, Total
0.2400 µg/L 12%
of the EPA limit 2 µg/L
7/22 SYR4 2012–2017
Beryllium, Total
0.1225 µg/L 3.1%
of the EPA limit 4 µg/L
worst single sample: 0.1300 µg/L
6/23 SYR4 2012–2017
Dichloroacetic Acid
0.6020 µg/L
No EPA limit set
worst single sample: 0.6500 µg/L
5/184 SYR4 2012–2019
Fluoride
44.98 µg/L 1.1%
of the EPA limit 4000 µg/L
worst single sample: 46.1 µg/L
5/46 SYR4 2012–2017
Benzene
0.6530 µg/L 13%
of the EPA limit 5 µg/L
worst single sample: 0.7000 µg/L
3/211 SYR4 2012–2019
cis-1,2-Dichloroethylene
0.1270 µg/L 0.2%
of the EPA limit 70 µg/L
worst single sample: 0.1300 µg/L
3/211 SYR4 2012–2019
Monobromoacetic Acid
0.2775 µg/L
No EPA limit set
worst single sample: 0.2800 µg/L
2/184 SYR4 2012–2019
Cyanide
16 µg/L 8%
of the EPA limit 200 µg/L
1/23 SYR4 2012–2017
Nitrate-Nitrite
6800 µg/L 68%
of the EPA limit 10000 µg/L
1/2 SYR4 2012–2017
47 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloropropane11Cl-PF3OUdS4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalChlorobenzeneCarbon TetrachlorideChromiumDichloromethaneEthylbenzeneHfpo-DaMonochloroacetic AcidNetfosaaNfdhaNmefosaaNitritePfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfmbaPfmpaPFNAPfpesPftaPftrdaPfunaStyreneTolueneTrichloroacetic AcidVinyl ChlorideXylenes, TotalLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
KENNEDY JR, WILLIAM
Phone
856-794-4056

Frequently asked questions about Vineland Water & Sewer Utility

Is Vineland Water & Sewer Utility tap water safe to drink?

EPA monitoring detected 35 contaminants in Vineland Water & Sewer Utility's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Vineland Water & Sewer Utility's water?

EPA monitoring detected Nitrate, Dibromochloromethane, Bromoform, Copper, Bromodichloromethane, and others. The full list with the level and data source for each is above.

How many people does Vineland Water & Sewer Utility serve?

Vineland Water & Sewer Utility reports serving 36,250 people in New Jersey, per its EPA record.

Has Vineland Water & Sewer Utility had any water quality violations?

The EPA has 725 violations on file for Vineland Water & Sewer Utility, of which 130 are health-based (a contaminant limit or required treatment was breached) and 8 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.