EPA monitoring tested this supplier for 71 contaminants and detected 20. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

71
contaminants tested
20
detected
81
people served
58
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Cumberland

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

58
health-based violations
479
violations on file
4
still open
ViolationTypeStatusPeriod
TT Health-based Unaddressed 2024-12-24
TT Health-based Unaddressed 2024-12-24
TT Health-based Resolved 2018-07-01 → 2018-12-31
TT Health-based Resolved 2018-07-01 → 2018-12-31
TT Health-based Resolved 2018-07-01 → 2018-12-31
TT Health-based Resolved 2018-07-01 → 2018-12-31
MCL Health-based Resolved 2016-07-01 → 2016-09-30
MCL Health-based Resolved 2016-07-01 → 2016-09-30
MCL Health-based Resolved 2016-07-01 → 2016-09-30
MCL Health-based Resolved 2016-07-01 → 2016-09-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
13355 µg/L 134%
of the EPA limit, at the 95th percentile of samples — 10000 µg/L
worst single sample: 16400 µg/L
70/70 SYR4 2012–2019
Copper
734 µg/L 56%
of the EPA limit 1300 µg/L
worst single sample: 1810 µg/L
61/65 SYR4 2012–2019
Lead
20.94 µg/L 140%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 33.8 µg/L
53/62 SYR4 2012–2019
Lead
0.0029 mg/L 19%
of the EPA limit 0.0150 mg/L
32/32 LCR 2025
Combined Radium (-226 And -228)
20.174 pCi/L 403%
of the EPA limit, at the 95th percentile of samples — 5 pCi/L
worst single sample: 32.7 pCi/L
25/29 SYR4 2012–2019
Chloroform
16.56 µg/L
No EPA limit set
worst single sample: 23 µg/L
8/16 SYR4 2012–2019
Bromodichloromethane
4.9 µg/L
No EPA limit set
worst single sample: 5.2 µg/L
6/16 SYR4 2012–2019
Gross Alpha, Excl. Radon And U
69.1725 pCi/L 461%
of the EPA limit, at the 95th percentile of samples — 15 pCi/L
worst single sample: 71.83 pCi/L
6/7 SYR4 2013–2017
Dibromochloromethane
3.56 µg/L
No EPA limit set
worst single sample: 3.9 µg/L
5/16 SYR4 2012–2019
TTHM
26.24 µg/L 33%
of the EPA limit 80 µg/L
worst single sample: 29 µg/L
5/8 SYR4 2012–2019
Bromoform
1.425 µg/L
No EPA limit set
worst single sample: 1.5 µg/L
4/16 SYR4 2012–2019
Arsenic
0.6550 µg/L 6.6%
of the EPA limit 10 µg/L
worst single sample: 0.6600 µg/L
3/3 SYR4 2012–2018
Selenium
2.81 µg/L 5.6%
of the EPA limit 50 µg/L
worst single sample: 3 µg/L
3/3 SYR4 2012–2018
Barium
0.3340 µg/L 0%
of the EPA limit 2000 µg/L
worst single sample: 0.3400 µg/L
2/3 SYR4 2012–2018
Chromium
3.595 µg/L 3.6%
of the EPA limit 100 µg/L
worst single sample: 3.7 µg/L
2/3 SYR4 2012–2018
Dichloroacetic Acid
1.1695 µg/L
No EPA limit set
worst single sample: 1.2 µg/L
2/9 SYR4 2012–2019
Thallium, Total
0.0790 µg/L 4%
of the EPA limit 2 µg/L
worst single sample: 0.0800 µg/L
2/3 SYR4 2012–2018
Total Haloacetic Acids (HAA5)
1.1695 µg/L 1.9%
of the EPA limit 60 µg/L
worst single sample: 1.2 µg/L
2/9 SYR4 2012–2019
1,2-Dichloroethane
0.3000 µg/L 6%
of the EPA limit 5 µg/L
1/11 SYR4 2012–2019
Mercury
0.0450 µg/L 2.3%
of the EPA limit 2 µg/L
1/3 SYR4 2012–2018
51 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideCombined UraniumDichloromethaneDalaponDibromoacetic AcidDinosebEthylene DibromideEndrinEthylbenzeneFluorideHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMethoxychlorMonobromoacetic AcidMonochloroacetic AcidOxamylPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneTolueneTrichloroacetic AcidTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
BARDIS, ALEX
Phone
732-539-1784

Frequently asked questions about Bayshore Mobile Home Park

Is Bayshore Mobile Home Park tap water safe to drink?

EPA monitoring detected 20 contaminants in Bayshore Mobile Home Park's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Bayshore Mobile Home Park's water?

EPA monitoring detected Nitrate, Copper, Lead, Lead, Combined Radium (-226 And -228), and others. The full list with the level and data source for each is above.

How many people does Bayshore Mobile Home Park serve?

Bayshore Mobile Home Park reports serving 81 people in New Jersey, per its EPA record.

Has Bayshore Mobile Home Park had any water quality violations?

The EPA has 479 violations on file for Bayshore Mobile Home Park, of which 58 are health-based (a contaminant limit or required treatment was breached) and 4 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.