Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Archived | 2025-07-01 → 2025-12-31 |
| TT | Health-based | Archived | 2025-01-01 → 2025-06-30 |
| TT | Health-based | Archived | 2025-01-01 → 2025-06-30 |
| TT | Health-based | Resolved | 2024-10-09 |
| TT | Health-based | Resolved | 2024-10-09 |
| TT | Health-based | Resolved | 2024-10-09 |
| TT | Health-based | Resolved | 2024-10-09 |
| TT | Health-based | Resolved | 2022-01-01 |
| TT | Health-based | Resolved | 2022-01-01 |
| TT | Health-based | Resolved | 2022-01-01 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 1359.5 µg/L 105% of the EPA limit, at the 95th percentile of samples — 1300 µg/L
worst single sample: 2140 µg/L | 92/93 | SYR4 | 2012–2019 |
| Lead | 13.845 µg/L 92% of the EPA limit 15 µg/L
worst single sample: 126 µg/L | 68/91 | SYR4 | 2012–2019 |
| Lead | 0.0040 mg/L 27% of the EPA limit 0.0150 mg/L | 28/28 | LCR | 2026 |
| Bromodichloromethane | 5.51 µg/L No EPA limit set
worst single sample: 5.9 µg/L | 21/22 | SYR4 | 2012–2019 |
| Chloroform | 7.7 µg/L No EPA limit set
worst single sample: 11 µg/L | 21/22 | SYR4 | 2012–2019 |
| Dibromochloromethane | 3.7 µg/L No EPA limit set | 21/22 | SYR4 | 2012–2019 |
| Bromoform | 1.08 µg/L No EPA limit set
worst single sample: 1.4 µg/L | 17/22 | SYR4 | 2012–2019 |
| TTHM | 18.48 µg/L 23% of the EPA limit 80 µg/L
worst single sample: 19 µg/L | 14/14 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 4.288 µg/L No EPA limit set
worst single sample: 4.42 µg/L | 13/14 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 8.744 µg/L 15% of the EPA limit 60 µg/L
worst single sample: 9.11 µg/L | 13/14 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 2.273 µg/L No EPA limit set
worst single sample: 2.3 µg/L | 10/14 | SYR4 | 2012–2019 |
| Nitrate | 447 µg/L 4.5% of the EPA limit 10000 µg/L | 8/16 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 1.9785 µg/L No EPA limit set
worst single sample: 2.01 µg/L | 4/14 | SYR4 | 2012–2019 |
| O-Dichlorobenzene | 0.2425 µg/L 0% of the EPA limit 600 µg/L
worst single sample: 0.2500 µg/L | 4/8 | SYR4 | 2012–2019 |
| Barium | 70.06 µg/L 3.5% of the EPA limit 2000 µg/L
worst single sample: 72.6 µg/L | 3/3 | SYR4 | 2012–2019 |
| Cadmium | 0.1327 µg/L 2.7% of the EPA limit 5 µg/L
worst single sample: 0.1400 µg/L | 3/3 | SYR4 | 2012–2019 |
| Arsenic | 0.4540 µg/L 4.5% of the EPA limit 10 µg/L
worst single sample: 0.4600 µg/L | 2/3 | SYR4 | 2012–2019 |
| Chlorobenzene | 0.0985 µg/L 0.1% of the EPA limit 100 µg/L
worst single sample: 0.1000 µg/L | 2/8 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 1.4635 µg/L No EPA limit set
worst single sample: 1.5 µg/L | 2/14 | SYR4 | 2012–2019 |
| Selenium | 1.675 µg/L 3.4% of the EPA limit 50 µg/L
worst single sample: 1.7 µg/L | 2/3 | SYR4 | 2012–2019 |
| Xylenes, Total | 1.748 µg/L 0% of the EPA limit 10000 µg/L
worst single sample: 1.83 µg/L | 2/8 | SYR4 | 2012–2019 |
| Antimony, Total | 0.0600 µg/L 1% of the EPA limit 6 µg/L | 1/3 | SYR4 | 2012–2019 |
| Benzene | 0.0400 µg/L 0.8% of the EPA limit 5 µg/L | 1/8 | SYR4 | 2012–2019 |
| Beryllium, Total | 0.0300 µg/L 0.8% of the EPA limit 4 µg/L | 1/3 | SYR4 | 2012–2019 |
| Chromium | 0.5000 µg/L 0.5% of the EPA limit 100 µg/L | 1/3 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 2.31 pCi/L 46% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2015 |
| Ethylbenzene | 0.2400 µg/L 0% of the EPA limit 700 µg/L | 1/8 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 6.69 pCi/L 45% of the EPA limit 15 pCi/L | 1/1 | SYR4 | 2015 |
| Thallium, Total | 0.1400 µg/L 7% of the EPA limit 2 µg/L | 1/3 | SYR4 | 2012–2019 |
| P-Dichlorobenzene | 0.0400 µg/L 0.1% of the EPA limit 75 µg/L | 1/8 | SYR4 | 2012–2019 |
23 contaminants tested, none detected
Utility contact
Frequently asked questions about Borough of Woodbine
Is Borough of Woodbine tap water safe to drink?
EPA monitoring detected 30 contaminants in Borough of Woodbine's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Borough of Woodbine's water?
EPA monitoring detected Copper, Lead, Lead, Bromodichloromethane, Chloroform, and others. The full list with the level and data source for each is above.
How many people does Borough of Woodbine serve?
Borough of Woodbine reports serving 2,650 people in New Jersey, per its EPA record.
Has Borough of Woodbine had any water quality violations?
The EPA has 107 violations on file for Borough of Woodbine, of which 16 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.