← New Jersey

Tap water quality report

Jbmdl - Mcguire Afb

EPA monitoring tested this supplier for 82 contaminants and detected 21. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

82
contaminants tested
21
detected
12,227
people served
8
health-based violations
Water source
Ground water
Ownership
Federal government
Counties served
Burlington

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

8
health-based violations
218
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 1995-01-01 → 1995-01-31
MCL Health-based Resolved 1995-01-01 → 1995-01-31
MCL Health-based Resolved 1995-01-01 → 1995-01-31
MCL Health-based Resolved 1995-01-01 → 1995-01-31
MCL Health-based Resolved 1994-05-01 → 1994-05-31
MCL Health-based Resolved 1994-05-01 → 1994-05-31
MCL Health-based Resolved 1994-05-01 → 1994-05-31
MCL Health-based Archived 1991-06-01 → 1991-06-30
Other Monitoring Resolved 2024-07-01
Other Monitoring Resolved 2024-07-01

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
298.3 µg/L 23%
of the EPA limit 1300 µg/L
worst single sample: 322 µg/L
75/80 SYR4 2012–2018
Chloroform
23.506 µg/L
No EPA limit set
worst single sample: 98.8 µg/L
73/75 SYR4 2012–2019
Bromodichloromethane
6.14 µg/L
No EPA limit set
worst single sample: 10.1 µg/L
69/75 SYR4 2012–2019
TTHM
34.3365 µg/L 43%
of the EPA limit 80 µg/L
worst single sample: 107.9 µg/L
68/68 SYR4 2012–2019
Dibromochloromethane
2.866 µg/L
No EPA limit set
worst single sample: 4.41 µg/L
63/75 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
15.7 µg/L 26%
of the EPA limit 60 µg/L
worst single sample: 32.1 µg/L
59/68 SYR4 2012–2019
Dichloroacetic Acid
6.8085 µg/L
No EPA limit set
worst single sample: 10.7 µg/L
50/68 SYR4 2012–2019
Trichloroacetic Acid
8.165 µg/L
No EPA limit set
worst single sample: 12.6 µg/L
36/68 SYR4 2012–2019
Monochloroacetic Acid
4.738 µg/L
No EPA limit set
worst single sample: 5.32 µg/L
25/68 SYR4 2012–2019
Monobromoacetic Acid
1.649 µg/L
No EPA limit set
worst single sample: 3.71 µg/L
19/68 SYR4 2012–2019
Dibromoacetic Acid
5 µg/L
No EPA limit set
18/68 SYR4 2012–2019
Lead
0.00080 mg/L 5.3%
of the EPA limit 0.0150 mg/L
17/17 LCR 2024
Lead
14 µg/L 93%
of the EPA limit 15 µg/L
worst single sample: 24 µg/L
11/70 SYR4 2012–2018
Barium
62.7 µg/L 3.1%
of the EPA limit 2000 µg/L
worst single sample: 63 µg/L
7/10 SYR4 2012–2017
Fluoride
1300 µg/L 33%
of the EPA limit 4000 µg/L
7/10 SYR4 2012–2017
Nitrate
700 µg/L 7%
of the EPA limit 10000 µg/L
6/46 SYR4 2012–2019
Bromoform
1.7375 µg/L
No EPA limit set
worst single sample: 1.91 µg/L
4/75 SYR4 2012–2019
Cyanide
11.8 µg/L 5.9%
of the EPA limit 200 µg/L
worst single sample: 12 µg/L
3/10 SYR4 2012–2017
Cadmium
0.2950 µg/L 5.9%
of the EPA limit 5 µg/L
worst single sample: 0.3000 µg/L
2/10 SYR4 2012–2017
Chromium
0.8900 µg/L 0.9%
of the EPA limit 100 µg/L
worst single sample: 0.9000 µg/L
2/10 SYR4 2012–2017
Thallium, Total
0.5850 µg/L 29%
of the EPA limit 2 µg/L
worst single sample: 0.6000 µg/L
2/10 SYR4 2012–2017
61 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAsbestosBenzeneBeryllium, TotalChlorobenzeneCarbon TetrachlorideCombined Radium (-226 And -228)Combined UraniumDichloromethaneEthylene DibromideEthylbenzeneHfpo-DaMercuryNetfosaaNfdhaNmefosaaPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaSeleniumStyreneTetrachloroethyleneTolueneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
JICHA, KRISTEN
Phone
609-754-6171

Frequently asked questions about Jbmdl - Mcguire Afb

Is Jbmdl - Mcguire Afb tap water safe to drink?

EPA monitoring detected 21 contaminants in Jbmdl - Mcguire Afb's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Jbmdl - Mcguire Afb's water?

EPA monitoring detected Copper, Chloroform, Bromodichloromethane, TTHM, Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does Jbmdl - Mcguire Afb serve?

Jbmdl - Mcguire Afb reports serving 12,227 people in New Jersey, per its EPA record.

Has Jbmdl - Mcguire Afb had any water quality violations?

The EPA has 218 violations on file for Jbmdl - Mcguire Afb, of which 8 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.