Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Resolved | 2020-12-01 → 2020-12-31 |
| MR | Monitoring | Resolved | 2020-12-01 → 2020-12-31 |
| MR | Monitoring | Resolved | 2020-10-01 → 2020-12-31 |
| MR | Monitoring | Resolved | 2020-10-01 → 2020-12-31 |
| MR | Monitoring | Resolved | 2014-04-01 → 2014-06-30 |
| MR | Monitoring | Resolved | 2014-04-01 → 2014-06-30 |
| MR | Monitoring | Resolved | 2014-04-01 → 2014-06-30 |
| MR | Monitoring | Resolved | 2014-04-01 → 2014-06-30 |
| MR | Monitoring | Resolved | 2014-04-01 → 2014-06-30 |
| MR | Monitoring | Resolved | 2014-04-01 → 2014-06-30 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 619.15 µg/L 48% of the EPA limit 1300 µg/L
worst single sample: 1010 µg/L | 168/170 | SYR4 | 2012–2019 |
| Chloroform | 30.075 µg/L No EPA limit set
worst single sample: 41.7 µg/L | 102/102 | SYR4 | 2012–2019 |
| Bromodichloromethane | 14.1 µg/L No EPA limit set
worst single sample: 17.7 µg/L | 101/102 | SYR4 | 2012–2019 |
| Dibromochloromethane | 8.539 µg/L No EPA limit set
worst single sample: 10 µg/L | 98/102 | SYR4 | 2012–2019 |
| TTHM | 52.72 µg/L 66% of the EPA limit 80 µg/L
worst single sample: 64.9 µg/L | 73/73 | SYR4 | 2012–2019 |
| Lead | 37.9 µg/L 253% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 62.5 µg/L | 71/167 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 13.56 µg/L 23% of the EPA limit 60 µg/L
worst single sample: 28 µg/L | 71/73 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 8.234 µg/L No EPA limit set
worst single sample: 9 µg/L | 69/73 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 7.637 µg/L No EPA limit set
worst single sample: 15.1 µg/L | 64/73 | SYR4 | 2012–2019 |
| Bromoform | 1.2325 µg/L No EPA limit set
worst single sample: 1.51 µg/L | 60/97 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 3545 µg/L 35% of the EPA limit 10000 µg/L
worst single sample: 3720 µg/L | 46/46 | SYR4 | 2012–2019 |
| Lead | 0.0037 mg/L 25% of the EPA limit 0.0150 mg/L | 25/25 | LCR | 2025 |
| Barium | 40.215 µg/L 2% of the EPA limit 2000 µg/L
worst single sample: 48 µg/L | 10/10 | SYR4 | 2012–2019 |
| Chromium | 19.715 µg/L 20% of the EPA limit 100 µg/L
worst single sample: 24.3 µg/L | 8/10 | SYR4 | 2012–2019 |
| Nitrate | 3380 µg/L 34% of the EPA limit 10000 µg/L | 8/8 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 1.5 µg/L No EPA limit set | 4/73 | SYR4 | 2012–2019 |
| Arsenic | 2.2 µg/L 22% of the EPA limit 10 µg/L | 1/10 | SYR4 | 2012–2019 |
| Beryllium, Total | 2.21 µg/L 55% of the EPA limit 4 µg/L | 1/10 | SYR4 | 2012–2019 |
| Cadmium | 0.9470 µg/L 19% of the EPA limit 5 µg/L | 1/10 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 2.1 pCi/L 42% of the EPA limit 5 pCi/L | 1/10 | SYR4 | 2013–2015 |
| Di(2-ethylhexyl) Phthalate | 0.2800 µg/L 4.7% of the EPA limit 6 µg/L | 1/1 | SYR4 | 2015 |
| Endrin | 0.0250 µg/L 1.3% of the EPA limit 2 µg/L | 1/1 | SYR4 | 2015 |
| Fluoride | 80 µg/L 2% of the EPA limit 4000 µg/L | 1/10 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 4.26 pCi/L 28% of the EPA limit 15 pCi/L | 1/10 | SYR4 | 2013–2015 |
| Monochloroacetic Acid | 5 µg/L No EPA limit set | 1/73 | SYR4 | 2012–2019 |
| Selenium | 8.18 µg/L 16% of the EPA limit 50 µg/L | 1/10 | SYR4 | 2012–2019 |
78 contaminants tested, none detected
Utility contact
Frequently asked questions about Veolia Water New Jersey Franklin Lakes
Is Veolia Water New Jersey Franklin Lakes tap water safe to drink?
EPA monitoring detected 33 contaminants in Veolia Water New Jersey Franklin Lakes's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Veolia Water New Jersey Franklin Lakes's water?
EPA monitoring detected Copper, Chloroform, Bromodichloromethane, Dibromochloromethane, TTHM, and others. The full list with the level and data source for each is above.
How many people does Veolia Water New Jersey Franklin Lakes serve?
Veolia Water New Jersey Franklin Lakes reports serving 5,038 people in New Jersey, per its EPA record.
Has Veolia Water New Jersey Franklin Lakes had any water quality violations?
The EPA has 18 violations on file for Veolia Water New Jersey Franklin Lakes, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.