Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2013-06-01 → 2013-06-30 |
| MCL | Health-based | Resolved | 2013-06-01 → 2013-06-30 |
| MCL | Health-based | Resolved | 2013-06-01 → 2013-06-30 |
| MCL | Health-based | Resolved | 2013-06-01 → 2013-06-30 |
| MCL | Health-based | Resolved | 2012-12-01 → 2012-12-31 |
| MCL | Health-based | Resolved | 2012-12-01 → 2012-12-31 |
| MCL | Health-based | Resolved | 2012-12-01 → 2012-12-31 |
| MCL | Health-based | Resolved | 2012-12-01 → 2012-12-31 |
| MCL | Health-based | Resolved | 2012-09-01 → 2012-09-30 |
| MCL | Health-based | Resolved | 2012-09-01 → 2012-09-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Chloroform | 8.588 µg/L No EPA limit set
worst single sample: 14.5 µg/L | 149/159 | SYR4 | 2012–2019 |
| TTHM | 13.82 µg/L 17% of the EPA limit 80 µg/L
worst single sample: 19.2 µg/L | 114/121 | SYR4 | 2012–2019 |
| Bromodichloromethane | 4.218 µg/L No EPA limit set
worst single sample: 6.07 µg/L | 98/159 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 6.868 µg/L 11% of the EPA limit 60 µg/L
worst single sample: 8.24 µg/L | 83/121 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 3.046 µg/L No EPA limit set
worst single sample: 3.29 µg/L | 77/121 | SYR4 | 2012–2019 |
| Copper | 357.6 µg/L 28% of the EPA limit 1300 µg/L
worst single sample: 484 µg/L | 55/75 | SYR4 | 2014–2019 |
| Trichloroacetic Acid | 4.2655 µg/L No EPA limit set
worst single sample: 5.14 µg/L | 52/121 | SYR4 | 2012–2019 |
| Dibromochloromethane | 2.19 µg/L No EPA limit set
worst single sample: 2.5 µg/L | 43/159 | SYR4 | 2012–2019 |
| Fluoride | 260 µg/L 6.5% of the EPA limit 4000 µg/L
worst single sample: 320 µg/L | 27/33 | SYR4 | 2014–2019 |
| Lead | 0.0038 mg/L 25% of the EPA limit 0.0150 mg/L | 15/15 | LCR | 2023 |
| Lead | 2.54 µg/L 17% of the EPA limit 15 µg/L
worst single sample: 2.55 µg/L | 11/60 | SYR4 | 2014–2017 |
| Barium | 1 µg/L 0.1% of the EPA limit 2000 µg/L | 7/18 | SYR4 | 2014–2019 |
| Chromium | 1 µg/L 1% of the EPA limit 100 µg/L | 7/18 | SYR4 | 2014–2019 |
| Monochloroacetic Acid | 0.5980 µg/L No EPA limit set
worst single sample: 0.6100 µg/L | 7/121 | SYR4 | 2012–2019 |
| Cyanide | 39.25 µg/L 20% of the EPA limit 200 µg/L
worst single sample: 45 µg/L | 6/15 | SYR4 | 2014–2019 |
| Xylenes, Total | 72.955 µg/L 0.7% of the EPA limit 10000 µg/L
worst single sample: 88.3 µg/L | 6/46 | SYR4 | 2014–2019 |
| Nitrate-Nitrite | 175.55 µg/L 1.8% of the EPA limit 10000 µg/L
worst single sample: 176 µg/L | 4/21 | SYR4 | 2016–2019 |
| Ethylbenzene | 9.088 µg/L 1.3% of the EPA limit 700 µg/L
worst single sample: 9.78 µg/L | 3/46 | SYR4 | 2014–2019 |
| Selenium | 0.4450 µg/L 0.9% of the EPA limit 50 µg/L
worst single sample: 0.4600 µg/L | 3/18 | SYR4 | 2014–2019 |
| Cadmium | 0.2765 µg/L 5.5% of the EPA limit 5 µg/L
worst single sample: 0.2900 µg/L | 2/18 | SYR4 | 2014–2019 |
| Combined Radium (-226 And -228) | 1.5 pCi/L 30% of the EPA limit 5 pCi/L | 2/6 | SYR4 | 2017–2018 |
| Mercury | 0.0456 µg/L 2.3% of the EPA limit 2 µg/L
worst single sample: 0.0460 µg/L | 2/18 | SYR4 | 2014–2019 |
| Bromoform | 0.1300 µg/L No EPA limit set | 1/159 | SYR4 | 2012–2019 |
61 contaminants tested, none detected
Utility contact
Frequently asked questions about Ventnor City Water & Sewer Utility
Is Ventnor City Water & Sewer Utility tap water safe to drink?
EPA monitoring detected 23 contaminants in Ventnor City Water & Sewer Utility's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Ventnor City Water & Sewer Utility's water?
EPA monitoring detected Chloroform, TTHM, Bromodichloromethane, Total Haloacetic Acids (HAA5), Dichloroacetic Acid, and others. The full list with the level and data source for each is above.
How many people does Ventnor City Water & Sewer Utility serve?
Ventnor City Water & Sewer Utility reports serving 22,150 people in New Jersey, per its EPA record.
Has Ventnor City Water & Sewer Utility had any water quality violations?
The EPA has 123 violations on file for Ventnor City Water & Sewer Utility, of which 28 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.