Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Archived | 1991-05-01 → 1991-05-31 |
| MCL | Health-based | Archived | 1991-05-01 → 1991-05-31 |
| MCL | Health-based | Archived | 1989-03-01 → 1989-05-31 |
| MCL | Health-based | Archived | 1989-03-01 → 1989-05-31 |
| MR | Monitoring | Resolved | 2024-12-30 |
| MR | Monitoring | Resolved | 2024-12-30 |
| MR | Monitoring | Resolved | 2022-01-01 → 2022-03-31 |
| MR | Monitoring | Resolved | 2022-01-01 → 2022-03-31 |
| MR | Monitoring | Resolved | 2022-01-01 → 2022-03-31 |
| MR | Monitoring | Resolved | 2022-01-01 → 2022-03-31 |
PFAS detected
| Contaminant | Max | Detection rate | Period |
|---|---|---|---|
| PFOA | 0.0052 µg/L | 2/10 | 2025 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Chloroform | 13.625 µg/L No EPA limit set
worst single sample: 20 µg/L | 156/167 | SYR4 | 2012–2019 |
| Bromodichloromethane | 5.28 µg/L No EPA limit set
worst single sample: 7 µg/L | 145/167 | SYR4 | 2012–2019 |
| Dibromochloromethane | 3.9 µg/L No EPA limit set
worst single sample: 7.5 µg/L | 143/167 | SYR4 | 2012–2019 |
| TTHM | 23 µg/L 29% of the EPA limit 80 µg/L
worst single sample: 28 µg/L | 141/142 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 4.7505 µg/L 7.9% of the EPA limit 60 µg/L
worst single sample: 29 µg/L | 90/142 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 2.3065 µg/L No EPA limit set
worst single sample: 17 µg/L | 72/142 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 3.4885 µg/L No EPA limit set
worst single sample: 12 µg/L | 68/142 | SYR4 | 2012–2019 |
| Bromoform | 3.55 µg/L No EPA limit set
worst single sample: 5 µg/L | 61/167 | SYR4 | 2012–2019 |
| Nitrate | 767.05 µg/L 7.7% of the EPA limit 10000 µg/L
worst single sample: 772 µg/L | 32/80 | SYR4 | 2012–2019 |
| Lead | 28.88 µg/L 193% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 1110 µg/L | 27/269 | SYR4 | 2012–2018 |
| Copper | 94.8 µg/L 7.3% of the EPA limit 1300 µg/L
worst single sample: 101 µg/L | 25/284 | SYR4 | 2012–2018 |
| Lead | 0.0019 mg/L 12% of the EPA limit 0.0150 mg/L | 21/21 | LCR | 2024 |
| Nitrate-Nitrite | 765.7 µg/L 7.7% of the EPA limit 10000 µg/L
worst single sample: 772 µg/L | 15/36 | SYR4 | 2012–2019 |
| Barium | 82.705 µg/L 4.1% of the EPA limit 2000 µg/L
worst single sample: 89.4 µg/L | 14/15 | SYR4 | 2012–2017 |
| Dibromoacetic Acid | 1.692 µg/L No EPA limit set
worst single sample: 2.13 µg/L | 13/142 | SYR4 | 2012–2019 |
| Fluoride | 259.2 µg/L 6.5% of the EPA limit 4000 µg/L
worst single sample: 262 µg/L | 9/30 | SYR4 | 2012–2017 |
| Mercury | 0.9685 µg/L 48% of the EPA limit 2 µg/L
worst single sample: 1 µg/L | 8/15 | SYR4 | 2012–2017 |
| Monochloroacetic Acid | 0.7850 µg/L No EPA limit set
worst single sample: 0.8000 µg/L | 6/142 | SYR4 | 2012–2019 |
| Selenium | 0.7150 µg/L 1.4% of the EPA limit 50 µg/L
worst single sample: 0.7600 µg/L | 6/15 | SYR4 | 2012–2017 |
| Cadmium | 0.1070 µg/L 2.1% of the EPA limit 5 µg/L
worst single sample: 0.1100 µg/L | 4/15 | SYR4 | 2012–2017 |
| Chromium | 0.8770 µg/L 0.9% of the EPA limit 100 µg/L
worst single sample: 0.9000 µg/L | 3/15 | SYR4 | 2012–2017 |
| Arsenic | 0.1575 µg/L 1.6% of the EPA limit 10 µg/L
worst single sample: 0.1600 µg/L | 2/15 | SYR4 | 2012–2017 |
| Combined Radium (-226 And -228) | 3.3575 pCi/L 67% of the EPA limit 5 pCi/L
worst single sample: 3.4 pCi/L | 2/5 | SYR4 | 2017 |
| Gross Alpha, Excl. Radon And U | 10.025 pCi/L 67% of the EPA limit 15 pCi/L
worst single sample: 10.3 pCi/L | 2/5 | SYR4 | 2017 |
| Thallium, Total | 0.0490 µg/L 2.5% of the EPA limit 2 µg/L
worst single sample: 0.0500 µg/L | 2/15 | SYR4 | 2012–2017 |
| Antimony, Total | 0.3300 µg/L 5.5% of the EPA limit 6 µg/L | 1/15 | SYR4 | 2012–2017 |
| Beryllium, Total | 0.0900 µg/L 2.3% of the EPA limit 4 µg/L | 1/15 | SYR4 | 2012–2017 |
74 contaminants tested, none detected
Utility contact
Frequently asked questions about Hamilton Township Mua
Is Hamilton Township Mua tap water safe to drink?
EPA monitoring detected 28 contaminants in Hamilton Township Mua's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Hamilton Township Mua's water?
EPA monitoring detected Chloroform, Bromodichloromethane, Dibromochloromethane, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Hamilton Township Mua serve?
Hamilton Township Mua reports serving 21,720 people in New Jersey, per its EPA record.
Has Hamilton Township Mua had any water quality violations?
The EPA has 289 violations on file for Hamilton Township Mua, of which 4 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.