Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2022-07-01 → 2022-12-31 |
| TT | Health-based | Resolved | 2022-07-01 → 2022-12-31 |
| TT | Health-based | Resolved | 2022-07-01 → 2022-12-31 |
| TT | Health-based | Resolved | 2022-07-01 → 2022-12-31 |
| TT | Health-based | Resolved | 2022-07-01 → 2022-12-31 |
| TT | Health-based | Resolved | 2022-07-01 → 2022-12-31 |
| TT | Health-based | Resolved | 2016-05-01 |
| TT | Health-based | Resolved | 2016-05-01 |
| TT | Health-based | Resolved | 2016-05-01 |
| TT | Health-based | Resolved | 2016-05-01 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 1850.5 µg/L 142% of the EPA limit, at the 95th percentile of samples — 1300 µg/L
worst single sample: 4220 µg/L | 90/107 | SYR4 | 2012–2019 |
| Lead | 16.26 µg/L 108% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 28.8 µg/L | 57/99 | SYR4 | 2012–2019 |
| Nitrate | 2305 µg/L 23% of the EPA limit 10000 µg/L
worst single sample: 2320 µg/L | 36/44 | SYR4 | 2012–2019 |
| Chloroform | 1.8 µg/L No EPA limit set
worst single sample: 2.6 µg/L | 33/42 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 29/29 | LCR | 2025 |
| Bromodichloromethane | 0.2720 µg/L No EPA limit set
worst single sample: 0.3200 µg/L | 13/42 | SYR4 | 2012–2019 |
| Arsenic | 1.365 µg/L 14% of the EPA limit 10 µg/L
worst single sample: 1.4 µg/L | 8/8 | SYR4 | 2012–2018 |
| Barium | 167.55 µg/L 8.4% of the EPA limit 2000 µg/L
worst single sample: 170 µg/L | 8/8 | SYR4 | 2012–2018 |
| Cadmium | 0.0898 µg/L 1.8% of the EPA limit 5 µg/L
worst single sample: 0.0940 µg/L | 8/8 | SYR4 | 2012–2018 |
| Mercury | 0.3609 µg/L 18% of the EPA limit 2 µg/L
worst single sample: 0.3990 µg/L | 8/8 | SYR4 | 2012–2018 |
| Combined Radium (-226 And -228) | 2.87 pCi/L 57% of the EPA limit 5 pCi/L
worst single sample: 2.94 pCi/L | 6/6 | SYR4 | 2012–2018 |
| Selenium | 4.975 µg/L 10% of the EPA limit 50 µg/L
worst single sample: 5.1 µg/L | 6/8 | SYR4 | 2012–2018 |
| TTHM | 1.63 µg/L 2% of the EPA limit 80 µg/L
worst single sample: 1.68 µg/L | 6/12 | SYR4 | 2012–2019 |
| Thallium, Total | 0.0875 µg/L 4.4% of the EPA limit 2 µg/L
worst single sample: 0.0900 µg/L | 6/8 | SYR4 | 2012–2018 |
| Chromium | 4.4 µg/L 4.4% of the EPA limit 100 µg/L
worst single sample: 4.6 µg/L | 3/8 | SYR4 | 2012–2018 |
| Dibromochloromethane | 0.2540 µg/L No EPA limit set
worst single sample: 0.2600 µg/L | 3/38 | SYR4 | 2012–2019 |
| P-Dichlorobenzene | 0.0500 µg/L 0.1% of the EPA limit 75 µg/L | 3/30 | SYR4 | 2012–2019 |
| Beryllium, Total | 0.0595 µg/L 1.5% of the EPA limit 4 µg/L
worst single sample: 0.0600 µg/L | 2/8 | SYR4 | 2012–2018 |
32 contaminants tested, none detected
Utility contact
Frequently asked questions about Tilton Terrace Mhp
Is Tilton Terrace Mhp tap water safe to drink?
EPA monitoring detected 18 contaminants in Tilton Terrace Mhp's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Tilton Terrace Mhp's water?
EPA monitoring detected Copper, Lead, Nitrate, Chloroform, Lead, and others. The full list with the level and data source for each is above.
How many people does Tilton Terrace Mhp serve?
Tilton Terrace Mhp reports serving 456 people in New Jersey, per its EPA record.
Has Tilton Terrace Mhp had any water quality violations?
The EPA has 227 violations on file for Tilton Terrace Mhp, of which 13 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.