← New Jersey

Tap water quality report

Buena Family Manor Mhp

EPA monitoring tested this supplier for 44 contaminants and detected 11. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

44
contaminants tested
11
detected
64
people served
0
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Atlantic

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
35
violations on file
0
still open
ViolationTypeStatusPeriod
MR Monitoring Resolved 2018-12-30
MR Monitoring Resolved 2018-12-30
MR Monitoring Resolved 2008-01-01 → 2010-12-31
MR Monitoring Resolved 2008-01-01 → 2010-12-31
MR Monitoring Resolved 2008-01-01 → 2010-12-31
MR Monitoring Resolved 2008-01-01 → 2010-12-31
MR Monitoring Resolved 2008-01-01 → 2010-12-31
MR Monitoring Resolved 2008-01-01 → 2010-12-31
MR Monitoring Resolved 2008-01-01 → 2010-12-31
MR Monitoring Resolved 2008-01-01 → 2010-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
57.3 µg/L 4.4%
of the EPA limit 1300 µg/L
worst single sample: 58 µg/L
15/20 SYR4 2012–2018
Lead
0.0013 mg/L 8.7%
of the EPA limit 0.0150 mg/L
14/14 LCR 2024
Nitrate
550 µg/L 5.5%
of the EPA limit 10000 µg/L
10/16 SYR4 2012–2019
Lead
0.7840 µg/L 5.2%
of the EPA limit 15 µg/L
worst single sample: 0.9400 µg/L
5/16 SYR4 2012–2018
Barium
32.82 µg/L 1.6%
of the EPA limit 2000 µg/L
worst single sample: 33.3 µg/L
3/3 SYR4 2012–2018
Combined Radium (-226 And -228)
3.6375 pCi/L 73%
of the EPA limit 5 pCi/L
worst single sample: 3.75 pCi/L
2/3 SYR4 2012–2018
Thallium, Total
0.2680 µg/L 13%
of the EPA limit 2 µg/L
worst single sample: 0.2700 µg/L
2/3 SYR4 2012–2018
Cadmium
0.0400 µg/L 0.8%
of the EPA limit 5 µg/L
1/3 SYR4 2012–2018
Chloroform
0.1700 µg/L
No EPA limit set
1/3 SYR4 2012–2018
Chromium
1.1 µg/L 1.1%
of the EPA limit 100 µg/L
1/3 SYR4 2012–2018
Mercury
0.1210 µg/L 6.1%
of the EPA limit 2 µg/L
1/3 SYR4 2012–2018
33 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-DichloropropaneAntimony, TotalArsenicBenzeneBeryllium, TotalBromodichloromethaneBromoformChlorobenzeneCyanideCarbon TetrachlorideDichloromethaneDibromochloromethaneEthylene DibromideEthylbenzeneFluorideNitriteSeleniumStyreneTetrachloroethyleneTolueneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
DEGASPERIS, KYLE
Phone
862-266-1399

Frequently asked questions about Buena Family Manor Mhp

Is Buena Family Manor Mhp tap water safe to drink?

EPA monitoring detected 11 contaminants in Buena Family Manor Mhp's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Buena Family Manor Mhp's water?

EPA monitoring detected Copper, Lead, Nitrate, Lead, Barium, and others. The full list with the level and data source for each is above.

How many people does Buena Family Manor Mhp serve?

Buena Family Manor Mhp reports serving 64 people in New Jersey, per its EPA record.

Has Buena Family Manor Mhp had any water quality violations?

The EPA has 35 violations on file for Buena Family Manor Mhp, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.