Compliance record
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 8.275 µg/L No EPA limit set
worst single sample: 9.9 µg/L | 94/94 | SYR4 | 2014–2019 |
| Chloroform | 83.7 µg/L No EPA limit set
worst single sample: 93 µg/L | 94/94 | SYR4 | 2014–2019 |
| TTHM | 92 µg/L 115% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 103.59 µg/L | 88/88 | SYR4 | 2014–2019 |
| Total Haloacetic Acids (HAA5) | 25.3 µg/L 42% of the EPA limit 60 µg/L
worst single sample: 29 µg/L | 88/88 | SYR4 | 2014–2019 |
| Trichloroacetic Acid | 14 µg/L No EPA limit set
worst single sample: 19 µg/L | 88/88 | SYR4 | 2014–2019 |
| Dichloroacetic Acid | 13.4 µg/L No EPA limit set
worst single sample: 21 µg/L | 87/88 | SYR4 | 2014–2019 |
| Dibromochloromethane | 1.105 µg/L No EPA limit set
worst single sample: 1.4 µg/L | 74/94 | SYR4 | 2014–2019 |
| Copper | 82.3 µg/L 6.3% of the EPA limit 1300 µg/L
worst single sample: 130 µg/L | 59/66 | SYR4 | 2014–2019 |
| Lead | 9.2 µg/L 61% of the EPA limit 15 µg/L
worst single sample: 13 µg/L | 20/60 | SYR4 | 2014–2017 |
| Lead | 0.0040 mg/L 27% of the EPA limit 0.0150 mg/L | 14/14 | LCR | 2023 |
| Fluoride | 685 µg/L 17% of the EPA limit 4000 µg/L
worst single sample: 690 µg/L | 6/6 | SYR4 | 2014–2019 |
| P-Dichlorobenzene | 3.6 µg/L 4.8% of the EPA limit 75 µg/L
worst single sample: 3.7 µg/L | 3/10 | SYR4 | 2014–2019 |
| Dichloromethane | 0.9000 µg/L 18% of the EPA limit 5 µg/L | 1/7 | SYR4 | 2014–2019 |
93 contaminants tested, none detected
Utility contact
Frequently asked questions about Laconia Water Works
Is Laconia Water Works tap water safe to drink?
EPA monitoring detected 13 contaminants in Laconia Water Works's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Laconia Water Works's water?
EPA monitoring detected Bromodichloromethane, Chloroform, TTHM, Total Haloacetic Acids (HAA5), Trichloroacetic Acid, and others. The full list with the level and data source for each is above.
How many people does Laconia Water Works serve?
Laconia Water Works reports serving 17,125 people in New Hampshire, per its EPA record.
Has Laconia Water Works had any water quality violations?
The EPA has no formal drinking-water violations on file for Laconia Water Works.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.