← New Hampshire

Tap water quality report

Liberty Ridge Mhp

EPA monitoring tested this supplier for 75 contaminants and detected 14. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

75
contaminants tested
14
detected
91
people served
33
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Merrimack

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

33
health-based violations
133
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2022-07-01 → 2022-09-30
MCL Health-based Resolved 2022-07-01 → 2022-09-30
MCL Health-based Resolved 2022-07-01 → 2022-09-30
MCL Health-based Resolved 2022-07-01 → 2022-09-30
MCL Health-based Resolved 2004-10-01 → 2004-10-31
MCL Health-based Resolved 2004-10-01 → 2004-10-31
MCL Health-based Resolved 2004-10-01 → 2004-10-31
MCL Health-based Resolved 2004-10-01 → 2004-10-31
TT Health-based Resolved 2004-01-01
TT Health-based Resolved 2004-01-01

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Arsenic
2 µg/L 20%
of the EPA limit 10 µg/L
worst single sample: 2.4 µg/L
24/26 SYR4 2014–2019
Copper
421 µg/L 32%
of the EPA limit 1300 µg/L
worst single sample: 590 µg/L
14/14 SYR4 2015–2019
Nitrate
1200 µg/L 12%
of the EPA limit 10000 µg/L
10/24 SYR4 2014–2019
Lead
5.24 µg/L 35%
of the EPA limit 15 µg/L
worst single sample: 5.4 µg/L
9/10 SYR4 2015–2018
Bromoform
1.2 µg/L
No EPA limit set
5/13 SYR4 2014–2019
Barium
107.6 µg/L 5.4%
of the EPA limit 2000 µg/L
worst single sample: 110 µg/L
4/4 SYR4 2016–2019
Combined Uranium
3.7 µg/L 12%
of the EPA limit 30 µg/L
worst single sample: 3.8 µg/L
3/3 SYR4 2016–2019
Dibromochloromethane
0.8050 µg/L
No EPA limit set
worst single sample: 0.8300 µg/L
3/13 SYR4 2014–2019
Fluoride
3140 µg/L 79%
of the EPA limit 4000 µg/L
worst single sample: 3200 µg/L
3/4 SYR4 2016–2019
Gross Alpha, Excl. Radon And U
11.18 pCi/L 75%
of the EPA limit 15 pCi/L
worst single sample: 11.6 pCi/L
3/3 SYR4 2016–2019
Combined Radium (-226 And -228)
1.165 pCi/L 23%
of the EPA limit 5 pCi/L
worst single sample: 1.2 pCi/L
2/2 SYR4 2016
Lead
0.0230 mg/L 153%
above the EPA limit of 0.0150 mg/L
2/2 LCR 2024
Mercury
0.2000 µg/L 10%
of the EPA limit 2 µg/L
2/4 SYR4 2016–2019
Selenium
1 µg/L 2%
of the EPA limit 50 µg/L
1/4 SYR4 2016–2019
61 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromodichloromethaneChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneChloroformChromiumDichloromethaneDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromoacetic AcidDichloroacetic AcidDinosebEthylene DibromideEndrinEthylbenzeneGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNitriteOxamylPentachlorophenolPicloramSimazineStyreneTTHMTetrachloroethyleneThallium, TotalTolueneTotal Haloacetic Acids (HAA5)ToxapheneTrichloroacetic AcidTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
TANYA JONES

Frequently asked questions about Liberty Ridge Mhp

Is Liberty Ridge Mhp tap water safe to drink?

EPA monitoring detected 14 contaminants in Liberty Ridge Mhp's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Liberty Ridge Mhp's water?

EPA monitoring detected Arsenic, Copper, Nitrate, Lead, Bromoform, and others. The full list with the level and data source for each is above.

How many people does Liberty Ridge Mhp serve?

Liberty Ridge Mhp reports serving 91 people in New Hampshire, per its EPA record.

Has Liberty Ridge Mhp had any water quality violations?

The EPA has 133 violations on file for Liberty Ridge Mhp, of which 33 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.