Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2012-07-01 → 2012-07-31 |
| MCL | Health-based | Resolved | 2012-07-01 → 2012-07-31 |
| MCL | Health-based | Resolved | 2012-07-01 → 2012-07-31 |
| MCL | Health-based | Resolved | 2012-07-01 → 2012-07-31 |
| MR | Monitoring | Resolved | 2021-12-30 |
| MR | Monitoring | Resolved | 2021-12-30 |
| MR | Monitoring | Resolved | 2021-07-01 → 2021-10-01 |
| MR | Monitoring | Resolved | 2021-07-01 → 2021-10-01 |
| MR | Monitoring | Resolved | 2021-07-01 → 2021-10-01 |
| MR | Monitoring | Resolved | 2021-07-01 → 2021-10-01 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 357 µg/L 27% of the EPA limit 1300 µg/L
worst single sample: 650 µg/L | 22/22 | SYR4 | 2015–2019 |
| Lead | 2.55 µg/L 17% of the EPA limit 15 µg/L
worst single sample: 3 µg/L | 10/20 | SYR4 | 2015–2018 |
| Bromodichloromethane | 2.43 µg/L No EPA limit set
worst single sample: 2.5 µg/L | 8/8 | SYR4 | 2014–2019 |
| Chloroform | 4.245 µg/L No EPA limit set
worst single sample: 4.7 µg/L | 8/8 | SYR4 | 2014–2019 |
| Dibromochloromethane | 1.165 µg/L No EPA limit set
worst single sample: 1.2 µg/L | 8/8 | SYR4 | 2014–2019 |
| TTHM | 7.625 µg/L 9.5% of the EPA limit 80 µg/L
worst single sample: 7.8 µg/L | 6/6 | SYR4 | 2014–2019 |
| Nitrate | 520 µg/L 5.2% of the EPA limit 10000 µg/L | 4/12 | SYR4 | 2014–2019 |
| Arsenic | 3.57 µg/L 36% of the EPA limit 10 µg/L
worst single sample: 3.6 µg/L | 2/2 | SYR4 | 2016–2019 |
| Barium | 8.855 µg/L 0.4% of the EPA limit 2000 µg/L
worst single sample: 8.9 µg/L | 2/2 | SYR4 | 2016–2019 |
| Dichloroacetic Acid | 1.795 µg/L No EPA limit set
worst single sample: 1.8 µg/L | 2/6 | SYR4 | 2014–2019 |
| Total Haloacetic Acids (HAA5) | 2.935 µg/L 4.9% of the EPA limit 60 µg/L
worst single sample: 3 µg/L | 2/6 | SYR4 | 2014–2019 |
| Combined Radium (-226 And -228) | 0.5000 pCi/L 10% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2015 |
| Combined Uranium | 1.8 µg/L 6% of the EPA limit 30 µg/L | 1/1 | SYR4 | 2015 |
| Trichloroacetic Acid | 1.2 µg/L No EPA limit set | 1/6 | SYR4 | 2014–2019 |
60 contaminants tested, none detected
Utility contact
Frequently asked questions about Precinct of Haverhill Corner
Is Precinct of Haverhill Corner tap water safe to drink?
EPA monitoring detected 14 contaminants in Precinct of Haverhill Corner's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Precinct of Haverhill Corner's water?
EPA monitoring detected Copper, Lead, Bromodichloromethane, Chloroform, Dibromochloromethane, and others. The full list with the level and data source for each is above.
How many people does Precinct of Haverhill Corner serve?
Precinct of Haverhill Corner reports serving 540 people in New Hampshire, per its EPA record.
Has Precinct of Haverhill Corner had any water quality violations?
The EPA has 41 violations on file for Precinct of Haverhill Corner, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.