← New Hampshire

Tap water quality report

Hampstead Area Water

EPA monitoring tested this supplier for 107 contaminants and detected 29. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

107
contaminants tested
29
detected
7,153
people served
42
health-based violations
Water source
SWP
Ownership
Private
Counties served
Rockingham

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

42
health-based violations
174
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2020-11-01
TT Health-based Resolved 2020-11-01
TT Health-based Resolved 2020-11-01
TT Health-based Resolved 2020-11-01
MCL Health-based Resolved 2020-07-01 → 2020-09-30
MCL Health-based Resolved 2020-07-01 → 2020-09-30
MCL Health-based Resolved 2020-07-01 → 2020-09-30
MCL Health-based Resolved 2020-07-01 → 2020-09-30
MCL Health-based Resolved 2018-07-01 → 2018-09-30
MCL Health-based Resolved 2018-07-01 → 2018-09-30

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
PFOA 0.0072 µg/L 12/24 2024
Pfhxa 0.0051 µg/L 8/24 2024
PFBS 0.0072 µg/L 7/24 2024
Pfpea 0.0050 µg/L 5/24 2024
PFOS 0.0075 µg/L 1/24 2024

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
336.4 µg/L 26%
of the EPA limit 1300 µg/L
worst single sample: 861 µg/L
94/118 SYR4 2014–2019
Arsenic
10.15 µg/L 102%
of the EPA limit, at the 95th percentile of samples — 10 µg/L
worst single sample: 34 µg/L
60/124 SYR4 2014–2019
Bromodichloromethane
7.685 µg/L
No EPA limit set
worst single sample: 16 µg/L
44/71 SYR4 2014–2019
Dibromochloromethane
6.4 µg/L
No EPA limit set
worst single sample: 12 µg/L
41/71 SYR4 2014–2019
Chloroform
9.7 µg/L
No EPA limit set
worst single sample: 18 µg/L
35/71 SYR4 2014–2019
Combined Radium (-226 And -228)
9.865 pCi/L 197%
of the EPA limit, at the 95th percentile of samples — 5 pCi/L
worst single sample: 16 pCi/L
32/34 SYR4 2014–2019
Combined Uranium
9.5 µg/L 32%
of the EPA limit 30 µg/L
worst single sample: 16 µg/L
31/36 SYR4 2014–2019
Lead
7 µg/L 47%
of the EPA limit 15 µg/L
worst single sample: 9 µg/L
31/118 SYR4 2014–2019
Gross Alpha, Excl. Radon And U
21.585 pCi/L 144%
of the EPA limit, at the 95th percentile of samples — 15 pCi/L
worst single sample: 30.7 pCi/L
24/30 SYR4 2014–2019
Barium
217.7 µg/L 11%
of the EPA limit 2000 µg/L
worst single sample: 276 µg/L
23/24 SYR4 2014–2019
TTHM
20.945 µg/L 26%
of the EPA limit 80 µg/L
worst single sample: 22 µg/L
22/36 SYR4 2016–2019
Chromium
17.1 µg/L 17%
of the EPA limit 100 µg/L
worst single sample: 19 µg/L
20/24 SYR4 2014–2019
Fluoride
842 µg/L 21%
of the EPA limit 4000 µg/L
worst single sample: 860 µg/L
19/24 SYR4 2014–2019
Lithium
26.9 µg/L
No EPA limit set
19/24 UCMR-5 2024
Bromoform
4.17 µg/L
No EPA limit set
worst single sample: 4.3 µg/L
14/71 SYR4 2014–2019
Lead
0.0020 mg/L 13%
of the EPA limit 0.0150 mg/L
10/10 LCR 2024
Selenium
7.55 µg/L 15%
of the EPA limit 50 µg/L
worst single sample: 10 µg/L
8/24 SYR4 2014–2019
Total Haloacetic Acids (HAA5)
14.36 µg/L 24%
of the EPA limit 60 µg/L
worst single sample: 14.4 µg/L
5/8 SYR4 2016–2019
Dibromoacetic Acid
2.51 µg/L
No EPA limit set
worst single sample: 2.6 µg/L
4/8 SYR4 2016–2019
Dichloroacetic Acid
8.44 µg/L
No EPA limit set
worst single sample: 8.8 µg/L
4/8 SYR4 2016–2019
Nitrate
1900 µg/L 19%
of the EPA limit 10000 µg/L
4/146 SYR4 2014–2019
Trichloroacetic Acid
5.555 µg/L
No EPA limit set
worst single sample: 5.6 µg/L
4/8 SYR4 2016–2019
Di(2-ethylhexyl) Phthalate
1.6 µg/L 27%
of the EPA limit 6 µg/L
1/34 SYR4 2014–2019
Toluene
0.5700 µg/L 0.1%
of the EPA limit 1000 µg/L
1/67 SYR4 2014–2019
78 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDinosebDiquatEthylene DibromideEndrinEthylbenzeneGlyphosateHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNetfosaaNfdhaNmefosaaNitriteOxamylPfbaPfdaPfdoaPfeesaPfhpaPfhpsPFHXSPfmbaPfmpaPFNAPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
KRISTEN TRAVASSOS

Frequently asked questions about Hampstead Area Water

Is Hampstead Area Water tap water safe to drink?

EPA monitoring detected 29 contaminants in Hampstead Area Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Hampstead Area Water's water?

EPA monitoring detected Copper, Arsenic, Bromodichloromethane, Dibromochloromethane, Chloroform, and others. The full list with the level and data source for each is above.

How many people does Hampstead Area Water serve?

Hampstead Area Water reports serving 7,153 people in New Hampshire, per its EPA record.

Has Hampstead Area Water had any water quality violations?

The EPA has 174 violations on file for Hampstead Area Water, of which 42 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.