Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2019-12-15 |
| TT | Health-based | Resolved | 2019-12-15 |
| TT | Health-based | Resolved | 2019-12-15 |
| TT | Health-based | Resolved | 2019-12-15 |
| MCL | Health-based | Resolved | 2010-04-01 → 2010-04-30 |
| MCL | Health-based | Resolved | 2010-04-01 → 2010-04-30 |
| MCL | Health-based | Resolved | 2010-04-01 → 2010-04-30 |
| MCL | Health-based | Resolved | 2010-04-01 → 2010-04-30 |
| MCL | Health-based | Resolved | 2000-05-01 → 2000-05-31 |
| MCL | Health-based | Resolved | 2000-05-01 → 2000-05-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 140 µg/L 11% of the EPA limit 1300 µg/L
worst single sample: 970 µg/L | 21/23 | SYR4 | 2014–2019 |
| Lead | 42 µg/L 280% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 66 µg/L | 9/23 | SYR4 | 2014–2019 |
| Combined Radium (-226 And -228) | 1.3 pCi/L 26% of the EPA limit 5 pCi/L | 4/5 | SYR4 | 2014–2019 |
| Barium | 122 µg/L 6.1% of the EPA limit 2000 µg/L
worst single sample: 133 µg/L | 3/3 | SYR4 | 2014–2018 |
| Chromium | 6.7 µg/L 6.7% of the EPA limit 100 µg/L
worst single sample: 7 µg/L | 3/3 | SYR4 | 2014–2018 |
| Fluoride | 437 µg/L 11% of the EPA limit 4000 µg/L
worst single sample: 450 µg/L | 3/3 | SYR4 | 2014–2018 |
| Gross Alpha, Excl. Radon And U | 2 pCi/L 13% of the EPA limit 15 pCi/L | 3/5 | SYR4 | 2014–2019 |
| Arsenic | 1 µg/L 10% of the EPA limit 10 µg/L | 1/3 | SYR4 | 2014–2018 |
| Combined Uranium | 0.2000 µg/L 0.7% of the EPA limit 30 µg/L | 1/5 | SYR4 | 2014–2019 |
| Lead | 0.0340 mg/L 227% above the EPA limit of 0.0150 mg/L | 1/1 | LCR | 2019 |
59 contaminants tested, none detected
Utility contact
Frequently asked questions about Abenaki Water/Tioga Belmont
Is Abenaki Water/Tioga Belmont tap water safe to drink?
EPA monitoring detected 10 contaminants in Abenaki Water/Tioga Belmont's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Abenaki Water/Tioga Belmont's water?
EPA monitoring detected Copper, Lead, Combined Radium (-226 And -228), Barium, Chromium, and others. The full list with the level and data source for each is above.
How many people does Abenaki Water/Tioga Belmont serve?
Abenaki Water/Tioga Belmont reports serving 55 people in Connecticut, per its EPA record.
Has Abenaki Water/Tioga Belmont had any water quality violations?
The EPA has 140 violations on file for Abenaki Water/Tioga Belmont, of which 34 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.