Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2012-10-01 → 2012-10-31 |
| MCL | Health-based | Resolved | 2012-10-01 → 2012-10-31 |
| MCL | Health-based | Resolved | 2012-10-01 → 2012-10-31 |
| MCL | Health-based | Resolved | 2012-10-01 → 2012-10-31 |
| TT | Health-based | Resolved | 1994-01-01 → 1995-07-03 |
| TT | Health-based | Resolved | 1994-01-01 → 1995-07-03 |
| MCL | Health-based | Archived | 1993-08-01 → 1993-08-31 |
| MCL | Health-based | Archived | 1993-08-01 → 1993-08-31 |
| MCL | Health-based | Archived | 1993-08-01 → 1993-08-31 |
| Other | Monitoring | Resolved | 2016-07-01 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 65.8346 µg/L 5.1% of the EPA limit 1300 µg/L
worst single sample: 85 µg/L | 44/44 | SYR4 | 2015–2019 |
| Nitrate | 1656.32 µg/L 17% of the EPA limit 10000 µg/L
worst single sample: 1664.5 µg/L | 24/24 | SYR4 | 2014–2019 |
| Lead | 0.0010 mg/L 6.7% of the EPA limit 0.0150 mg/L | 13/13 | LCR | 2024 |
| Bromoform | 5.525 µg/L No EPA limit set
worst single sample: 6.2 µg/L | 10/20 | SYR4 | 2014–2019 |
| Dibromochloromethane | 3.11 µg/L No EPA limit set
worst single sample: 3.2 µg/L | 10/20 | SYR4 | 2014–2019 |
| Lead | 8.4112 µg/L 56% of the EPA limit 15 µg/L
worst single sample: 9.7 µg/L | 10/40 | SYR4 | 2016–2019 |
| TTHM | 9.415 µg/L 12% of the EPA limit 80 µg/L
worst single sample: 10 µg/L | 10/20 | SYR4 | 2014–2019 |
| Bromodichloromethane | 1 µg/L No EPA limit set | 7/20 | SYR4 | 2014–2019 |
| Total Haloacetic Acids (HAA5) | 2.71 µg/L 4.5% of the EPA limit 60 µg/L
worst single sample: 3.1 µg/L | 7/10 | SYR4 | 2014–2019 |
| Dibromoacetic Acid | 1.76175 µg/L No EPA limit set
worst single sample: 1.8 µg/L | 6/10 | SYR4 | 2014–2019 |
| Barium | 4.07 µg/L 0.2% of the EPA limit 2000 µg/L
worst single sample: 4.1 µg/L | 4/4 | SYR4 | 2015–2018 |
| Fluoride | 328.5 µg/L 8.2% of the EPA limit 4000 µg/L
worst single sample: 330 µg/L | 4/4 | SYR4 | 2015–2018 |
| Combined Radium (-226 And -228) | 0.8600 pCi/L 17% of the EPA limit 5 pCi/L
worst single sample: 0.9000 pCi/L | 2/2 | SYR4 | 2014 |
| Gross Alpha, Excl. Radon And U | 0.5800 pCi/L 3.9% of the EPA limit 15 pCi/L
worst single sample: 0.6000 pCi/L | 2/2 | SYR4 | 2014 |
| Monochloroacetic Acid | 3.1 µg/L No EPA limit set | 1/10 | SYR4 | 2014–2019 |
92 contaminants tested, none detected
Utility contact
Frequently asked questions about Lower Bartlett Water Pct
Is Lower Bartlett Water Pct tap water safe to drink?
EPA monitoring detected 15 contaminants in Lower Bartlett Water Pct's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Lower Bartlett Water Pct's water?
EPA monitoring detected Copper, Nitrate, Lead, Bromoform, Dibromochloromethane, and others. The full list with the level and data source for each is above.
How many people does Lower Bartlett Water Pct serve?
Lower Bartlett Water Pct reports serving 3,850 people in New Hampshire, per its EPA record.
Has Lower Bartlett Water Pct had any water quality violations?
The EPA has 15 violations on file for Lower Bartlett Water Pct, of which 9 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.