← Nebraska

Tap water quality report

Ceresco, Village of

EPA monitoring tested this supplier for 75 contaminants and detected 10. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

75
contaminants tested
10
detected
919
people served
6
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Saunders

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

6
health-based violations
6
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 1999-07-01 → 1999-07-31
MCL Health-based Resolved 1999-07-01 → 1999-07-31
MCL Health-based Resolved 1999-07-01 → 1999-07-31
MCL Health-based Resolved 1999-07-01 → 1999-07-31
MCL Health-based Resolved 1980-10-01 → 1981-09-30
MCL Health-based Archived 1977-06-22 → 1977-07-21

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
309.8 µg/L 24%
of the EPA limit 1300 µg/L
worst single sample: 538 µg/L
30/30 SYR4 2013–2019
Lead
4.505 µg/L 30%
of the EPA limit 15 µg/L
worst single sample: 6 µg/L
26/30 SYR4 2013–2019
Nitrate-Nitrite
331 µg/L 3.3%
of the EPA limit 10000 µg/L
16/16 SYR4 2012–2019
Lead
0.0160 mg/L 107%
above the EPA limit of 0.0150 mg/L
7/7 LCR 2025
Barium
33.56 µg/L 1.7%
of the EPA limit 2000 µg/L
worst single sample: 33.6 µg/L
3/3 SYR4 2013–2019
Fluoride
643.1 µg/L 16%
of the EPA limit 4000 µg/L
worst single sample: 644 µg/L
3/3 SYR4 2013–2019
Arsenic
1.05 µg/L 11%
of the EPA limit 10 µg/L
1/2 SYR4 2014–2017
Combined Radium (-226 And -228)
3.26 pCi/L 65%
of the EPA limit 5 pCi/L
1/1 SYR4 2017
Combined Uranium
3.278 µg/L 11%
of the EPA limit 30 µg/L
1/1 SYR4 2014
Heptachlor Epoxide
0.0750 µg/L 37%
of the EPA limit 0.2000 µg/L
1/10 SYR4 2013–2019
65 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromodichloromethaneBromoformChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChloroformChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromoacetic AcidDibromochloromethaneDichloroacetic AcidDinosebDiquatEthylene DibromideEndrinEthylbenzeneHexachlorobenzeneHeptachlorHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTTHMTetrachloroethyleneThallium, TotalTolueneTotal Haloacetic Acids (HAA5)ToxapheneTrichloroacetic AcidTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
LINDGREN, JOAN
Phone
402-665-2391
Email
[email protected]

Frequently asked questions about Ceresco, Village of

Is Ceresco, Village of tap water safe to drink?

EPA monitoring detected 10 contaminants in Ceresco, Village of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Ceresco, Village of's water?

EPA monitoring detected Copper, Lead, Nitrate-Nitrite, Lead, Barium, and others. The full list with the level and data source for each is above.

How many people does Ceresco, Village of serve?

Ceresco, Village of reports serving 919 people in Nebraska, per its EPA record.

Has Ceresco, Village of had any water quality violations?

The EPA has 6 violations on file for Ceresco, Village of, of which 6 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.