Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2005-10-01 → 2005-12-31 |
| MCL | Health-based | Resolved | 2005-10-01 → 2005-12-31 |
| MCL | Health-based | Resolved | 2005-10-01 → 2005-12-31 |
| MCL | Health-based | Resolved | 2005-10-01 → 2005-12-31 |
| MCL | Health-based | Resolved | 2005-10-01 → 2005-12-31 |
| MCL | Health-based | Resolved | 2005-10-01 → 2005-12-31 |
| MCL | Health-based | Resolved | 2005-07-01 → 2005-09-30 |
| MCL | Health-based | Resolved | 2005-07-01 → 2005-09-30 |
| MCL | Health-based | Resolved | 2005-07-01 → 2005-09-30 |
| MCL | Health-based | Resolved | 2005-07-01 → 2005-09-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate-Nitrite | 5750.5 µg/L 58% of the EPA limit 10000 µg/L
worst single sample: 7590 µg/L | 62/62 | SYR4 | 2012–2019 |
| Copper | 299.55 µg/L 23% of the EPA limit 1300 µg/L
worst single sample: 550 µg/L | 60/60 | SYR4 | 2013–2019 |
| Lead | 9.4305 µg/L 63% of the EPA limit 15 µg/L
worst single sample: 12.7 µg/L | 54/60 | SYR4 | 2013–2019 |
| Bromodichloromethane | 10.4625 µg/L No EPA limit set
worst single sample: 12.9 µg/L | 14/14 | SYR4 | 2012–2019 |
| Bromoform | 18.915 µg/L No EPA limit set
worst single sample: 23.4 µg/L | 14/14 | SYR4 | 2012–2019 |
| Chloroform | 2.765 µg/L No EPA limit set
worst single sample: 3.35 µg/L | 14/14 | SYR4 | 2012–2019 |
| Dibromochloromethane | 23.63 µg/L No EPA limit set
worst single sample: 28.7 µg/L | 14/14 | SYR4 | 2012–2019 |
| Lead | 0.0120 mg/L 80% of the EPA limit 0.0150 mg/L | 14/14 | LCR | 2025 |
| TTHM | 53.87 µg/L 67% of the EPA limit 80 µg/L
worst single sample: 68.3 µg/L | 14/14 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 6.86 µg/L No EPA limit set
worst single sample: 7.37 µg/L | 11/11 | SYR4 | 2014–2019 |
| Total Haloacetic Acids (HAA5) | 11.1 µg/L 19% of the EPA limit 60 µg/L
worst single sample: 12 µg/L | 11/11 | SYR4 | 2014–2019 |
| Trichloroacetic Acid | 0.7940 µg/L No EPA limit set
worst single sample: 0.8000 µg/L | 7/11 | SYR4 | 2014–2019 |
| Dichloroacetic Acid | 1.7525 µg/L No EPA limit set
worst single sample: 1.84 µg/L | 6/11 | SYR4 | 2014–2019 |
| Monobromoacetic Acid | 1.892 µg/L No EPA limit set
worst single sample: 1.98 µg/L | 5/11 | SYR4 | 2014–2019 |
| Arsenic | 8.021 µg/L 80% of the EPA limit 10 µg/L
worst single sample: 8.1 µg/L | 3/3 | SYR4 | 2012–2018 |
| Lithium | 66.2 µg/L No EPA limit set | 2/2 | UCMR-5 | 2024 |
| 1,2-Dichloroethane | 0.5410 µg/L 11% of the EPA limit 5 µg/L | 1/14 | SYR4 | 2012–2019 |
| Barium | 55.1 µg/L 2.8% of the EPA limit 2000 µg/L | 1/1 | SYR4 | 2014 |
| Chromium | 4.14 µg/L 4.1% of the EPA limit 100 µg/L | 1/1 | SYR4 | 2014 |
| Combined Radium (-226 And -228) | 0.6450 pCi/L 13% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2016 |
| Fluoride | 911 µg/L 23% of the EPA limit 4000 µg/L | 1/1 | SYR4 | 2014 |
| Selenium | 9.33 µg/L 19% of the EPA limit 50 µg/L | 1/1 | SYR4 | 2014 |
82 contaminants tested, none detected
Utility contact
Frequently asked questions about Mccook, City of
Is Mccook, City of tap water safe to drink?
EPA monitoring detected 22 contaminants in Mccook, City of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Mccook, City of's water?
EPA monitoring detected Nitrate-Nitrite, Copper, Lead, Bromodichloromethane, Bromoform, and others. The full list with the level and data source for each is above.
How many people does Mccook, City of serve?
Mccook, City of reports serving 7,450 people in Nebraska, per its EPA record.
Has Mccook, City of had any water quality violations?
The EPA has 123 violations on file for Mccook, City of, of which 122 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.