← Nebraska

Tap water quality report

Lincoln, City of

EPA monitoring tested this supplier for 106 contaminants and detected 23. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

106
contaminants tested
23
detected
296,000
people served
8
health-based violations
Water source
Ground water under surface influence
Ownership
Local government
Counties served
Lancaster

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

8
health-based violations
8
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2004-06-01 → 2004-06-30
MCL Health-based Resolved 2004-06-01 → 2004-06-30
MCL Health-based Resolved 2004-06-01 → 2004-06-30
MCL Health-based Resolved 2004-06-01 → 2004-06-30
MCL Health-based Resolved 2004-06-01 → 2004-06-30
MCL Health-based Resolved 2004-06-01 → 2004-06-30
MCL Health-based Resolved 2004-06-01 → 2004-06-30
MCL Health-based Resolved 2004-06-01 → 2004-06-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Bromodichloromethane
15.18 µg/L
No EPA limit set
worst single sample: 17 µg/L
223/223 SYR4 2012–2019
Chloroform
18.78 µg/L
No EPA limit set
worst single sample: 28.1 µg/L
223/223 SYR4 2012–2019
Dibromochloromethane
9.649 µg/L
No EPA limit set
worst single sample: 12.8 µg/L
223/223 SYR4 2012–2019
TTHM
44.05 µg/L 55%
of the EPA limit 80 µg/L
worst single sample: 50.4 µg/L
223/223 SYR4 2012–2019
Dichloroacetic Acid
13.65 µg/L
No EPA limit set
worst single sample: 18.1 µg/L
216/217 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
24.35 µg/L 41%
of the EPA limit 60 µg/L
worst single sample: 35.2 µg/L
216/217 SYR4 2012–2019
Trichloroacetic Acid
8.1025 µg/L
No EPA limit set
worst single sample: 15.8 µg/L
216/217 SYR4 2012–2019
Dibromoacetic Acid
2.907 µg/L
No EPA limit set
worst single sample: 4.23 µg/L
207/217 SYR4 2012–2019
Bromoform
2.235 µg/L
No EPA limit set
worst single sample: 2.43 µg/L
202/223 SYR4 2012–2019
Copper
907 µg/L 70%
of the EPA limit 1300 µg/L
worst single sample: 1560 µg/L
157/157 SYR4 2013–2019
Lead
6.123 µg/L 41%
of the EPA limit 15 µg/L
worst single sample: 403 µg/L
112/157 SYR4 2013–2019
Fluoride
992.95 µg/L 25%
of the EPA limit 4000 µg/L
worst single sample: 1040 µg/L
102/102 SYR4 2012–2019
Nitrate-Nitrite
2849.5 µg/L 28%
of the EPA limit 10000 µg/L
worst single sample: 3130 µg/L
32/32 SYR4 2012–2019
Bromate
3.52 µg/L 35%
of the EPA limit 10 µg/L
worst single sample: 4.2 µg/L
18/30 SYR4 2012–2019
Arsenic
8.9775 µg/L 90%
of the EPA limit 10 µg/L
worst single sample: 9.75 µg/L
16/16 SYR4 2012–2019
Lead
0.0045 mg/L 30%
of the EPA limit 0.0150 mg/L
11/11 LCR 2025
Atrazine
0.3355 µg/L 11%
of the EPA limit 3 µg/L
worst single sample: 0.4300 µg/L
10/16 SYR4 2012–2019
Barium
143.75 µg/L 7.2%
of the EPA limit 2000 µg/L
worst single sample: 154 µg/L
6/6 SYR4 2013–2019
Lithium
23.7 µg/L
No EPA limit set
6/6 UCMR-5 2023
Chromium
1.409 µg/L 1.4%
of the EPA limit 100 µg/L
worst single sample: 1.42 µg/L
2/6 SYR4 2013–2019
Combined Radium (-226 And -228)
1.01915 pCi/L 20%
of the EPA limit 5 pCi/L
worst single sample: 1.04 pCi/L
2/2 SYR4 2015
Antimony, Total
0.6720 µg/L 11%
of the EPA limit 6 µg/L
1/6 SYR4 2013–2019
Selenium
6.61 µg/L 13%
of the EPA limit 50 µg/L
1/6 SYR4 2013–2019
83 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAsbestosBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNetfosaaNfdhaNmefosaaOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
OWEN, STEVEN R
Phone
402-441-5925
Email
[email protected]

Frequently asked questions about Lincoln, City of

Is Lincoln, City of tap water safe to drink?

EPA monitoring detected 23 contaminants in Lincoln, City of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Lincoln, City of's water?

EPA monitoring detected Bromodichloromethane, Chloroform, Dibromochloromethane, TTHM, Dichloroacetic Acid, and others. The full list with the level and data source for each is above.

How many people does Lincoln, City of serve?

Lincoln, City of reports serving 296,000 people in Nebraska, per its EPA record.

Has Lincoln, City of had any water quality violations?

The EPA has 8 violations on file for Lincoln, City of, of which 8 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?