← Nebraska

Tap water quality report

Valley, City of

EPA monitoring tested this supplier for 73 contaminants and detected 17. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

73
contaminants tested
17
detected
3,294
people served
7
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Douglas

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

7
health-based violations
7
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2014-10-01 → 2014-10-31
MCL Health-based Resolved 2014-10-01 → 2014-10-31
MCL Health-based Resolved 2014-10-01 → 2014-10-31
MCL Health-based Resolved 2014-10-01 → 2014-10-31
MCL Health-based Archived 1993-04-01 → 1993-04-30
MCL Health-based Archived 1993-04-01 → 1993-04-30
MCL Health-based Archived 1993-04-01 → 1993-04-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Fluoride
1490 µg/L 37%
of the EPA limit 4000 µg/L
worst single sample: 1540 µg/L
97/97 SYR4 2012–2019
Copper
777.2 µg/L 60%
of the EPA limit 1300 µg/L
worst single sample: 1220 µg/L
33/33 SYR4 2013–2019
Lead
13.76 µg/L 92%
of the EPA limit 15 µg/L
worst single sample: 16.8 µg/L
17/33 SYR4 2013–2019
Nitrate-Nitrite
465 µg/L 4.7%
of the EPA limit 10000 µg/L
14/16 SYR4 2012–2019
Bromodichloromethane
11.835 µg/L
No EPA limit set
worst single sample: 12 µg/L
12/12 SYR4 2012–2019
Bromoform
4.3885 µg/L
No EPA limit set
worst single sample: 4.79 µg/L
12/12 SYR4 2012–2019
Chloroform
7.566 µg/L
No EPA limit set
worst single sample: 7.61 µg/L
12/12 SYR4 2012–2019
Dibromochloromethane
12.885 µg/L
No EPA limit set
worst single sample: 13.6 µg/L
12/12 SYR4 2012–2019
TTHM
36.72 µg/L 46%
of the EPA limit 80 µg/L
worst single sample: 37.6 µg/L
12/12 SYR4 2012–2019
Lead
0.0020 mg/L 13%
of the EPA limit 0.0150 mg/L
10/10 LCR 2025
Total Haloacetic Acids (HAA5)
4.924 µg/L 8.2%
of the EPA limit 60 µg/L
worst single sample: 5.19 µg/L
8/9 SYR4 2012–2019
Trichloroacetic Acid
1.6281 µg/L
No EPA limit set
worst single sample: 1.92 µg/L
7/9 SYR4 2012–2019
Dibromoacetic Acid
2.4585 µg/L
No EPA limit set
worst single sample: 2.64 µg/L
4/9 SYR4 2012–2019
Dichloroacetic Acid
1.934 µg/L
No EPA limit set
worst single sample: 2.06 µg/L
4/9 SYR4 2012–2019
Atrazine
0.1224 µg/L 4.1%
of the EPA limit 3 µg/L
worst single sample: 0.1240 µg/L
2/8 SYR4 2012–2019
Arsenic
2.24 µg/L 22%
of the EPA limit 10 µg/L
1/1 SYR4 2017
Barium
132 µg/L 6.6%
of the EPA limit 2000 µg/L
1/1 SYR4 2015
56 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined Radium (-226 And -228)DichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndrinEthylbenzeneHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
LEWIS, LINDA
Phone
402-359-2251
Email
[email protected]

Frequently asked questions about Valley, City of

Is Valley, City of tap water safe to drink?

EPA monitoring detected 17 contaminants in Valley, City of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Valley, City of's water?

EPA monitoring detected Fluoride, Copper, Lead, Nitrate-Nitrite, Bromodichloromethane, and others. The full list with the level and data source for each is above.

How many people does Valley, City of serve?

Valley, City of reports serving 3,294 people in Nebraska, per its EPA record.

Has Valley, City of had any water quality violations?

The EPA has 7 violations on file for Valley, City of, of which 7 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.