← Nebraska

Tap water quality report

Beemer, Village of

EPA monitoring tested this supplier for 70 contaminants and detected 12. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

70
contaminants tested
12
detected
650
people served
35
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Cuming

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

35
health-based violations
37
violations on file
2
still open
ViolationTypeStatusPeriod
MCL Health-based Archived 2026-01-01 → 2026-03-31
MCL Health-based Archived 2026-01-01 → 2026-03-31
MCL Health-based Resolved 2013-10-01 → 2013-12-31
MCL Health-based Resolved 2013-10-01 → 2013-12-31
MCL Health-based Resolved 2013-10-01 → 2013-12-31
MCL Health-based Resolved 2013-10-01 → 2013-12-31
MCL Health-based Resolved 2013-07-01 → 2013-09-30
MCL Health-based Resolved 2013-07-01 → 2013-09-30
MCL Health-based Resolved 2013-07-01 → 2013-09-30
MCL Health-based Resolved 2013-07-01 → 2013-09-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate-Nitrite
9733.5 µg/L 97%
of the EPA limit 10000 µg/L
worst single sample: 15500 µg/L
72/72 SYR4 2012–2019
Selenium
78.09 µg/L 156%
of the EPA limit, at the 95th percentile of samples — 50 µg/L
worst single sample: 101 µg/L
35/35 SYR4 2012–2019
Copper
1540.5 µg/L 119%
of the EPA limit, at the 95th percentile of samples — 1300 µg/L
worst single sample: 3280 µg/L
32/32 SYR4 2013–2019
Lead
4.835 µg/L 32%
of the EPA limit 15 µg/L
worst single sample: 8.42 µg/L
11/32 SYR4 2013–2019
Lead
0.00058 mg/L 3.9%
of the EPA limit 0.0150 mg/L
9/9 LCR 2025
Arsenic
8.598 µg/L 86%
of the EPA limit 10 µg/L
worst single sample: 8.79 µg/L
4/4 SYR4 2012–2018
Combined Uranium
14.0738 µg/L 47%
of the EPA limit 30 µg/L
worst single sample: 14.3487 µg/L
4/4 SYR4 2014–2015
Barium
207.7 µg/L 10%
of the EPA limit 2000 µg/L
worst single sample: 211 µg/L
3/3 SYR4 2012–2018
Chromium
11.001 µg/L 11%
of the EPA limit 100 µg/L
worst single sample: 11.8 µg/L
3/3 SYR4 2012–2018
Combined Radium (-226 And -228)
1.309 pCi/L 26%
of the EPA limit 5 pCi/L
worst single sample: 1.41 pCi/L
3/3 SYR4 2012–2017
Fluoride
348.3 µg/L 8.7%
of the EPA limit 4000 µg/L
worst single sample: 349 µg/L
3/3 SYR4 2012–2018
Gross Alpha, Excl. Radon And U
2.27 pCi/L 15%
of the EPA limit 15 pCi/L
worst single sample: 2.4 pCi/L
3/4 SYR4 2014–2015
58 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromodichloromethaneBromoformChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChloroformDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromochloromethaneDinosebDiquatEthylene DibromideEndrinEthylbenzeneGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorOxamylPentachlorophenolPicloramSimazineStyreneTTHMTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
MEAIKE, TRACI
Phone
402-528-3253
Email
[email protected]

Frequently asked questions about Beemer, Village of

Is Beemer, Village of tap water safe to drink?

EPA monitoring detected 12 contaminants in Beemer, Village of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Beemer, Village of's water?

EPA monitoring detected Nitrate-Nitrite, Selenium, Copper, Lead, Lead, and others. The full list with the level and data source for each is above.

How many people does Beemer, Village of serve?

Beemer, Village of reports serving 650 people in Nebraska, per its EPA record.

Has Beemer, Village of had any water quality violations?

The EPA has 37 violations on file for Beemer, Village of, of which 35 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.