EPA monitoring tested this supplier for 68 contaminants and detected 10. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

68
contaminants tested
10
detected
549
people served
133
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Chase

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

133
health-based violations
148
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2020-04-01 → 2020-06-30
MCL Health-based Resolved 2020-04-01 → 2020-06-30
MCL Health-based Resolved 2020-04-01 → 2020-06-30
MCL Health-based Resolved 2020-04-01 → 2020-06-30
MCL Health-based Resolved 2020-04-01 → 2020-06-30
MCL Health-based Resolved 2020-01-01 → 2020-03-31
MCL Health-based Resolved 2020-01-01 → 2020-03-31
MCL Health-based Resolved 2020-01-01 → 2020-03-31
MCL Health-based Resolved 2020-01-01 → 2020-03-31
MCL Health-based Resolved 2020-01-01 → 2020-03-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Arsenic
13.55 µg/L 136%
of the EPA limit, at the 95th percentile of samples — 10 µg/L
worst single sample: 14.3 µg/L
95/95 SYR4 2012–2019
Nitrate-Nitrite
2570 µg/L 26%
of the EPA limit 10000 µg/L
worst single sample: 2620 µg/L
48/48 SYR4 2012–2019
Copper
127.2 µg/L 9.8%
of the EPA limit 1300 µg/L
worst single sample: 131 µg/L
20/20 SYR4 2014–2017
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
12/12 LCR 2023
Barium
124.05 µg/L 6.2%
of the EPA limit 2000 µg/L
worst single sample: 126 µg/L
4/4 SYR4 2013–2019
Chromium
4.0805 µg/L 4.1%
of the EPA limit 100 µg/L
worst single sample: 4.49 µg/L
4/4 SYR4 2013–2019
Fluoride
1006.4 µg/L 25%
of the EPA limit 4000 µg/L
worst single sample: 1010 µg/L
4/4 SYR4 2013–2019
Lead
0.9469 µg/L 6.3%
of the EPA limit 15 µg/L
worst single sample: 0.9630 µg/L
4/20 SYR4 2014–2017
Combined Radium (-226 And -228)
2.2186 pCi/L 44%
of the EPA limit 5 pCi/L
worst single sample: 2.4 pCi/L
3/3 SYR4 2012–2018
Endrin
0.1040 µg/L 5.2%
of the EPA limit 2 µg/L
1/9 SYR4 2013–2019
58 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromodichloromethaneBromoformChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChloroformDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromochloromethaneDinosebDiquatEthylene DibromideEthylbenzeneGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTTHMTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
LAWLESS, SHANE D
Phone
308-883-2079
Email
[email protected]

Frequently asked questions about Wauneta, Village of

Is Wauneta, Village of tap water safe to drink?

EPA monitoring detected 10 contaminants in Wauneta, Village of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Wauneta, Village of's water?

EPA monitoring detected Arsenic, Nitrate-Nitrite, Copper, Lead, Barium, and others. The full list with the level and data source for each is above.

How many people does Wauneta, Village of serve?

Wauneta, Village of reports serving 549 people in Nebraska, per its EPA record.

Has Wauneta, Village of had any water quality violations?

The EPA has 148 violations on file for Wauneta, Village of, of which 133 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.