← Nebraska

Tap water quality report

Oakland, City of

EPA monitoring tested this supplier for 73 contaminants and detected 16. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

73
contaminants tested
16
detected
1,300
people served
0
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Burt

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
5
violations on file
5
still open
ViolationTypeStatusPeriod
RPT Monitoring Unaddressed 2024-10-17
RPT Monitoring Unaddressed 2024-10-17
MR Monitoring Unaddressed 2023-01-01
MR Monitoring Unaddressed 2023-01-01
MR Monitoring Unaddressed 2023-01-01

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
276 µg/L 21%
of the EPA limit 1300 µg/L
worst single sample: 429 µg/L
29/30 SYR4 2013–2019
Lead
34.37 µg/L 229%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 68.2 µg/L
18/30 SYR4 2013–2019
Nitrate-Nitrite
956 µg/L 9.6%
of the EPA limit 10000 µg/L
16/16 SYR4 2012–2019
Lead
0.0027 mg/L 18%
of the EPA limit 0.0150 mg/L
9/9 LCR 2022
Bromoform
7.88 µg/L
No EPA limit set
worst single sample: 9.49 µg/L
8/11 SYR4 2013–2019
TTHM
11.7615 µg/L 15%
of the EPA limit 80 µg/L
worst single sample: 13.9 µg/L
8/11 SYR4 2013–2019
Dibromochloromethane
3.122 µg/L
No EPA limit set
worst single sample: 3.53 µg/L
7/11 SYR4 2013–2019
Dibromoacetic Acid
2.06 µg/L
No EPA limit set
worst single sample: 2.09 µg/L
6/9 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
2.06 µg/L 3.4%
of the EPA limit 60 µg/L
worst single sample: 2.09 µg/L
6/9 SYR4 2013–2019
Bromodichloromethane
0.8860 µg/L
No EPA limit set
worst single sample: 0.9100 µg/L
4/11 SYR4 2013–2019
Combined Radium (-226 And -228)
2.8235 pCi/L 56%
of the EPA limit 5 pCi/L
worst single sample: 2.83 pCi/L
2/2 SYR4 2012–2018
Arsenic
1.01 µg/L 10%
of the EPA limit 10 µg/L
1/1 SYR4 2017
Barium
69 µg/L 3.5%
of the EPA limit 2000 µg/L
1/1 SYR4 2015
Chromium
4.37 µg/L 4.4%
of the EPA limit 100 µg/L
1/1 SYR4 2015
Fluoride
1100 µg/L 28%
of the EPA limit 4000 µg/L
1/1 SYR4 2015
Heptachlor Epoxide
0.0500 µg/L 25%
of the EPA limit 0.2000 µg/L
1/5 SYR4 2012–2018
57 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChloroformDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDichloroacetic AcidDinosebDiquatEthylene DibromideEndrinEthylbenzeneHexachlorobenzeneHeptachlorHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroacetic AcidTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
TANKSLEY III, DANIEL
Phone
402-870-1407
Email
[email protected]

Frequently asked questions about Oakland, City of

Is Oakland, City of tap water safe to drink?

EPA monitoring detected 16 contaminants in Oakland, City of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Oakland, City of's water?

EPA monitoring detected Copper, Lead, Nitrate-Nitrite, Lead, Bromoform, and others. The full list with the level and data source for each is above.

How many people does Oakland, City of serve?

Oakland, City of reports serving 1,300 people in Nebraska, per its EPA record.

Has Oakland, City of had any water quality violations?

The EPA has 5 violations on file for Oakland, City of, of which 0 are health-based (a contaminant limit or required treatment was breached) and 5 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.