Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2024-10-17 |
| MCL | Health-based | Resolved | 2012-07-01 → 2012-07-31 |
| MCL | Health-based | Resolved | 2012-07-01 → 2012-07-31 |
| MCL | Health-based | Resolved | 2012-07-01 → 2012-07-31 |
| MCL | Health-based | Resolved | 2012-07-01 → 2012-07-31 |
| MCL | Health-based | Resolved | 2012-07-01 → 2012-07-31 |
| MCL | Health-based | Resolved | 2000-08-01 → 2000-08-31 |
| MCL | Health-based | Resolved | 2000-08-01 → 2000-08-31 |
| MCL | Health-based | Resolved | 2000-08-01 → 2000-08-31 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Total Haloacetic Acids (HAA5) | 41.4 µg/L 69% of the EPA limit 60 µg/L
worst single sample: 53 µg/L | 84/86 | SYR4 | 2012–2019 |
| TTHM | 44.83 µg/L 56% of the EPA limit 80 µg/L
worst single sample: 71 µg/L | 83/84 | SYR4 | 2012–2019 |
| Chloroform | 30.15 µg/L No EPA limit set
worst single sample: 35.8 µg/L | 71/72 | SYR4 | 2013–2019 |
| Bromodichloromethane | 11.3 µg/L No EPA limit set
worst single sample: 13 µg/L | 70/72 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 27.435 µg/L No EPA limit set
worst single sample: 34.3 µg/L | 70/72 | SYR4 | 2013–2019 |
| Trichloroacetic Acid | 9.465 µg/L No EPA limit set
worst single sample: 11.1 µg/L | 68/72 | SYR4 | 2013–2019 |
| Dibromochloromethane | 4.03 µg/L No EPA limit set
worst single sample: 4.5 µg/L | 59/72 | SYR4 | 2013–2019 |
| Copper | 228.15 µg/L 18% of the EPA limit 1300 µg/L
worst single sample: 413 µg/L | 34/71 | SYR4 | 2012–2018 |
| Monochloroacetic Acid | 3.145 µg/L No EPA limit set
worst single sample: 4.7 µg/L | 34/72 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 1.7 µg/L No EPA limit set
worst single sample: 2 µg/L | 21/72 | SYR4 | 2013–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 17/17 | LCR | 2025 |
| Fluoride | 896 µg/L 22% of the EPA limit 4000 µg/L
worst single sample: 910 µg/L | 15/15 | SYR4 | 2013–2017 |
| Nitrate | 1640 µg/L 16% of the EPA limit 10000 µg/L | 8/80 | SYR4 | 2012–2019 |
| Lead | 27.6 µg/L 184% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 36 µg/L | 7/71 | SYR4 | 2012–2018 |
| Dichloromethane | 0.8800 µg/L 18% of the EPA limit 5 µg/L
worst single sample: 0.9000 µg/L | 2/24 | SYR4 | 2012–2019 |
85 contaminants tested, none detected
Utility contact
Frequently asked questions about Bell Arthur Water Corp
Is Bell Arthur Water Corp tap water safe to drink?
EPA monitoring detected 22 contaminants in Bell Arthur Water Corp's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Bell Arthur Water Corp's water?
EPA monitoring detected Total Haloacetic Acids (HAA5), TTHM, Chloroform, Bromodichloromethane, Dichloroacetic Acid, and others. The full list with the level and data source for each is above.
How many people does Bell Arthur Water Corp serve?
Bell Arthur Water Corp reports serving 11,483 people in North Carolina, per its EPA record.
Has Bell Arthur Water Corp had any water quality violations?
The EPA has 145 violations on file for Bell Arthur Water Corp, of which 11 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.