← North Carolina

Tap water quality report

Southern Pines, Town of

EPA monitoring tested this supplier for 105 contaminants and detected 14. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

105
contaminants tested
14
detected
24,102
people served
41
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Moore

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

41
health-based violations
126
violations on file
6
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2024-10-17
TT Health-based Resolved 2024-10-17
MCL Health-based Resolved 2004-01-01 → 2004-03-31
MCL Health-based Resolved 2004-01-01 → 2004-03-31
MCL Health-based Resolved 2004-01-01 → 2004-03-31
MCL Health-based Resolved 2003-10-01 → 2003-12-31
MCL Health-based Resolved 2003-10-01 → 2003-12-31
MCL Health-based Resolved 2003-10-01 → 2003-12-31
MCL Health-based Resolved 2003-10-01 → 2003-12-31
MCL Health-based Resolved 2003-10-01 → 2003-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
TTHM
59.75 µg/L 75%
of the EPA limit 80 µg/L
worst single sample: 75 µg/L
126/126 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
66.5 µg/L 111%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 102.6 µg/L
123/128 SYR4 2012–2019
Chloroform
37.45 µg/L
No EPA limit set
worst single sample: 60 µg/L
100/100 SYR4 2013–2019
Dichloroacetic Acid
42.125 µg/L
No EPA limit set
worst single sample: 58.4 µg/L
94/100 SYR4 2013–2019
Trichloroacetic Acid
16.635 µg/L
No EPA limit set
worst single sample: 23.2 µg/L
94/100 SYR4 2013–2019
Monochloroacetic Acid
5.545 µg/L
No EPA limit set
worst single sample: 6.9 µg/L
72/100 SYR4 2013–2019
Bromodichloromethane
4 µg/L
No EPA limit set
worst single sample: 5 µg/L
70/100 SYR4 2013–2019
Copper
274.7 µg/L 21%
of the EPA limit 1300 µg/L
worst single sample: 401 µg/L
64/246 SYR4 2012–2019
Lead
44.95 µg/L 300%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 241 µg/L
48/247 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
21/21 LCR 2025
Fluoride
901 µg/L 23%
of the EPA limit 4000 µg/L
worst single sample: 1000 µg/L
7/8 SYR4 2012–2019
Dibromochloromethane
4 µg/L
No EPA limit set
4/100 SYR4 2013–2019
Hexachlorocyclopentadiene
0.1755 µg/L 0.4%
of the EPA limit 50 µg/L
worst single sample: 0.1800 µg/L
4/20 SYR4 2012–2019
Xylenes, Total
0.5000 µg/L 0%
of the EPA limit 10000 µg/L
1/13 SYR4 2012–2019
91 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAtrazineBhc-GammaBariumBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined Radium (-226 And -228)Combined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromoacetic AcidDinosebEthylene DibromideEndrinEthylbenzeneHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideLassoMercuryMethoxychlorMonobromoacetic AcidNetfosaaNfdhaNmefosaaNitrateOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
MCKEW, DAVID
Phone
910-281-4719
Email
[email protected]

Frequently asked questions about Southern Pines, Town of

Is Southern Pines, Town of tap water safe to drink?

EPA monitoring detected 14 contaminants in Southern Pines, Town of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Southern Pines, Town of's water?

EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Chloroform, Dichloroacetic Acid, Trichloroacetic Acid, and others. The full list with the level and data source for each is above.

How many people does Southern Pines, Town of serve?

Southern Pines, Town of reports serving 24,102 people in North Carolina, per its EPA record.

Has Southern Pines, Town of had any water quality violations?

The EPA has 126 violations on file for Southern Pines, Town of, of which 41 are health-based (a contaminant limit or required treatment was breached) and 6 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.