← North Carolina

Tap water quality report

South Granville Wtr&Sewer Authority

EPA monitoring tested this supplier for 108 contaminants and detected 16. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

108
contaminants tested
16
detected
18,555
people served
126
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Granville

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

126
health-based violations
162
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2017-07-01 → 2017-09-30
MCL Health-based Resolved 2017-07-01 → 2017-09-30
MCL Health-based Resolved 2017-07-01 → 2017-09-30
MCL Health-based Resolved 2017-07-01 → 2017-09-30
MCL Health-based Resolved 2017-07-01 → 2017-09-30
MCL Health-based Resolved 2017-07-01 → 2017-09-30
MCL Health-based Resolved 2017-07-01 → 2017-09-30
MCL Health-based Resolved 2017-07-01 → 2017-09-30
MCL Health-based Resolved 2017-07-01 → 2017-09-30
MCL Health-based Resolved 2017-07-01 → 2017-09-30

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
PFOA 0.0110 µg/L 3/4 2024
PFOS 0.0190 µg/L 3/4 2024

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
404.5 µg/L 31%
of the EPA limit 1300 µg/L
worst single sample: 994 µg/L
156/332 SYR4 2014–2019
TTHM
102.6 µg/L 128%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 117 µg/L
145/145 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
83.49 µg/L 139%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 111 µg/L
138/146 SYR4 2012–2019
Bromodichloromethane
7 µg/L
No EPA limit set
worst single sample: 12 µg/L
118/118 SYR4 2013–2019
Chloroform
97.75 µg/L
No EPA limit set
worst single sample: 112 µg/L
118/118 SYR4 2013–2019
Trichloroacetic Acid
41.65 µg/L
No EPA limit set
worst single sample: 55 µg/L
110/118 SYR4 2013–2019
Dichloroacetic Acid
41.65 µg/L
No EPA limit set
worst single sample: 50 µg/L
108/118 SYR4 2013–2019
Monobromoacetic Acid
32.1 µg/L
No EPA limit set
worst single sample: 38 µg/L
27/118 SYR4 2013–2019
Lead
23 µg/L 153%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 141 µg/L
24/332 SYR4 2014–2019
Monochloroacetic Acid
9.2 µg/L
No EPA limit set
worst single sample: 11 µg/L
19/118 SYR4 2013–2019
Lead
0.0030 mg/L 20%
of the EPA limit 0.0150 mg/L
18/18 LCR 2025
Fluoride
668.5 µg/L 17%
of the EPA limit 4000 µg/L
worst single sample: 680 µg/L
6/8 SYR4 2012–2019
Dibromoacetic Acid
3.8 µg/L
No EPA limit set
worst single sample: 4 µg/L
5/118 SYR4 2013–2019
Combined Radium (-226 And -228)
1 pCi/L 20%
of the EPA limit 5 pCi/L
2/2 SYR4 2016–2017
92 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAtrazineBhc-GammaBariumBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromochloromethaneDinosebEthylene DibromideEndrinEthylbenzeneGross Alpha, Excl. Radon And UHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaNitrateNitrate-NitriteNitriteOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
SCHROYER, SCOTT
Phone
919-575-3367
Email
[email protected]

Frequently asked questions about South Granville Wtr&Sewer Authority

Is South Granville Wtr&Sewer Authority tap water safe to drink?

EPA monitoring detected 16 contaminants in South Granville Wtr&Sewer Authority's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in South Granville Wtr&Sewer Authority's water?

EPA monitoring detected Copper, TTHM, Total Haloacetic Acids (HAA5), Bromodichloromethane, Chloroform, and others. The full list with the level and data source for each is above.

How many people does South Granville Wtr&Sewer Authority serve?

South Granville Wtr&Sewer Authority reports serving 18,555 people in North Carolina, per its EPA record.

Has South Granville Wtr&Sewer Authority had any water quality violations?

The EPA has 162 violations on file for South Granville Wtr&Sewer Authority, of which 126 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.