Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2014-01-01 → 2014-01-31 |
| MCL | Health-based | Resolved | 2014-01-01 → 2014-01-31 |
| MCL | Health-based | Resolved | 2014-01-01 → 2014-01-31 |
| MCL | Health-based | Resolved | 2014-01-01 → 2014-01-31 |
| MCL | Health-based | Resolved | 2014-01-01 → 2014-01-31 |
| MCL | Health-based | Resolved | 2012-10-01 → 2012-10-31 |
| MCL | Health-based | Resolved | 2012-10-01 → 2012-10-31 |
| MCL | Health-based | Resolved | 2012-10-01 → 2012-10-31 |
| MCL | Health-based | Resolved | 2012-10-01 → 2012-10-31 |
| MCL | Health-based | Resolved | 2012-09-01 → 2012-09-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate-Nitrite | 1940 µg/L 19% of the EPA limit 10000 µg/L
worst single sample: 2040 µg/L | 46/48 | SYR4 | 2012–2019 |
| Copper | 855 µg/L 66% of the EPA limit 1300 µg/L
worst single sample: 890 µg/L | 15/15 | SYR4 | 2013–2019 |
| Lead | 0.0020 mg/L 13% of the EPA limit 0.0150 mg/L | 12/12 | LCR | 2025 |
| Arsenic | 2 µg/L 20% of the EPA limit 10 µg/L | 9/9 | SYR4 | 2012–2018 |
| Combined Uranium | 4.75 µg/L 16% of the EPA limit 30 µg/L
worst single sample: 5 µg/L | 6/6 | SYR4 | 2012–2016 |
| Lead | 2 µg/L 13% of the EPA limit 15 µg/L | 6/15 | SYR4 | 2013–2019 |
| Barium | 116 µg/L 5.8% of the EPA limit 2000 µg/L
worst single sample: 120 µg/L | 3/3 | SYR4 | 2012 |
| Combined Radium (-226 And -228) | 1.49 pCi/L 30% of the EPA limit 5 pCi/L
worst single sample: 1.5 pCi/L | 3/3 | SYR4 | 2012 |
| Fluoride | 1500 µg/L 38% of the EPA limit 4000 µg/L
worst single sample: 1600 µg/L | 3/3 | SYR4 | 2012 |
| Di(2-ethylhexyl) Phthalate | 4.345 µg/L 72% of the EPA limit 6 µg/L
worst single sample: 4.4 µg/L | 2/15 | SYR4 | 2012–2018 |
| Gross Alpha, Excl. Radon And U | 3.355 pCi/L 22% of the EPA limit 15 pCi/L
worst single sample: 3.4 pCi/L | 2/6 | SYR4 | 2012–2016 |
| Dibromoacetic Acid | 0.3000 µg/L No EPA limit set | 1/2 | SYR4 | 2018–2019 |
| TTHM | 1.3 µg/L 1.6% of the EPA limit 80 µg/L | 1/11 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 0.3000 µg/L 0.5% of the EPA limit 60 µg/L | 1/2 | SYR4 | 2018–2019 |
58 contaminants tested, none detected
Utility contact
Frequently asked questions about Emkayan Village Co Water and Sewer Dist
Is Emkayan Village Co Water and Sewer Dist tap water safe to drink?
EPA monitoring detected 14 contaminants in Emkayan Village Co Water and Sewer Dist's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Emkayan Village Co Water and Sewer Dist's water?
EPA monitoring detected Nitrate-Nitrite, Copper, Lead, Arsenic, Combined Uranium, and others. The full list with the level and data source for each is above.
How many people does Emkayan Village Co Water and Sewer Dist serve?
Emkayan Village Co Water and Sewer Dist reports serving 160 people in Montana, per its EPA record.
Has Emkayan Village Co Water and Sewer Dist had any water quality violations?
The EPA has 73 violations on file for Emkayan Village Co Water and Sewer Dist, of which 58 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.