Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2025-12-01 → 2025-12-31 |
| TT | Health-based | Resolved | 2025-12-01 → 2025-12-31 |
| TT | Health-based | Resolved | 2025-12-01 → 2025-12-31 |
| TT | Health-based | Resolved | 2022-03-01 → 2022-03-31 |
| TT | Health-based | Resolved | 2022-03-01 → 2022-03-31 |
| TT | Health-based | Resolved | 2022-03-01 → 2022-03-31 |
| TT | Health-based | Resolved | 2022-03-01 → 2022-03-31 |
| TT | Health-based | Resolved | 2022-03-01 → 2022-03-31 |
| TT | Health-based | Resolved | 2022-03-01 → 2022-03-31 |
| TT | Health-based | Resolved | 2021-10-01 → 2021-10-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 320 µg/L 25% of the EPA limit 1300 µg/L
worst single sample: 1020 µg/L | 56/60 | SYR4 | 2013–2019 |
| Chloroform | 22.65 µg/L No EPA limit set
worst single sample: 46 µg/L | 28/28 | SYR4 | 2012–2019 |
| TTHM | 23.65 µg/L 30% of the EPA limit 80 µg/L
worst single sample: 47 µg/L | 28/28 | SYR4 | 2012–2019 |
| Bromodichloromethane | 1.17 µg/L No EPA limit set
worst single sample: 1.3 µg/L | 24/28 | SYR4 | 2012–2019 |
| Lead | 6.55 µg/L 44% of the EPA limit 15 µg/L
worst single sample: 857 µg/L | 24/60 | SYR4 | 2013–2019 |
| Lead | 0.0020 mg/L 13% of the EPA limit 0.0150 mg/L | 21/21 | LCR | 2025 |
| Dichloroacetic Acid | 10.05 µg/L No EPA limit set
worst single sample: 11 µg/L | 20/20 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 27.1 µg/L 45% of the EPA limit 60 µg/L
worst single sample: 29 µg/L | 20/20 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 17 µg/L No EPA limit set | 20/20 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 46.5 µg/L 0.5% of the EPA limit 10000 µg/L
worst single sample: 50 µg/L | 8/9 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 1.55 µg/L No EPA limit set
worst single sample: 1.6 µg/L | 6/20 | SYR4 | 2012–2019 |
| Nitrate | 30 µg/L 0.3% of the EPA limit 10000 µg/L | 2/2 | SYR4 | 2013 |
| Fluoride | 20 µg/L 0.5% of the EPA limit 4000 µg/L | 1/1 | SYR4 | 2013 |
| Gross Alpha, Excl. Radon And U | 2.1 pCi/L 14% of the EPA limit 15 pCi/L | 1/1 | SYR4 | 2013 |
91 contaminants tested, none detected
Utility contact
Frequently asked questions about Libby City of
Is Libby City of tap water safe to drink?
EPA monitoring detected 14 contaminants in Libby City of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Libby City of's water?
EPA monitoring detected Copper, Chloroform, TTHM, Bromodichloromethane, Lead, and others. The full list with the level and data source for each is above.
How many people does Libby City of serve?
Libby City of reports serving 4,892 people in Montana, per its EPA record.
Has Libby City of had any water quality violations?
The EPA has 331 violations on file for Libby City of, of which 103 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.