← Montana

Tap water quality report

Bridger Town of

EPA monitoring tested this supplier for 73 contaminants and detected 17. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

73
contaminants tested
17
detected
750
people served
0
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Carbon

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
105
violations on file
0
still open
ViolationTypeStatusPeriod
Other Monitoring Resolved 2023-07-01
Other Monitoring Resolved 2023-07-01
MON Monitoring Resolved 2021-09-01 → 2021-09-30
MON Monitoring Resolved 2021-09-01 → 2021-09-30
MON Monitoring Resolved 2021-09-01 → 2021-09-30
MR Monitoring Resolved 2020-12-30
MR Monitoring Resolved 2020-12-30
MON Monitoring Resolved 2019-08-01 → 2019-08-31
MON Monitoring Resolved 2019-08-01 → 2019-08-31
MON Monitoring Resolved 2019-08-01 → 2019-08-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate-Nitrite
1523.5 µg/L 15%
of the EPA limit 10000 µg/L
worst single sample: 1540 µg/L
32/32 SYR4 2012–2019
Copper
261.95 µg/L 20%
of the EPA limit 1300 µg/L
worst single sample: 284 µg/L
30/30 SYR4 2013–2019
Lead
6.85 µg/L 46%
of the EPA limit 15 µg/L
worst single sample: 7 µg/L
24/30 SYR4 2013–2019
TTHM
14.45 µg/L 18%
of the EPA limit 80 µg/L
worst single sample: 15 µg/L
12/13 SYR4 2012–2019
Chloroform
11 µg/L
No EPA limit set
11/13 SYR4 2012–2019
Lead
0.0040 mg/L 27%
of the EPA limit 0.0150 mg/L
10/10 LCR 2016
Bromodichloromethane
4.22 µg/L
No EPA limit set
worst single sample: 4.5 µg/L
9/13 SYR4 2012–2019
Dibromochloromethane
2.24 µg/L
No EPA limit set
worst single sample: 2.4 µg/L
9/13 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
5.34 µg/L 8.9%
of the EPA limit 60 µg/L
worst single sample: 5.4 µg/L
7/7 SYR4 2012–2019
Dibromoacetic Acid
0.7350 µg/L
No EPA limit set
worst single sample: 0.7600 µg/L
6/7 SYR4 2012–2019
Dichloroacetic Acid
3.78 µg/L
No EPA limit set
worst single sample: 3.9 µg/L
5/7 SYR4 2012–2019
Barium
79.5 µg/L 4%
of the EPA limit 2000 µg/L
worst single sample: 80 µg/L
2/2 SYR4 2012
Combined Uranium
6 µg/L 20%
of the EPA limit 30 µg/L
2/2 SYR4 2013
Fluoride
400 µg/L 10%
of the EPA limit 4000 µg/L
2/2 SYR4 2012
Gross Alpha, Excl. Radon And U
3.58 pCi/L 24%
of the EPA limit 15 pCi/L
worst single sample: 3.6 pCi/L
2/2 SYR4 2013
Selenium
3 µg/L 6%
of the EPA limit 50 µg/L
2/2 SYR4 2012
Trichloroacetic Acid
1.295 µg/L
No EPA limit set
worst single sample: 1.3 µg/L
2/7 SYR4 2012–2019
56 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined Radium (-226 And -228)DichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEndrinEthylbenzeneHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidOxamylPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
SWEET, KIRSTIN
Phone
406-662-3677

Frequently asked questions about Bridger Town of

Is Bridger Town of tap water safe to drink?

EPA monitoring detected 17 contaminants in Bridger Town of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Bridger Town of's water?

EPA monitoring detected Nitrate-Nitrite, Copper, Lead, TTHM, Chloroform, and others. The full list with the level and data source for each is above.

How many people does Bridger Town of serve?

Bridger Town of reports serving 750 people in Montana, per its EPA record.

Has Bridger Town of had any water quality violations?

The EPA has 105 violations on file for Bridger Town of, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.