Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2022-03-12 |
| TT | Health-based | Resolved | 2022-03-12 |
| TT | Health-based | Resolved | 2022-03-12 |
| MCL | Health-based | Resolved | 1996-12-01 → 1996-12-31 |
| MON | Monitoring | Resolved | 2022-02-01 → 2022-02-28 |
| MON | Monitoring | Resolved | 2022-02-01 → 2022-02-28 |
| MON | Monitoring | Resolved | 2022-02-01 → 2022-02-28 |
| MON | Monitoring | Resolved | 2022-02-01 → 2022-02-28 |
| MR | Monitoring | Resolved | 2021-09-29 |
| MR | Monitoring | Resolved | 2021-09-29 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate-Nitrite | 2617 µg/L 26% of the EPA limit 10000 µg/L
worst single sample: 3400 µg/L | 19/19 | SYR4 | 2012–2019 |
| Lead | 0.0040 mg/L 27% of the EPA limit 0.0150 mg/L | 12/12 | LCR | 2024 |
| Copper | 326 µg/L 25% of the EPA limit 1300 µg/L
worst single sample: 390 µg/L | 9/10 | SYR4 | 2014–2017 |
| Chloroform | 9.73 µg/L No EPA limit set
worst single sample: 14 µg/L | 8/9 | SYR4 | 2012–2018 |
| Nitrate | 3400 µg/L 34% of the EPA limit 10000 µg/L | 8/8 | SYR4 | 2016–2017 |
| TTHM | 14.325 µg/L 18% of the EPA limit 80 µg/L
worst single sample: 18 µg/L | 8/9 | SYR4 | 2012–2018 |
| Bromodichloromethane | 3.425 µg/L No EPA limit set
worst single sample: 3.7 µg/L | 6/9 | SYR4 | 2012–2018 |
| Fluoride | 105 µg/L 2.6% of the EPA limit 4000 µg/L
worst single sample: 110 µg/L | 6/6 | SYR4 | 2012–2017 |
| Dibromochloromethane | 2.52 µg/L No EPA limit set
worst single sample: 2.7 µg/L | 5/9 | SYR4 | 2012–2018 |
| Lead | 3 µg/L 20% of the EPA limit 15 µg/L | 5/10 | SYR4 | 2014–2017 |
| Barium | 1007 µg/L 50% of the EPA limit 2000 µg/L
worst single sample: 1070 µg/L | 4/6 | SYR4 | 2012–2017 |
| Arsenic | 3 µg/L 30% of the EPA limit 10 µg/L | 3/6 | SYR4 | 2012–2017 |
| Combined Uranium | 7.8 µg/L 26% of the EPA limit 30 µg/L
worst single sample: 8 µg/L | 3/3 | SYR4 | 2016–2017 |
| Gross Alpha, Excl. Radon And U | 8.68 pCi/L 58% of the EPA limit 15 pCi/L
worst single sample: 9.3 pCi/L | 3/3 | SYR4 | 2016–2017 |
| Bromoform | 1.07 µg/L No EPA limit set
worst single sample: 1.1 µg/L | 2/9 | SYR4 | 2012–2018 |
| Dibromoacetic Acid | 0.6675 µg/L No EPA limit set
worst single sample: 0.6700 µg/L | 2/3 | SYR4 | 2012–2018 |
| Total Haloacetic Acids (HAA5) | 0.6675 µg/L 1.1% of the EPA limit 60 µg/L
worst single sample: 0.6700 µg/L | 2/3 | SYR4 | 2012–2018 |
| Combined Radium (-226 And -228) | 1.4 pCi/L 28% of the EPA limit 5 pCi/L | 1/2 | SYR4 | 2016–2017 |
| Di(2-ethylhexyl) Phthalate | 2.1 µg/L 35% of the EPA limit 6 µg/L | 1/8 | SYR4 | 2013–2017 |
| Selenium | 2 µg/L 4% of the EPA limit 50 µg/L | 1/6 | SYR4 | 2012–2017 |
55 contaminants tested, none detected
Utility contact
Frequently asked questions about Alberton Town of
Is Alberton Town of tap water safe to drink?
EPA monitoring detected 20 contaminants in Alberton Town of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Alberton Town of's water?
EPA monitoring detected Nitrate-Nitrite, Lead, Copper, Chloroform, Nitrate, and others. The full list with the level and data source for each is above.
How many people does Alberton Town of serve?
Alberton Town of reports serving 495 people in Montana, per its EPA record.
Has Alberton Town of had any water quality violations?
The EPA has 32 violations on file for Alberton Town of, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.