Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| Other | Monitoring | Resolved | 2006-07-01 |
| MR | Monitoring | Archived | 1994-09-01 → 1994-09-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 9.6075 µg/L No EPA limit set
worst single sample: 12.7 µg/L | 86/86 | SYR4 | 2012–2019 |
| Chloroform | 89.525 µg/L No EPA limit set
worst single sample: 111 µg/L | 86/86 | SYR4 | 2012–2019 |
| TTHM | 93.875 µg/L 117% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 114 µg/L | 86/86 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 41.8 µg/L No EPA limit set
worst single sample: 56.7 µg/L | 85/86 | SYR4 | 2012–2019 |
| Copper | 8.7305 µg/L 0.7% of the EPA limit 1300 µg/L
worst single sample: 36.8 µg/L | 84/90 | SYR4 | 2013–2019 |
| Trichloroacetic Acid | 5.04 µg/L No EPA limit set
worst single sample: 8.66 µg/L | 81/86 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 47.68 µg/L 79% of the EPA limit 60 µg/L
worst single sample: 68.6 µg/L | 79/86 | SYR4 | 2012–2019 |
| Dibromochloromethane | 2.815 µg/L No EPA limit set
worst single sample: 4.2 µg/L | 66/86 | SYR4 | 2012–2019 |
| Lead | 11.5195 µg/L 77% of the EPA limit 15 µg/L
worst single sample: 27.2 µg/L | 22/90 | SYR4 | 2013–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 21/21 | LCR | 2025 |
| Dibromoacetic Acid | 2.648 µg/L No EPA limit set
worst single sample: 3.24 µg/L | 9/86 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 11.3 µg/L No EPA limit set
worst single sample: 11.6 µg/L | 3/86 | SYR4 | 2012–2019 |
32 contaminants tested, none detected
Utility contact
Frequently asked questions about Jefferson County Pwsd 3
Is Jefferson County Pwsd 3 tap water safe to drink?
EPA monitoring detected 12 contaminants in Jefferson County Pwsd 3's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Jefferson County Pwsd 3's water?
EPA monitoring detected Bromodichloromethane, Chloroform, TTHM, Dichloroacetic Acid, Copper, and others. The full list with the level and data source for each is above.
How many people does Jefferson County Pwsd 3 serve?
Jefferson County Pwsd 3 reports serving 17,000 people in Missouri, per its EPA record.
Has Jefferson County Pwsd 3 had any water quality violations?
The EPA has 2 violations on file for Jefferson County Pwsd 3, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.