← Missouri

Tap water quality report

Butler County Pwsd 1

EPA monitoring tested this supplier for 101 contaminants and detected 13. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

101
contaminants tested
13
detected
12,000
people served
8
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Butler

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

8
health-based violations
11
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2010-10-01 → 2010-10-31
MCL Health-based Resolved 2010-10-01 → 2010-10-31
MCL Health-based Resolved 2010-10-01 → 2010-10-31
MCL Health-based Resolved 2010-10-01 → 2010-10-31
MCL Health-based Resolved 2008-08-01 → 2008-08-31
MCL Health-based Resolved 2008-08-01 → 2008-08-31
MCL Health-based Resolved 2008-08-01 → 2008-08-31
MCL Health-based Resolved 2008-08-01 → 2008-08-31
MR Monitoring Resolved 2008-04-01
MR Monitoring Resolved 2008-04-01

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
114.3 µg/L 8.8%
of the EPA limit 1300 µg/L
worst single sample: 217 µg/L
80/82 SYR4 2012–2018
Nitrate-Nitrite
740 µg/L 7.4%
of the EPA limit 10000 µg/L
worst single sample: 750 µg/L
60/60 SYR4 2012–2019
Lead
15.35 µg/L 102%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 38.8 µg/L
26/82 SYR4 2012–2018
Lead
0.0014 mg/L 9.5%
of the EPA limit 0.0150 mg/L
17/17 LCR 2024
Barium
46.61 µg/L 2.3%
of the EPA limit 2000 µg/L
worst single sample: 56.4 µg/L
12/12 SYR4 2012–2018
Chromium
4.123 µg/L 4.1%
of the EPA limit 100 µg/L
worst single sample: 4.45 µg/L
7/12 SYR4 2012–2018
Combined Uranium
1.74032 µg/L 5.8%
of the EPA limit 30 µg/L
worst single sample: 1.788 µg/L
5/5 SYR4 2015–2016
Fluoride
129.5 µg/L 3.2%
of the EPA limit 4000 µg/L
worst single sample: 130 µg/L
2/12 SYR4 2012–2018
Gross Alpha, Excl. Radon And U
4.73 pCi/L 32%
of the EPA limit 15 pCi/L
worst single sample: 4.8 pCi/L
2/5 SYR4 2015–2016
Xylenes, Total
2.65 µg/L 0%
of the EPA limit 10000 µg/L
worst single sample: 2.76 µg/L
2/12 SYR4 2012–2018
Bromodichloromethane
0.5200 µg/L
No EPA limit set
1/19 SYR4 2012–2019
Chloroform
0.5700 µg/L
No EPA limit set
1/19 SYR4 2012–2019
Dibromochloromethane
0.6000 µg/L
No EPA limit set
1/19 SYR4 2012–2019
88 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAtrazineBhc-GammaBenzeneBeryllium, TotalBromoformChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneCombined Radium (-226 And -228)DichloromethaneDalaponDibromoacetic AcidDichloroacetic AcidDinosebEthylene DibromideEndrinEthylbenzeneHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNetfosaaNfdhaNmefosaaOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTTHMTetrachloroethyleneThallium, TotalTolueneTotal Haloacetic Acids (HAA5)ToxapheneTrichloroacetic AcidTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
NEYMAN, WILLIE
Phone
573-778-2249

Frequently asked questions about Butler County Pwsd 1

Is Butler County Pwsd 1 tap water safe to drink?

EPA monitoring detected 13 contaminants in Butler County Pwsd 1's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Butler County Pwsd 1's water?

EPA monitoring detected Copper, Nitrate-Nitrite, Lead, Lead, Barium, and others. The full list with the level and data source for each is above.

How many people does Butler County Pwsd 1 serve?

Butler County Pwsd 1 reports serving 12,000 people in Missouri, per its EPA record.

Has Butler County Pwsd 1 had any water quality violations?

The EPA has 11 violations on file for Butler County Pwsd 1, of which 8 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.