← Missouri

Tap water quality report

5 81 Motel & Campground

EPA monitoring tested this supplier for 62 contaminants and detected 7. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

62
contaminants tested
7
detected
36
people served
4
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Camden

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

4
health-based violations
84
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2009-11-01 → 2009-11-30
MCL Health-based Resolved 2009-11-01 → 2009-11-30
MCL Health-based Resolved 2009-11-01 → 2009-11-30
MCL Health-based Resolved 2009-11-01 → 2009-11-30
RPT Monitoring Resolved 2024-10-17
RPT Monitoring Resolved 2024-10-17
RPT Monitoring Resolved 2024-10-17
MR Monitoring Archived 2023-01-01 → 2025-12-31
MR Monitoring Archived 2023-01-01 → 2025-12-31
MR Monitoring Archived 2023-01-01 → 2025-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate-Nitrite
1020 µg/L 10%
of the EPA limit 10000 µg/L
24/24 SYR4 2012–2019
Copper
125.5 µg/L 9.7%
of the EPA limit 1300 µg/L
worst single sample: 238 µg/L
19/19 SYR4 2013–2019
Lead
0.0075 mg/L 50%
of the EPA limit 0.0150 mg/L
10/10 LCR 2025
Lead
8.319 µg/L 55%
of the EPA limit 15 µg/L
worst single sample: 9.03 µg/L
10/19 SYR4 2013–2019
Barium
69.3 µg/L 3.5%
of the EPA limit 2000 µg/L
worst single sample: 71.4 µg/L
4/4 SYR4 2014–2017
Chromium
1.472 µg/L 1.5%
of the EPA limit 100 µg/L
worst single sample: 1.48 µg/L
2/4 SYR4 2014–2017
Cadmium
0.3900 µg/L 7.8%
of the EPA limit 5 µg/L
1/4 SYR4 2014–2017
55 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicAtrazineBhc-GammaBenzeneBeryllium, TotalBromodichloromethaneBromoformChlorobenzeneCyanideCarbofuranCarbon TetrachlorideChlordaneChloroformDichloromethaneDalaponDibromochloromethaneDinosebEthylene DibromideEndrinEthylbenzeneFluorideHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
HOUSE, CLARENCE
Phone
573-873-5137

Frequently asked questions about 5 81 Motel & Campground

Is 5 81 Motel & Campground tap water safe to drink?

EPA monitoring detected 7 contaminants in 5 81 Motel & Campground's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in 5 81 Motel & Campground's water?

EPA monitoring detected Nitrate-Nitrite, Copper, Lead, Lead, Barium, and others. The full list with the level and data source for each is above.

How many people does 5 81 Motel & Campground serve?

5 81 Motel & Campground reports serving 36 people in Missouri, per its EPA record.

Has 5 81 Motel & Campground had any water quality violations?

The EPA has 84 violations on file for 5 81 Motel & Campground, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.