Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2008-08-01 → 2008-08-31 |
| MCL | Health-based | Resolved | 2008-08-01 → 2008-08-31 |
| MCL | Health-based | Resolved | 2008-08-01 → 2008-08-31 |
| MCL | Health-based | Resolved | 2005-10-01 → 2005-10-31 |
| MCL | Health-based | Resolved | 2005-10-01 → 2005-10-31 |
| MCL | Health-based | Resolved | 2005-10-01 → 2005-10-31 |
| MCL | Health-based | Resolved | 2005-10-01 → 2005-10-31 |
| MCL | Health-based | Resolved | 2005-06-01 → 2005-06-30 |
| MCL | Health-based | Resolved | 2005-06-01 → 2005-06-30 |
| MCL | Health-based | Resolved | 2005-06-01 → 2005-06-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 200.1 µg/L 15% of the EPA limit 1300 µg/L
worst single sample: 292 µg/L | 107/111 | SYR4 | 2012–2018 |
| Lead | 10.192 µg/L 68% of the EPA limit 15 µg/L
worst single sample: 59.2 µg/L | 69/111 | SYR4 | 2012–2018 |
| Lead | 0.0086 mg/L 57% of the EPA limit 0.0150 mg/L | 27/27 | LCR | 2024 |
| Barium | 186.9 µg/L 9.3% of the EPA limit 2000 µg/L
worst single sample: 204 µg/L | 20/20 | SYR4 | 2012–2018 |
| Fluoride | 871.5 µg/L 22% of the EPA limit 4000 µg/L
worst single sample: 900 µg/L | 20/20 | SYR4 | 2012–2018 |
| Combined Radium (-226 And -228) | 2.61 pCi/L 52% of the EPA limit 5 pCi/L
worst single sample: 3.1 pCi/L | 15/16 | SYR4 | 2013–2019 |
| Nitrate-Nitrite | 15 µg/L 0.2% of the EPA limit 10000 µg/L | 12/106 | SYR4 | 2012–2019 |
| Bromodichloromethane | 1.364 µg/L No EPA limit set
worst single sample: 1.44 µg/L | 9/32 | SYR4 | 2012–2019 |
| Chloroform | 1.206 µg/L No EPA limit set
worst single sample: 1.29 µg/L | 9/32 | SYR4 | 2012–2019 |
| Chromium | 2.62 µg/L 2.6% of the EPA limit 100 µg/L
worst single sample: 2.71 µg/L | 7/34 | SYR4 | 2012–2018 |
| Dibromochloromethane | 1.3225 µg/L No EPA limit set
worst single sample: 1.36 µg/L | 6/32 | SYR4 | 2012–2019 |
| TTHM | 4.42 µg/L 5.5% of the EPA limit 80 µg/L
worst single sample: 4.66 µg/L | 5/14 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 7.925 pCi/L 53% of the EPA limit 15 pCi/L
worst single sample: 8 pCi/L | 4/4 | SYR4 | 2014–2015 |
| Dichloroacetic Acid | 1.63 µg/L No EPA limit set
worst single sample: 1.66 µg/L | 2/14 | SYR4 | 2012–2019 |
| Bromoform | 0.5700 µg/L No EPA limit set | 1/32 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 1.66 µg/L 2.8% of the EPA limit 60 µg/L | 1/14 | SYR4 | 2012–2019 |
| Xylenes, Total | 3.12 µg/L 0% of the EPA limit 10000 µg/L | 1/19 | SYR4 | 2014–2018 |
84 contaminants tested, none detected
Utility contact
Frequently asked questions about Cole County Pwsd 2
Is Cole County Pwsd 2 tap water safe to drink?
EPA monitoring detected 17 contaminants in Cole County Pwsd 2's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Cole County Pwsd 2's water?
EPA monitoring detected Copper, Lead, Lead, Barium, Fluoride, and others. The full list with the level and data source for each is above.
How many people does Cole County Pwsd 2 serve?
Cole County Pwsd 2 reports serving 13,107 people in Missouri, per its EPA record.
Has Cole County Pwsd 2 had any water quality violations?
The EPA has 21 violations on file for Cole County Pwsd 2, of which 17 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.