Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2018-05-01 → 2018-05-31 |
| TT | Health-based | Resolved | 2018-05-01 → 2018-05-31 |
| TT | Health-based | Resolved | 2018-05-01 → 2018-05-31 |
| TT | Health-based | Resolved | 2018-05-01 → 2018-05-31 |
| TT | Health-based | Resolved | 2018-05-01 → 2018-05-31 |
| TT | Health-based | Resolved | 2017-11-01 → 2017-11-30 |
| TT | Health-based | Resolved | 2017-11-01 → 2017-11-30 |
| TT | Health-based | Resolved | 2017-11-01 → 2017-11-30 |
| TT | Health-based | Resolved | 2017-11-01 → 2017-11-30 |
| TT | Health-based | Resolved | 2017-11-01 → 2017-11-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Chlorite | 830 µg/L 83% of the EPA limit 1000 µg/L
worst single sample: 1510 µg/L | 277/289 | SYR4 | 2012–2019 |
| Bromodichloromethane | 17.4 µg/L No EPA limit set
worst single sample: 17.8 µg/L | 61/61 | SYR4 | 2012–2019 |
| Chloroform | 109 µg/L No EPA limit set
worst single sample: 116 µg/L | 61/61 | SYR4 | 2012–2019 |
| TTHM | 130.8 µg/L 164% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 137 µg/L | 53/53 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 41.275 µg/L No EPA limit set
worst single sample: 68.8 µg/L | 52/53 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 33.545 µg/L No EPA limit set
worst single sample: 41.7 µg/L | 52/53 | SYR4 | 2012–2019 |
| Dibromochloromethane | 3.485 µg/L No EPA limit set
worst single sample: 3.89 µg/L | 51/61 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 75.215 µg/L 125% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 107.56 µg/L | 50/53 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 2.246 µg/L No EPA limit set
worst single sample: 2.3 µg/L | 19/53 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 600 µg/L 6% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2012–2019 |
| Atrazine | 3.082 µg/L 103% of the EPA limit, at the 95th percentile of samples — 3 µg/L
worst single sample: 3.94 µg/L | 12/32 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 14.4 µg/L No EPA limit set
worst single sample: 15.2 µg/L | 11/53 | SYR4 | 2012–2019 |
| Barium | 82.1 µg/L 4.1% of the EPA limit 2000 µg/L
worst single sample: 82.8 µg/L | 8/8 | SYR4 | 2012–2019 |
| Copper | 4.398 µg/L 0.3% of the EPA limit 1300 µg/L
worst single sample: 4.72 µg/L | 8/8 | SYR4 | 2012–2019 |
| Fluoride | 150 µg/L 3.8% of the EPA limit 4000 µg/L | 7/8 | SYR4 | 2012–2019 |
| Arsenic | 1.4685 µg/L 15% of the EPA limit 10 µg/L
worst single sample: 1.49 µg/L | 2/8 | SYR4 | 2012–2019 |
| Chromium | 1.8415 µg/L 1.8% of the EPA limit 100 µg/L
worst single sample: 1.86 µg/L | 2/8 | SYR4 | 2012–2019 |
| Lasso | 0.7500 µg/L 38% of the EPA limit 2 µg/L | 1/32 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 9.57 µg/L No EPA limit set | 1/53 | SYR4 | 2012–2019 |
49 contaminants tested, none detected
Utility contact
Frequently asked questions about Nodaway Co East Pwsd 1
Is Nodaway Co East Pwsd 1 tap water safe to drink?
EPA monitoring detected 19 contaminants in Nodaway Co East Pwsd 1's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Nodaway Co East Pwsd 1's water?
EPA monitoring detected Chlorite, Bromodichloromethane, Chloroform, TTHM, Dichloroacetic Acid, and others. The full list with the level and data source for each is above.
How many people does Nodaway Co East Pwsd 1 serve?
Nodaway Co East Pwsd 1 reports serving 25 people in Missouri, per its EPA record.
Has Nodaway Co East Pwsd 1 had any water quality violations?
The EPA has 388 violations on file for Nodaway Co East Pwsd 1, of which 199 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.