← Minnesota

Tap water quality report

Renville

EPA monitoring tested this supplier for 71 contaminants and detected 13. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

71
contaminants tested
13
detected
1,301
people served
0
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Renville

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
6
violations on file
0
still open
ViolationTypeStatusPeriod
MR Monitoring Archived 1997-07-01 → 1997-07-31
MR Monitoring Archived 1997-07-01 → 1997-07-31
MR Monitoring Archived 1997-07-01 → 1997-07-31
MR Monitoring Archived 1997-06-01 → 1997-06-30
MR Monitoring Archived 1997-06-01 → 1997-06-30
MR Monitoring Archived 1997-06-01 → 1997-06-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
1692 µg/L 130%
of the EPA limit, at the 95th percentile of samples — 1300 µg/L
worst single sample: 2150 µg/L
60/60 SYR4 2012–2017
Fluoride
970 µg/L 24%
of the EPA limit 4000 µg/L
worst single sample: 1000 µg/L
33/33 SYR4 2012–2019
Lead
4.76 µg/L 32%
of the EPA limit 15 µg/L
worst single sample: 9.1 µg/L
33/60 SYR4 2012–2017
Lead
0.0050 mg/L 33%
of the EPA limit 0.0150 mg/L
16/16 LCR 2026
Nitrate-Nitrite
610 µg/L 6.1%
of the EPA limit 10000 µg/L
16/16 SYR4 2012–2019
Bromodichloromethane
11.35 µg/L
No EPA limit set
worst single sample: 12 µg/L
14/14 SYR4 2012–2019
Chloroform
12 µg/L
No EPA limit set
14/14 SYR4 2012–2019
Dibromochloromethane
6.945 µg/L
No EPA limit set
worst single sample: 7 µg/L
12/14 SYR4 2012–2019
Dichloroacetic Acid
4.96 µg/L
No EPA limit set
worst single sample: 5.5 µg/L
10/10 SYR4 2012–2019
Trichloroacetic Acid
3.24 µg/L
No EPA limit set
worst single sample: 3.4 µg/L
9/10 SYR4 2012–2019
Dibromoacetic Acid
2.08 µg/L
No EPA limit set
worst single sample: 2.2 µg/L
5/10 SYR4 2012–2019
Bromoform
0.9900 µg/L
No EPA limit set
worst single sample: 1 µg/L
3/14 SYR4 2012–2019
Barium
41.8 µg/L 2.1%
of the EPA limit 2000 µg/L
1/1 SYR4 2014
58 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinEthylbenzeneGlyphosateGross Alpha, Excl. Radon And UHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Phone
3203298366
Email
[email protected]

Frequently asked questions about Renville

Is Renville tap water safe to drink?

EPA monitoring detected 13 contaminants in Renville's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Renville's water?

EPA monitoring detected Copper, Fluoride, Lead, Lead, Nitrate-Nitrite, and others. The full list with the level and data source for each is above.

How many people does Renville serve?

Renville reports serving 1,301 people in Minnesota, per its EPA record.

Has Renville had any water quality violations?

The EPA has 6 violations on file for Renville, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.