← Minnesota

Tap water quality report

Marshall

EPA monitoring tested this supplier for 92 contaminants and detected 13. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

92
contaminants tested
13
detected
13,890
people served
0
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Lyon

Compliance record

No violations on file. The EPA has no formal drinking-water violations recorded for this supplier.

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
PFHXS 0.0047 µg/L 2/2 2024

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
597.05 µg/L 46%
of the EPA limit 1300 µg/L
worst single sample: 891 µg/L
90/90 SYR4 2012–2018
Lead
24.935 µg/L 166%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 43.9 µg/L
48/90 SYR4 2012–2018
Chloroform
1 µg/L
No EPA limit set
worst single sample: 1.2 µg/L
32/32 SYR4 2012–2019
Fluoride
950 µg/L 24%
of the EPA limit 4000 µg/L
worst single sample: 990 µg/L
31/32 SYR4 2012–2019
Nitrate-Nitrite
1100 µg/L 11%
of the EPA limit 10000 µg/L
16/16 SYR4 2012–2019
Lead
0.0080 mg/L 53%
of the EPA limit 0.0150 mg/L
13/13 LCR 2024
Dichloroacetic Acid
1.2 µg/L
No EPA limit set
6/29 SYR4 2012–2019
Chromium
0.5710 µg/L 0.6%
of the EPA limit 100 µg/L
worst single sample: 0.5800 µg/L
4/4 SYR4 2014
Arsenic
2.0215 µg/L 20%
of the EPA limit 10 µg/L
worst single sample: 2.04 µg/L
2/2 SYR4 2018–2019
Bromodichloromethane
0.2950 µg/L
No EPA limit set
worst single sample: 0.3000 µg/L
2/31 SYR4 2012–2019
Trichloroacetic Acid
1.195 µg/L
No EPA limit set
worst single sample: 1.2 µg/L
2/29 SYR4 2012–2019
Lithium
59.1 µg/L
No EPA limit set
2/2 UCMR-5 2024
79 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAtrazineBhc-GammaBenzeneBenzo(A)PyreneBromoformChlorobenzeneCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromoacetic AcidDibromochloromethaneDinosebEthylene DibromideEndrinEthylbenzeneGlyphosateHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNetfosaaNfdhaNmefosaaOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneTolueneToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Frequently asked questions about Marshall

Is Marshall tap water safe to drink?

EPA monitoring detected 13 contaminants in Marshall's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Marshall's water?

EPA monitoring detected Copper, Lead, Chloroform, Fluoride, Nitrate-Nitrite, and others. The full list with the level and data source for each is above.

How many people does Marshall serve?

Marshall reports serving 13,890 people in Minnesota, per its EPA record.

Has Marshall had any water quality violations?

The EPA has no formal drinking-water violations on file for Marshall.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.