← Minnesota

Tap water quality report

Park Rapids

EPA monitoring tested this supplier for 102 contaminants and detected 13. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

102
contaminants tested
13
detected
4,298
people served
26
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Hubbard

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

26
health-based violations
45
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2010-05-03 → 2010-11-03
MCL Health-based Resolved 2010-05-03 → 2010-11-03
MCL Health-based Resolved 2010-05-03 → 2010-11-03
MCL Health-based Resolved 2010-05-03 → 2010-11-03
MCL Health-based Resolved 2009-05-11 → 2009-07-01
MCL Health-based Resolved 2009-05-11 → 2009-07-01
MCL Health-based Resolved 2009-05-11 → 2009-07-01
MCL Health-based Resolved 2009-05-11 → 2009-07-01
MCL Health-based Resolved 2009-05-11 → 2009-07-01
MCL Health-based Resolved 2009-05-11 → 2009-07-01

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
295.9 µg/L 23%
of the EPA limit 1300 µg/L
worst single sample: 434 µg/L
60/60 SYR4 2012–2018
Lead
14.28 µg/L 95%
of the EPA limit 15 µg/L
worst single sample: 53.4 µg/L
47/60 SYR4 2012–2018
Fluoride
1000 µg/L 25%
of the EPA limit 4000 µg/L
worst single sample: 1200 µg/L
33/33 SYR4 2012–2019
Nitrate-Nitrite
9800 µg/L 98%
of the EPA limit 10000 µg/L
18/50 SYR4 2012–2019
Chloroform
12 µg/L
No EPA limit set
15/16 SYR4 2012–2019
Lead
0.0050 mg/L 33%
of the EPA limit 0.0150 mg/L
9/9 LCR 2024
Bromodichloromethane
5.3 µg/L
No EPA limit set
worst single sample: 5.9 µg/L
7/16 SYR4 2012–2019
Dichloroacetic Acid
4.43 µg/L
No EPA limit set
worst single sample: 5.3 µg/L
7/9 SYR4 2012–2019
Barium
138.8 µg/L 6.9%
of the EPA limit 2000 µg/L
worst single sample: 139 µg/L
3/3 SYR4 2014–2017
Dibromochloromethane
2.97 µg/L
No EPA limit set
worst single sample: 3.1 µg/L
3/16 SYR4 2012–2019
Trichloroacetic Acid
5.02 µg/L
No EPA limit set
worst single sample: 5.3 µg/L
3/9 SYR4 2012–2019
Gross Alpha, Excl. Radon And U
8.7 pCi/L 58%
of the EPA limit 15 pCi/L
1/4 SYR4 2014–2015
Nitrite
30 µg/L 3%
of the EPA limit 1000 µg/L
1/1 SYR4 2014
89 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromoacetic AcidDinosebEthylene DibromideEndrinEthylbenzeneGlyphosateHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNetfosaaNfdhaNmefosaaOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Phone
2187323163
Email
[email protected]

Frequently asked questions about Park Rapids

Is Park Rapids tap water safe to drink?

EPA monitoring detected 13 contaminants in Park Rapids's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Park Rapids's water?

EPA monitoring detected Copper, Lead, Fluoride, Nitrate-Nitrite, Chloroform, and others. The full list with the level and data source for each is above.

How many people does Park Rapids serve?

Park Rapids reports serving 4,298 people in Minnesota, per its EPA record.

Has Park Rapids had any water quality violations?

The EPA has 45 violations on file for Park Rapids, of which 26 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.