Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2008-05-28 → 2008-12-04 |
| MCL | Health-based | Resolved | 2008-05-28 → 2008-12-04 |
| MCL | Health-based | Resolved | 2008-05-28 → 2008-12-04 |
| MCL | Health-based | Resolved | 2008-05-28 → 2008-12-04 |
| MCL | Health-based | Resolved | 2008-03-17 → 2008-12-04 |
| MCL | Health-based | Resolved | 2008-03-17 → 2008-12-04 |
| MCL | Health-based | Resolved | 2008-03-17 → 2008-12-04 |
| MCL | Health-based | Resolved | 2008-03-17 → 2008-12-04 |
| MCL | Health-based | Resolved | 2003-07-01 → 2003-09-30 |
| MCL | Health-based | Resolved | 2003-07-01 → 2003-09-30 |
PFAS detected
| Contaminant | Max | Detection rate | Period |
|---|---|---|---|
| Pfba | 0.0119 µg/L | 6/12 | 2023 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 520.55 µg/L 40% of the EPA limit 1300 µg/L
worst single sample: 997 µg/L | 90/90 | SYR4 | 2012–2018 |
| Chloroform | 1.3 µg/L No EPA limit set
worst single sample: 1.7 µg/L | 68/73 | SYR4 | 2012–2019 |
| Bromodichloromethane | 2.66 µg/L No EPA limit set
worst single sample: 4.4 µg/L | 45/72 | SYR4 | 2012–2019 |
| Lead | 6.115 µg/L 41% of the EPA limit 15 µg/L
worst single sample: 15.6 µg/L | 38/90 | SYR4 | 2012–2018 |
| Nitrate-Nitrite | 375.5 µg/L 3.8% of the EPA limit 10000 µg/L
worst single sample: 460 µg/L | 34/90 | SYR4 | 2012–2019 |
| cis-1,2-Dichloroethylene | 18.35 µg/L 26% of the EPA limit 70 µg/L
worst single sample: 20 µg/L | 34/43 | SYR4 | 2012–2019 |
| Fluoride | 1100 µg/L 28% of the EPA limit 4000 µg/L | 32/32 | SYR4 | 2012–2019 |
| trans-1,2-Dichloroethylene | 0.9735 µg/L 1% of the EPA limit 100 µg/L
worst single sample: 1.8 µg/L | 32/43 | SYR4 | 2012–2019 |
| Dibromochloromethane | 6.51 µg/L No EPA limit set
worst single sample: 9.6 µg/L | 27/71 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 9.575 pCi/L 64% of the EPA limit 15 pCi/L
worst single sample: 11 pCi/L | 20/23 | SYR4 | 2012–2019 |
| Bromoform | 5.46 µg/L No EPA limit set
worst single sample: 5.8 µg/L | 18/72 | SYR4 | 2012–2019 |
| Lead | 0.0040 mg/L 27% of the EPA limit 0.0150 mg/L | 18/18 | LCR | 2025 |
| Vinyl Chloride | 2.13 µg/L 107% of the EPA limit, at the 95th percentile of samples — 2 µg/L
worst single sample: 2.3 µg/L | 18/42 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 2.16 µg/L No EPA limit set
worst single sample: 2.4 µg/L | 17/31 | SYR4 | 2012–2019 |
| Trichloroethylene | 0.6775 µg/L 14% of the EPA limit 5 µg/L
worst single sample: 0.7000 µg/L | 16/42 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 1.96 µg/L No EPA limit set
worst single sample: 2 µg/L | 9/31 | SYR4 | 2012–2019 |
| Lithium | 76.2 µg/L No EPA limit set | 7/12 | UCMR-5 | 2023 |
| Chromium | 0.3020 µg/L 0.3% of the EPA limit 100 µg/L
worst single sample: 0.3100 µg/L | 5/13 | SYR4 | 2014–2017 |
| Trichloroacetic Acid | 1.1 µg/L No EPA limit set | 4/31 | SYR4 | 2012–2019 |
| Benzene | 0.3800 µg/L 7.6% of the EPA limit 5 µg/L | 3/41 | SYR4 | 2012–2019 |
| Barium | 191 µg/L 9.6% of the EPA limit 2000 µg/L | 1/1 | SYR4 | 2017 |
| Di(2-ethylhexyl) Phthalate | 1.6 µg/L 27% of the EPA limit 6 µg/L | 1/16 | SYR4 | 2012–2018 |
78 contaminants tested, none detected
Utility contact
Frequently asked questions about Saint Louis Park
Is Saint Louis Park tap water safe to drink?
EPA monitoring detected 23 contaminants in Saint Louis Park's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Saint Louis Park's water?
EPA monitoring detected Copper, Chloroform, Bromodichloromethane, Lead, Nitrate-Nitrite, and others. The full list with the level and data source for each is above.
How many people does Saint Louis Park serve?
Saint Louis Park reports serving 50,010 people in Minnesota, per its EPA record.
Has Saint Louis Park had any water quality violations?
The EPA has 14 violations on file for Saint Louis Park, of which 14 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.